SERIES 90 MODUTROL IV

 MOTORS

63-2631—07

4

Table 2.  Power Consumption Ratings.

Table 3. Auxiliary Switch Ratings (in Amps).

a

40 VA pilot duty, 120/240 Vac on opposite contact.

Timing And Torque: 

Refer to Table 5.

Approvals:

Underwriters Laboratories Inc. Listed: File No. E4436, Guide 

No. XAPX to US and Canadian standards.

U.S. Patents: pending

Table 4. Primary 50017460-001 Color Code

All Transformers have brown secondary (24 VAC) wires.

Table 5. Series 90 Modutrol Motor Timing and Torque Ratings.

a

Timings apply to all TRADELINE models. Some OEM models are available with non-standard timing/torque.

b

The torque rating for dual-ended shaft motors is the sum of the shaft torques (power-end torque plus auxiliary-end torque).

c

Breakaway torque is maximum torque available to overcome occasional large loads such as a seized damper or valve.

d

Low timing is for M9184D1005 only.

NOTE: Some 150 lb-in. and 300 lb-in. torque adjustable stroke motors have timings that are twice that of the nominal timing.

IMPORTANT

Never use a Modutrol Motor continuously at the 

Breakaway Torque rating.

Accessories:

220736 Internal Auxiliary Switch Kit can be field-installed. 

One- (220736A) and Two- (220736B) switch kits available.

220738A Adapter Bracket raises motor shaft height by 19 mm 

to match that of previous Modutrol Motor models.

220741A Screw Terminal Adapter converts the standard 

quick-connect terminals to screw terminals.

221455A Infinitely Adjustable Crank Arm approximately 0.75 

inch shorter than the 4074ELY Crank Arm, can rotate 

through downward position and clear base of motor without 

requiring use of adapter bracket.

221508A Resistor Board plugs onto Series 90 Motor quick-

connect wire terminals. Provides same functionality as 

4074BYK, 4074EAU, 4074EDC, or 4074EED Resistor Kits.

4074BYK Series 90 Resistor Kit provides for unison control of 

up to six Series 90 Motors.

4074EAU W973 Resister Kit provides for control of two or three 

Series 90 Motors from a W973 Single-zone Logic Panel or 

W7100 Discharge Air Controller.

4074EDC 4-20 mA Resistor Kit drives one Series 90 Motor 

from a 4-20 mA controller.

4074EED Unison Control 4-20 mA Resistor Kit provides for 

control of up to four Series 90 Motors from one 4-20 mA 

controller.

4074ERU Weatherproofing Kit provides NEMA 3 rating for 

Modutrol IV Motors mounted in position other than upright.

50017460-001 Internal Transformer; 24/120/230 Vac 50/60 Hz 

primary, 24 Vac secondary, quick connect terminals.

50017460-003 Internal Transformer; 120 Vac 50/60 Hz pri-

mary, 24 Vac secondary, quick connect terminals.

7617ADW Crank Arm approximately 0.75 inch shorter than 

7616BR Crank Arm. Can rotate through downward position 

and clear base of motor without requiring use of adapter 

bracket.

Q100 Linkage connects Modutrol Motor to V51 Butterfly Valve. 

Requires the 220738A adapter bracket (packed with 

TRADELINE Modutrol IV Motors).

Power Consumption

Family

VA Rating

M9161V

10

M9164

10

M9172W

20

M9174

12

M9175B

20

M9181D

10

M9182A

15

M9182D

20

M9184

15

M9185

20

M9186G

20

M9191F

15

Single Contact Rating

a

120 V

240 V

Full Load

7.2

3.6

Locked Rotor

43.2

21.6

Lead Color

Primary Voltage

Brown

24 VAC

White

120 VAC

Blue

230 VAC

Black

Common

Nominal Timing

a

 in sec

Rated Torque in lb-in. (N•m)

b

Normal Running Torque

Breakaway Torque

c

90°

160°

Spring Return

Non-Spring Return

Spring Return

Non-Spring Return

30

60

35 (4)

70 (8)

15

d

/30

30

d

/60

60 (6.8)

75 (8.5)

120 (13.6)

150 (17)

30

60

150 (17)

300 (34)

60

120

300 (34)

600 (68)

Summary of Contents for Modutrol IV M9175D 1014

Page 1: ...eight of older motors is available Motors have field adjustable stroke 90 to 160 Die cast aluminum housing Integral auxiliary switches are available factory mounted or can be field added Nominal timing standard of 30 seconds 90 stroke and 60 seconds 160 stroke Other timings available Spring return motors can operate valve linkages form power end or auxiliary end shafts for normally closed or norma...

Page 2: ...Number Guide See Table 1 Table 1 Modutrol IV Series 2 and 3 Model Number Guide NOTE Torque designation corresponds to torque rating at standard timing nominally 60 sec for 160 and 30 sec for 90 except for 300 lb in motors which have timings of 2 or 4 min Dimensions Refer to Fig 2 Electrical Ratings Refer to Table 2 Control Inputs Proportional Series 90 NOTE Motor Series 90 control can be either El...

