MORLEY-IAS
Dimension
Series
Page 24
Document No. 996-148-000-5, Revision: 5
User Manual
5.3.1.3.2 Configuring / Stopping Individual Zone Tests
•
To configure or stop the testing of one or more zones individually, press
‘1’
and a new display is
shown from which the zones to be tested can be selected as follows:
[WALK TEST] Zone 1: NOT IN TEST
R
:Select Zone
←→
:Change X:Exit
•
The display shows the current test state for Zone 01.
•
Press
the
Ï
and
Ð
keys to select the required zone.
•
Press
the
Í
or
Î
keys to change the test status of a zone. There are three options: NOT IN TEST, IN
TEST WITH SOUNDERS, IN TEST – NO SOUNDERS and each button press cycles through the options.
•
If an alternate test is selected, after about 2-seconds, the display will prompt for confirmation that this
state should be entered as follows:
[WALK TEST] Zone 1: IN TEST WITH SNDRS
Press
9
to confirm X:Exit
•
Press
the
‘
9
’ key to confirm the change of test state or press the
‘X’
key to cancel any changes.
•
Repeat for each zone as required.
5.3.1.3.3 Stopping ALL Zone Tests
•
Press
‘2’
to select the stop all tests option. The display then shows:
Stop all Zones in Walk Test ?
Press
9
to confirm X:Cancel
•
Press
the
‘
9
’ key to confirm the termination of all zone (walk) tests or press the
‘X’
key to cancel and
keep the configured zones in the test condition. The display then returns to the zone test menu.
•
Remember to ensure that call points are returned to their normal condition and allow sufficient time for
smoke to clear from smoke detectors before stopping any zone tests. Otherwise, a full fire alarm
condition may result.
5.3.1.4 Output
Test
•
To select the option, press
‘4’
. The display shows the following menu options to test outputs internal to
the panel or outputs connected to the detection loop.
[U0 Outputs] 1:Internal 2:Loop
•
NOTE: Any output test in progress will automatically be cancelled after 60-seconds if no button is
pressed.