background image

PRODUCT DATA

63-2587-1

N20, N34 Series MN7220, MN7234

NON-SPRING RETURN DAMPER ACTUATOR

20/34 Nm (175/300 lb-in) FOR MODULATING CONTROL

GENERAL

These direct-coupled damper actuators provide modulating 

control for:

• rotary valves,

• air handling units,

• ventilation flaps,

• louvers, and

• reliable control for air damper applications with up to 50 

sq.ft. (20 Nm / 175 lb-in) or 85 sq. ft. (34 Nm / 300 lb-in) 

(seal-less damper blades; air friction-dependent).

FEATURES

• New self-centering shaft adapter
• Access cover to facilitate connectivity
• Declutch for manual adjustment
• Mechanical end limits (MN7220 only)
• Field-installable auxiliary switches
• Rotation direction selectable by switch
• Mountable in any orientation (no IP54 if upside down)
• Mechanical position indicator

SPECIFICATIONS

Supply voltage

24 Vac 

±

20%, 50/60 Hz;

24 Vdc -10...+20%

Nominal voltage

24 Vac, 50/60 Hz; 24 Vdc

All values stated hereinafter apply to operation under 

nominal voltage conditions.

Power consumption

MN7220

6 VA / 6 W

MN7234

8 VA / 6 W

Ambient limits

Ambient operating limits

-5...+140 °F (-20...+60 

°

C)

Ambient storage limits

-40...+175 °F (-40...+80 

°

C)

Relative humidity

5...95%, non-condensing

Safety

Protection standard

IP54 (non-USA models)
NEMA2 (USA models)

Protection class

II as per EN 60730-1

Overvoltage category

II

Lifetime

Full strokes

60000

Repositions

1.5 million

Mounting

Round damper shaft

3/8...1-1/16” (10...27 mm)

Square damper shaft

3/8...11/16” (10...18 mm);
45° steps

Shaft length

min. 7/8” (22 mm)

Control signal

0(2)...10 Vdc
0(4)...20 mA

Input impedance

100 k

Ω

 [0...10 V]

500 

Ω

m [0...20 mA]

Feedback signal

Limits

±

 1 mA at 0...10 V

Auxiliary switch (when included)

Rating

5 A (resistive) / 3 A (inductive)

Triggering points

5

°

 / 85

°

Torque rating

MN7220

175 lb-in (20 Nm)

MN7234

300 lb-in (34 Nm)

Runtime

95 sec (60 Hz) / 110 sec (50 Hz)

Rotation stroke

95

°

 

±

 3

°

Dimensions

see “Dimensions” on page 8

Weight

3 lbs. (1.35 kg)

Noise rating

40 dB(A) max. at 1 m

Summary of Contents for MN7220

Page 1: ...ltage 24 Vac 50 60 Hz 24 Vdc All values stated hereinafter apply to operation under nominal voltage conditions Power consumption MN7220 6 VA 6 W MN7234 8 VA 6 W Ambient limits Ambient operating limits 5 140 F 20 60 C Ambient storage limits 40 175 F 40 80 C Relative humidity 5 95 non condensing Safety Protection standard IP54 non USA models NEMA2 USA models Protection class II as per EN 60730 1 Ove...

Page 2: ...ct Identification System OPERATION FUNCTIONS Fig 2 Setting units and control elements Legend for Fig 2 Setting units and control elements 1 Self centering shaft adapter 2 Retainer clip 3 Rotational angle scales 0 90 90 0 4 Mechanical end limits 20 Nm 175 lb in models only 5 Declutch button 6 Anti rotation bracket 7 Rotation direction switch 8 Access cover 9 Internal auxiliary switch wire 10 Power ...

Page 3: ...hes view with PCB at bottom Autoadapt Dip Switch for Normal Operation In its default shipping position the autoadapt dip switch for normal operation is set to ON as shown in Fig 4 Dip switches view with PCB at bottom 4 If it is set to OFF no autoadapting is performed and the control signal map remains constant The autoadapt functionality does not have to be triggered Rather the SmartAct actuator d...

Page 4: ...8 Specifically it is important that they properly mesh with the rotational angle scales when the screws are tightened Fig 8 Correct incorrect tightening of end limits Internal Auxiliary Switches The internal auxiliary switches are set to change from common to normally open at angles of 5 and 85 respectively from the totally counterclockwise position Fig 9 Internal auxiliary switches Override If te...

Page 5: ...round In the case of short shafts the shaft adapter may be reversed and mounted on the duct side Stroke Limitation with Mechanical End Limits The mechanical end limits 20 Nm 175 lb in models only enable the stroke to be limited from 0 90 in increments of 3 Wiring Access cover To facilitate wiring the actuator to the controller the access cover can be detached from the actuator IMPORTANT Remove pow...

Page 6: ...ety isolating transformer connecting cable terminal name supply and signal lines 1 24 Vac 24 Vdc 2 24 Vac 24 Vdc 3Y 0 2 10 Vdc 0 4 20 mA control signal 5U 0 2 10 V feedback signal auxiliary switched when included CCW left 5 S1 Common S2 normally closed S3 normally open CW right 85 S4 Common S5 normally closed S6 normally open AUXILIARY S1 S2 S3 S4 S5 S6 S3 S2 S1 S6 S5 S4 AUXILIARY TERMINAL STRIP 2...

Page 7: ...N20 N34 SERIES MN7220 MN7234 7 63 2587 1 ...

Page 8: ...om N20 N34 SERIES MN7220 MN7234 U S Registered Trademark 2005 Honeywell International Inc 63 2587 1 M S Rev 10 05 DIMENSIONS 60 30 0 90 shaft adapter shaft adapter reverse anti rotation bracket 100 mm 3 15 16 20 6 mm 1 3 16 48 mm 1 7 8 95 223 mm 8 25 32 92 mm 3 5 8 1000 mm 39 5 mm 0 05 0 10 mm 25 128 0 002 0 004 2 mm 5 64 20 mm 25 32 13 mm 1 2 7 mm 9 32 132 mm 5 3 16 min 60 mm 2 3 8 230 mm 0 5 mm ...