Page 3: ...ROKE 160 DEGREE STROKE NON SPRING RETURN MOTORS 160 10 90 45 SPRING RETURN MOTORS AND NON SPRING RETURN MOTORS ASYMMETRICAL MOTORS SYMMETRICAL MOTORS M18998D 4 7 8 124 5 1 2 140 13 16 20 4 1 16 103 1 4 7 1 1 2 37 5 1 2 140 JUNCTION BOX MOTOR AUXILIARY END POWER END ADAPTER BRACKET 2 9 16 66 5 3 8 137 6 7 16 164 9 16 15 3 4 19 TOP VIEW OF BRACKET TOP VIEW 4 5 8 116 4 1 4 107 2 5 16 58 11 16 17 4 7 ...

Page 4: ...stor Board plugs onto Series 90 Motor quick connect wire terminals Provides same functionality as 4074BYK 4074EAU 4074EDC or 4074EED Resistor Kits 4074BYK Series 90 Resistor Kit provides for unison control of up to six Series 90 Motors 4074EAU W973 Resister Kit provides for control of two or three Series 90 Motors from a W973 Single zone Logic Panel or W7100 Discharge Air Controller 4074EDC 4 20 m...

Page 5: ...ns and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service techni cian 4 After installation is complete check out product opera tion as provided in these instructions CAUTION Electrical Shock or Equipment Damage Hazard Can shock individuals or short equipment circuitry Disconnect all power supplies before installation Motors wi...

Page 6: ... except the Q5001 To mount the motor with the bracket See Fig 3 1 Mount the bracket to the equipment with existing or stan dard bolts 2 Using the provided bolts mount the motor to the bracket threaded holes For valve linkage applications other than the Q5001 1 Mount the bracket to the linkage 2 Position the motor on the bracket to align the motor shaft with the linkage 3 Attach the motor to the br...

Page 7: ...pply VA rating is large enough to provide power to all motors used without overloading 3 Fig 11 shows that the motor terminals are quick connects located on top of the printed circuit board 4 To access the wiring compartment a Remove the four screws from the junction box top b Lift off the cover 5 Refer to Fig 5 for typical wiring and Fig 7 for internal auxiliary switch connections NOTE Reverse mo...

Page 8: ...PROTECTION AS REQUIRED TRANSFORMER MAY BE INTERNAL OR EXTERNAL M770A SERIES 90 CONTROLLER MOTOR L1 HOT L2 1 1 2 R W B R W B T1 T2 TRANSFORMER POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED TRANSFORMER MAY BE INTERNAL OR EXTERNAL M13708 135 OHM POTENTIOMETER MOTOR BLUE LEAD YELLOW LEAD RED LEAD USE NEC CLASS 1 WIRING UNLESS POWER SUPPLY MEETS CLASS 2 REQUIREMENTS TAPE UNU...

Page 9: ...6284D4004 S M6285A1005 S M6285A1054 S M6285A4009 S 600 Ohms No Yes No 187 Ohm M6274F1009 F M6284F1070 F M6284F1078 F M6285F1001 F M6294F1009 F M6294F1017 F M6284D1032 F 10 K Ohms No No Yes Not Available M6284A1071 S M6284A1089 S M6284C1028 S 196 346 Ohms Yes Yes No 274 Ohm M6284A1030 S M6284A1055 S M6284A1097 S M6284B1004 S M6284C1010 S M6284C1044 S M6284F1013 S M6284F1039 S M6285A1039 S M6285A104...

Page 10: ... Motors Adjustable timing for M9182D1023 The timing potentiometer the second from the right Refer to Fig 10 sets the timing to 1minute if turned fully CCW 2 minutes if turned to its middle point and 4 minutes if turned fully CW CAUTION Careless Installation Hazard Use of excessive force while adjusting cams damages the motor To avoid damaging motor end switches set cams by moving only the top of t...

Page 11: ...oth directions 9 Disconnect the potentiometer reconnect the controller and replace the motor top cover NOTE Changing the differential from 1 to 10 reverses the switching action For example with a 10 dif ferential switch contacts R B make and R W break on a counterclockwise closed rotation With a 1 differential switch contacts R W make and R B break on a counterclockwise closed rotation OPERATION U...

Page 12: ...IFF MOTOR OPEN MOTOR CLOSE POWER END OUTER AUXILIARY CAM BLUE LEFT OUTER AUXILIARY SWITCH FAST RISEPORTION APPROX 1 DIFF 1 8 INCH STRAIGHT BLADE SCREWDRIVER RIGHT INNER AUXILIARY SWITCH SLOW RISE PORTION APPROX 10 DIFF INNER AUXILIARY CAM RED FAST RISE PORTION APPROX 1 DIFF FAST RISE PORTION APPROX 1 DIFF SLOW RISE PORTION APPROX 10 DIFF MOTOR OPEN MOTOR CLOSE POWER END OUTER AUXILIARY CAM RED LEF...

Page 13: ...the old motor 2 Remove the crank arm from shaft of old motor and remove the old motor 3 Determine necessity of the mounting bracket If the link age can reach the new motor shaft position and the crank arm has clearance for the necessary rotation the bracket is not required Use the 220738A Adapter Bracket or the 221455A Crank Arm if the crank arm must rotate through the bottom plane of the motor a ...

Page 14: ...SERIES 90 MODUTROL IV MOTORS 63 2631 07 14 ...

Page 15: ...SERIES 90 MODUTROL IV MOTORS 15 63 2631 07 ...

Page 16: ... liability for any damages arising out of your use or modification to the literature You will defend and indemnify Honeywell its affiliates and subsidiaries from and against any liability cost or damages including attorneys fees arising out of or resulting from any modification to the literature by you ...

Reviews: