NFC functionality and parameter settings
Parameters can be set via the supporting app using the NPC function. On the settings interface, select the "Advanced Settings" option to
configure the maximum opening, dead zones and sensitivity. After configuring the settings, move your device close to the actuator to up-
load the set parameters. A prompt will be displayed in the app indicating that the settings have been uploaded. Return to the parameter
settings interface and move your device close to the actuator to view the configured parameters.
Parameter
Set range or options
Language
Chinese, English, Auto
Valve series
V5GV, V5011P, V5013P, V5211F
Dead zone
1.0–10.0
Sensitivity
0.5–10.0
Maximum opening
30%–100%
NOTE:
1. To ensure the physical security of the device, it can only be accessed by authorized personnel.
2. Ensure the secure installation, deployment and operation and maintenance management of the device.
3. Models with NFC configuration functionality must be used in conjunction with the dedicated app provided by Honeywell.
4. Install the app on a dedicated phone, ensuring that it has not been jailbroken or that the firmware has not been replaced. Regularly scan
the phone for viruses and check the app permissions.
5. If a fault occurs during use of the app, please report the error code to Honeywell.
6. If you find a vulnerability in the security system, please contact https://www.honeywell.com/en-us/product-security
MU1B-0685GE51 R0620A