5 Level 2 Display / Control Functions
5.1 Display
Functions
•
All of the display functions available at Level 1 are also available at Level 2.
5.2 Control
Functions
•
The four main control keys are locked at Level 1 (Note: Mute Buzzer key is always enabled). To
enable the Level 2 control functions, press any control key and the following display will be shown:
CONTROL KEY LOCKED – ACCESS REQUIRED
Enter Level 2/3 passcode
←
:BackSp
•
Enter the Level 2 pass-code (for example, the default pass-code is 1234) using the
number
buttons.
As each number is entered, a
‘*’
character is shown on the display. When all four digits have been
entered, press the
‘
9
’
key. (If a wrong number key is pressed, press the
Í
key to erase the number
entered and re-enter the correct / required number).
•
If the pass-code is correct, the display will revert to the normal display. Level 2 access will remain available
for 5-minutes (programmable). Press the required control to perform the desired action – see below.
•
If the pass-code is entered incorrectly, the display will show the following message for 60 seconds.
Press the
‘X’
button to revert immediately to the normal displays. The eight-character number on the
bottom line is a control code and is only relevant to Level 3 use.
ERROR – INCORRECT PASSCODE !!!
C8B0E488
•
Alternatively, if the key-switch option is fitted and programmed to enable Level 2 access, insert the key
and turn clockwise to enable Level 2 Control functions.
5.2.1 Sound Alarms / Evacuate
To activate all sounder outputs and evacuate the building press the SOUND ALARMS key.
5.2.2 Silence / Resound Alarms
To silence the sounder outputs press the SILENCE / RESOUND key.
To reactivate all silenced sounder outputs press the SILENCE / RESOUND key again.
5.2.3 Accept / Delayed Day Mode Alarms
If the system is programmed to operate with the Delayed Day Mode function the panel will
indicate the alarm but will not immediately activate the outputs (sounders or relays). Press the
ACCEPT key to acknowledge the alarm and enter the Investigation Phase – refer to Section 6
for further information.
5.2.4 Reset
To reset the panel from a fire alarm or fault condition, firstly correct and rectify the problem and
then press the RESET key. To prevent fault conditions being registered from faulty devices
disable the device – refer to the Enable / Disable Menu.