VB6 SERIES 6-WAY CONTROL BALL VALVES AND ACTUATORS - INSTALLATION INSTRUCTIONS

 9

Printed in USA

31-00380M-02

IMPORTANT:

 

The zero (closed) position of the valve can be 

achieved with control signal as shown in the 

below table.

Floating/2-Position Run Mode 

(Not recommended)

Using  the  MN7510A2001  actuator  in  floating  /

2-position mode is not recommended with 6-way

valves.    Both  Sequence  1  and  Sequence  2  are

closed  at  the  actuator  mid-stroke,  45  degree

actuator  rotation.  It  must  be  possible  to  com

-

mand  the  actuator  to  position  itself  in  the  mid-

stroke position, which is difficult to do with preci

-

sion in floating mode, and impossible when float

-

ing mode is used for 2-position control. 
If  it is  desired  to  use the 6-way  valve for simple

seasonal  changeover  service,  it  is  best  if  three

distinct positions can be achieved: 

1. Fully clockwise actuator rotation for 

Sequence 2 to be fully open.

2. Fully counterclockwise actuator rotation for 

Sequence 1 to be fully open.

3. Exactly mid-stroke, 45-degree actuator 

rotation, for Sequence 1 and 2 both being 

closed.

This scheme can only be achieved with the actu

-

ator selector switch set to one of the four modu

-

lating  modes,  using  0-10  Vdc,  2-10  Vdc,  10-0

Vdc,  or  10-2  Vdc  to  achieve  full  clockwise,  full

counterclockwise, and precisely mid-stroke actu

-

ator  positions.  If  desired,  the  actuator  analog

feedback can be used to verify actual position.
If only step 1 and 2 above are desired, and there

is  no  need  for  step  3  to  rotate  the  actuator  to

exactly 45 degrees to turn both Sequence 1 and

2 completely off, the floating mode may be used

for 3-wire 2-position control.

Power-Off Behavior

If power is removed, the shaft adapter remains in

position.

Service/Off Mode

If the function selection switch is set to the “Ser

-

vice/Off”  position,  then  all  rotary  movement  is

canceled,  and  all  control  signals  are  ignored,

allowing  the  actuator  to  be  manually  operated

safely. Press and hold the De-clutch button and

use  the  handle  to  operate  the  actuator  to

Sequence 1, 2, or, Off positions.

Overriding

The  MN7510A2001  can  be  overridden  to  the

50% position by applying a 24 V signal to termi

-

nal 4 (see Figure 13.) With 24 V signal applied the

actuator will ignore the control signal at terminal

3 and instead drive to the 50% position closing

both Sequence 1 and Sequence 2.

Feedback

If correspondingly wired via terminal 5 (see Fig

-

ure  13  to  Figure  15),  the  actuator  provides  a

feedback  signal proportional  to the  actual  posi

-

tion of the shaft adapter.

Valve closed command  (45 

degree actuator rotation)

Actuator Control 

Signal Setting

Controller 

Output

0-10 Vdc

5Vdc

2-10 Vdc

6 Vdc

10-0 Vdc

5Vdc

10-2 Vdc

6 Vdc

Summary of Contents for MN7510A2001

Page 1: ... use in chilled water and hot water closed loop applications only with a media temperature range of 0 ºF to 212 ºF 18 ºC to 100 ºC and static pressures up to 600 psi These valves are to be operated with the Honey well MN7510A2001 actuator only Water should be properly filtered treated and conditioned for good operating performance according to local conditions and recommenda tions of the boiler or...

Page 2: ...rd Foreign particles like dirt and metal chips can damage the ball seals For trouble free operation of the product good installation practice must include initial system flushing and chemical water treatment Clean the lines upstream of particles larger than 1 16 inch diameter welding slag pipe scale sand and other suspended particulate Use of a 50 micron or finer system side stream filter is sugge...

