background image

ML7999A UNIVERSAL PARALLEL-POSITIONING ACTUATOR

5

65-0239—2

Fig. 5. Opening ML7999 low-voltage wiring compartment.

Fig. 6. Typical ML7999 wiring.

OPERATION

Table 1. On-Board LED Indications.

Actuator Setup

After the password (ID signal) has been written to the 

ML7999, the actuator stroke will have to be determined for the 

fuel, air and FGR, if used. The auto seek open/closed function 

can be used to find the actuator end strokes. It is important, if 

you use the auto seek open/closed function, that you move off 

the mechanical end stops of the actuator by a 

minimum of 

five degrees

. See Fig. 7.

Fig. 7. Mechanical end stop changes for auto seek open/

closed function.

CHECKOUT AND TROUBLESHOOTING

Checkout

Refer to the R7999 literature (form 66-1120) for system 

checkout.

Troubleshooting

If the actuator does not operate properly during Checkout, 

perform the following troubleshooting steps. Perform these 

steps before replacing the actuator:

1.

Check the actuator label to make sure the power and 

control signal requirements are correct for the 

application.

2.

Check for the presence of 120-240 Vac at the actuator 

(L1) and (L2) connections when the actuator should be 

driving. If the voltage is not present or is low, check the 

power supply.

3.

Ensure actuator stroke matches stroke of damper or 

valve.

a. Remove the cover.

b. Press the button labeled CW. The actuator should 

drive the device clockwise.

c. Press the button labeled CCW. The actuator should 

drive the device counterclockwise.

4.

If the actuator operates properly, check the controller for 

proper output signals.

5.

If the actuator does not drive, remove power, disconnect 

the actuator hub, and try to turn the shaft clockwise and 

counterclockwise. If the shaft turns freely throughout the 

90-degree stroke and the actuator is installed properly, 

replace the actuator.

6.

If the shaft does not turn freely for the full 90 degrees, 

check for binding. If necessary, adjust mounting to 

prevent binding.

7.

If the device shaft does not turn freely, fix or replace the 

device.

M16470

LINE VOLTAGE
WIRING

LOW 
VOLTAGE
WIRING

GND

L2

L1

DR1
DR2
CW
S
CCW

L2

L1

ML7999

R7999

M16469

1/2 IN. MAXIMUM

TERMINATE WIRE SHIELD AT THE CONTROLLER (R7999).

SEE FIGURE 5 FOR ACTUATOR WIRING.

1

2

1

2

G

LED

Online

Configured

Meaning

Notes

Fast Blink

No

Yes

Awaiting ID signal.

Responds only to ID signal.

Slow Blink

Yes

Yes

ID signal recognized.

Monitors signals for operation or offline commands.

Steady On

No

No

Actuator has failed.

Return actuator to factory.

ACTUATOR MECHANICAL OPEN/CLOSED FIXED STOPS

M19666

ACTUATOR MECHANICAL OPEN/CLOSED FIXED STOPS
MOVED MINIMUM OF 5 DEGREES

Summary of Contents for ML7999A

Page 1: ...FEATURES Universal power supply input Password protected with an eight digit hexadecimal identification signal 100 lb in 11 3 Nm torque Includes integral position feedback potentiometer Separate wiring compartment between line voltage power wiring and low voltage control Direct coupling shaft interface mounting Couples directly to a 1 2 in 13 mm shaft with no additional parts required Couples dire...

Page 2: ...differential between DR1 DR2 Drive Counterclockwise Maximum 4 25 Vdc differential between DR1 DR2 NOTE Actuator does not respond until the 8 digit ID signal from the R7999 is passed via DR1 DR2 Actuator Stroke 95 nominal 3 mechanically limited Output Hub Position Accuracy 0 1 Torque Ratings at Rated Voltages Lift and Hold Minimum 100 lb in 11 3 Nm Breakaway Minimum 100 lb in 11 3 Nm Stall Minimum ...

Page 3: ... and acid fumes can damage the actuator metal parts Install actuator in areas free of acid fumes and other deteriorating vapors Mounting ML7999 Actuator The actuator mounts on a 1 2 in round or square shaft For shafts smaller than 1 2 in self centering adapters are available for 5 16 in and 3 8 in shafts For shafts larger than 1 2 in adapters are available for 5 8 in 3 4 in and 9 16 in CAUTION Equ...

Page 4: ... Ground Earth ground is required for proper operation of the ControLinks system Earth ground provides a connection between the subbase and the control panel of the equipment The earth ground must be capable of conducting enough current to blow the fuse or breaker in the event of an internal short 1 Use wide straps or brackets to provide minimum length maximum surface area ground conductors If a le...

Page 5: ...r is low check the power supply 3 Ensure actuator stroke matches stroke of damper or valve a Remove the cover b Press the button labeled CW The actuator should drive the device clockwise c Press the button labeled CCW The actuator should drive the device counterclockwise 4 If the actuator operates properly check the controller for proper output signals 5 If the actuator does not drive remove power...

Page 6: ... does not drive replace the actuator 9 If the actuator and device shaft turn freely remount the actuator to the device according to instructions in the Installation section Make sure the actuator does not bind and that the actuator and device are both at the same clockwise or counterclockwise end stop when assembled Hook up the wires and repeat the Checkout procedures Troubleshoot if necessary ...

Page 7: ...7 65 0239 2 ...

Page 8: ...well Europe S A Honeywell Latin American Honeywell International Inc Honeywell Limited Honeywell Limitée Control Products 3 Avenue du Bourget Region 1985 Douglas Drive North 35 Dynamic Drive Honeywell Building 1140 Brussels 480 Sawgrass Corporate Parkway Golden Valley MN 55422 Scarborough Ontario 17 Changi Business Park Central 1 Belgium Suite 200 M1V 4Z9 Singapore 486073 Sunrise FL 33325 ...

Reviews: