MORLEY-IAS
Dimension
Series
Page 4
Document No. 996-148-000-5, Revision: 5
User Manual
1.5 EN54
Information
EN54
9
•
This Fire Alarm Control Panel complies with the requirements of EN54-2/4. In addition
to the basic requirements of EN54, the panel conforms to the following optional
functions.
Option EN54-2
Clause
Indication:
Alarm
counter
7.13
Fault signals from points
8.3
Controls:
Delays to outputs
7.11.1
Manual or automatic switching of delays to outputs
7.11.2
Dependency on more than one alarm signal: Type C
7.12.3
Disablement of each address point
9.5
Test
condition
10
Outputs:
Outputs to fire alarm device(s)
7.8
EN54
9
•
The power supplies for the Dimension Series of panels comply with the following
clauses of EN54-4.
DX1/2/4e Power Supply Functions
EN54-4 Clause
Derive power supply from main power source
Derive power supply from a standby battery source
Charge and monitor the standby battery source
Detect & signal power supply faults
5.1
5.2
5.3
5.4
EN54
N/A
•
In addition to the functions required by EN54-2, the panel supports a number of
ancillary functions that are not required by EN54. These are outlined below:
Ancillary Function
Manual Section
Auxiliary supply output
Refer to Product Manual
Peripheral loop output & supported devices
Refer to Product Manual
Auxiliary relay outputs
Refer to Product Manual
Printer option
8
Class Change Input
7.2
Group Disable
5.3.5.3