Page 3: ...valve to the supply and return pipes of the coil 6 Connect the A ports and B ports as per the flow sequences Refer to below figure Figure 1 Typical flow directions for Sequence 1 and 2 IMPORTANT Strictly follow flow direction and port connec tions as per flow sequences 7 Clear threads on both valve and piping of any debris Honeywell recommends Permabond A1044 or equivalent thread or pipe sealant W...

Page 4: ...g 1 Use a suitable plier to hold the clip of the Uni versal shaft adapter 2 Pull out the Clip as shown in below figure to remove Universal shaft adapter Now the actuator is ready to assemble on 6 way control ball valve Assembling the actuator on Valve body 1 Make sure that the Gear box is in zero posi tion as shown in below figure Use the appro priate wrench to adjust if necessary Figure 4 Zero po...

Page 5: ...to any position Rotate the Stem adapter so that the notch on the Stem adapter points as shown in figure below Figure 7 Adjusting the Stem adapter to zero position 5 Slide the Brass sleeve over the end of the Stem adapter as shown in figure below Figure 8 Assembly of Brass sleeve 6 Place the actuator assembly on the Valve body as shown in below figure Figure 9 Assembly on the Valve body IMPORTANT T...

Page 6: ...pressing it downwards press fit to assemble it firmly Figure 11 Mounting of Handle on the actuator Manual Adjustment IMPORTANT To prevent equipment damage you must remove power or set the function selection switch to the Service Off position before manual adjustment After removing power or setting the function selection switch to the Service Off position the Gear box can be disengaged using the De...

Page 7: ... use the appropriate electrical cable conduits and cable gland to properly secure the actuator wiring 4 Replace the wiring cover once done Actuator Run modes The function selection switch see Figure 16 can be used to place the actuator into any one of two different modes Modulating run mode Floating 2 position run mode Service Off mode Caution To avoid personal injury electrical shock and to preve...

Page 8: ... 13 then as soon as operating power is applied the shaft adapter will run first completely counterclockwise and then completely clockwise after which it will run according to the control signals applied Use the above flow curve with given actuator control signal settings to configure 6 way valve for Sequence 1 cooling Sequence 2 and Off position Note that in Figure 13 it is shown how to over ride ...

Page 9: ...hieve full clockwise full counterclockwise and precisely mid stroke actu ator positions If desired the actuator analog feedback can be used to verify actual position If only step 1 and 2 above are desired and there is no need for step 3 to rotate the actuator to exactly 45 degrees to turn both Sequence 1 and 2 completely off the floating mode may be used for 3 wire 2 position control Power Off Beh...

Page 10: ... 0 95 CV 0 46 0 33 0 40 0 46 0 65 0 80 0 92 1 03 1 13 1 22 1 30 1 38 1 45 CV 0 80 0 57 0 69 0 80 1 13 1 39 1 60 1 79 1 96 2 12 2 26 2 40 2 53 CV1 20 0 85 1 04 1 20 1 70 2 08 2 40 2 68 2 94 3 17 3 39 3 60 3 79 CV 1 90 1 34 1 65 1 90 2 69 3 29 3 80 4 25 4 65 5 03 5 37 5 70 6 01 CV 3 00 2 12 2 60 3 00 4 24 5 20 6 00 6 71 7 35 7 94 8 49 9 00 9 49 CV 4 70 3 32 4 07 4 70 6 65 8 14 9 40 10 51 11 51 12 44...

Page 11: ...NS Dimension of Valve body Table 2 Dimensions Valve nominal size A B C D E F Valve Body Inch inch mm inch mm inch mm inch mm inch mm inch mm VB6A 1 2 6 85 174 2 76 70 6 63 168 5 33 135 4 14 105 3 77 95 VB6B 3 4 7 01 178 3 07 78 6 92 176 5 46 139 4 15 105 4 09 104 Figure 18 Dimension of VB6 series 6 way control valve ...

Page 12: ...ll makes no representations or warranties with respect to this document In no event shall Honeywell be liable for technical or editorial omissions or mistakes in this document nor shall it be liable for any damages direct or incidental arising out of or related to the use of this document No part of this document may be reproduced in any form or by any means without prior written permission from H...

Reviews: