INSTALLATION INSTRUCTIONS

Copyright © 1996 Honeywell Inc.   •   All Rights Reserved

MP909E

UL Listed Damper Actuator

BEFORE INSTALLATION

The MP909E UL Listed Pneumatic Damper Actuator is used
for control of Leakage Rated (Smoke) Dampers, classified
under Underwriters Laboratories Standard 555S, for use in
smoke control systems. The MP909 is a piston-type, rolling-
diaphragm operated actuator and can be mounted in any
position and installed either externally or internally.

The UL listing of the actuator and the damper classification
apply only when Listed Honeywell Actuators are installed on
Honeywell D640SD, D641SD, D644SD, or D645SD Series
Dampers as specified in the installation instructions shipped
with the devices.

All installations must also comply with the requirements of
NFPA 90A, National Fire Protection Standard for the
Installation of Air Conditioning Systems.

Table 1 lists the only MP909 Actuators approved for use with
UL Classified Leakage Rated (Smoke) Dampers.

Table 1. Damper Actuators for Leakage Rated Dampers.

Actuator

Model

Spring Range

psi (kPa)

Mounting

Bracket

MP909E1422

5-10 (34-69)

Internal/

Normally

Open

Trunnion

MP909E1414

5-10 (34-69)

Internal/

Normally

Closed

Trunnion

MP909E1034

5-10 (34-69)

External

90

°

 Fixed

MP909E1364

5-10 (34-69)

External

Trunnion

Mainline pressure limits:

15 psi minimum

25 psi maximum

Tools needed:

1. 7/16-inch box end wrench
2. 1/8-inch Allen wrench
3. Squeeze bulb

INSTALLATION

External Mounting

1

For external mounting dimensions, see Figure 1.

2

Check faceplate position (Fig. 2). Adjust faceplate
position if necessary.

3

Determine the damper drive axle direction of rotation to
the normal position (position with 0 psi applied to
actuator).

4

Rotate damper drive axle to normal position.

5

Locate proper shaft hole (Fig. 3) over damper shaft.
Arrow on bracket surrounding hole should match
rotation determined in Step 3.

6

Position mounting bracket.

7

Secure mounting bracket. Use four of the 10 holes
available in bracket and drill screws provided.

8

To provide close-off force, use a squeeze bulb and
stroke the actuator:

a.

For normally open dampers, fully extend actuator
shaft then retract 1/2-inch (13 mm).

b.

For normally closed dampers, extend actuator
shaft 1/2-inch (13 mm).

CAUTION

See Figure 4 for proper tightening of crankarm bolts.

9

Go to PIPING section.

Internal Mounting

Normally Closed

1

For normally closed internal mounting dimensions, see
Figure 5.

2

Check faceplate position (Fig. 6). Adjust faceplate
position if necessary.

3

Use a 1/8-inch Allen wrench to loosen mounting set
screws on damper mounting clamp (Fig. 6) one turn.
Remove and discard shipping stop.

4

Locate factory-installed drive ear on damper. (Mounted
per Damper Ordering Instructions.) Actuators must be
mounted only in this (these) position(s)

95-6076

11-95 UL

Summary of Contents for MP909E

Page 1: ... pressure limits 15 psi minimum 25 psi maximum Tools needed 1 7 16 inch box end wrench 2 1 8 inch Allen wrench 3 Squeeze bulb INSTALLATION External Mounting 1 For external mounting dimensions see Figure 1 2 Check faceplate position Fig 2 Adjust faceplate position if necessary 3 Determine the damper drive axle direction of rotation to the normal position position with 0 psi applied to actuator 4 Ro...

Page 2: ... 1 INCH STROKE OPERATORS AND N C DAMPERS 1 1 Fig 2 External Mounting Faceplate Positioning Fig 3 External Installation 5 Remove mounting screw from damper end of truss link Loosen screw between base and truss link Remove clevis pin from damper end of actuator pushrod 6 Set actuator in place by hooking actuator mounting clamp over bottom edge of damper frame 7 Set damper to the normal closed positi...

Page 3: ...Mounted Normally Closed Mounting Dimensions in Inches Millimeters 3 8 10 CLEARANCE 17 430 EDGE OF DAMPER 6 3 8 160 C8210 FACEPLATE PARALLEL TO BACK EDGE OF MOUNTING BRACKET C8212 TRUSS LINK TRUSS LINK MOUNTING SCREW 1 1 FACEPLATE PIVOT PLATE PUSHROD 1 13 32 INCH 36 MM REF DAMPER DRIVE EAR E HOLE CLEVIS PIN P HOLE DAMPER MOUNTING CLAMP SHIPPING STOP SETSCREWS MOUNTING BRACKET PUSHROD DAMPER DRIVE E...

Page 4: ...er drive ear with clevis pin J Tighten set screws on mounting clamp K Connect truss link to damper and tighten both truss link screws Truss link must be bent slightly 17 430 EDGE OF DAMPER 6 1 2 165 C8213 MP909E Fig 7 Internal Mounting Normally Open Dimensions in Inches Millimeters C8214 1 1 REFERENCE DIMENSIONS 4 INCH STROKE FACTORY SET 3 3 16 INCH 81 MM CLEVIS PIN C CLEVIS PIN B FACTORY INSTALLE...

Page 5: ...E BRASS FERRULE WITH RED FERRULE CCT1574 NOTE ORIENTATION REPLACE BRASS FERRULE 1 4 IN BARBED FITTING ACTUATOR C8217 TO CONTROLLER NUT NUT 1 4 IN COPPER TUBING Fig 10 Transition Piping for 1 4 Inch Barbed Fitting to 1 4 Inch Copper Tubing C8215 DAMPER FRAME DUCT FLOOR 1 4 IN COPPER TUBING MP909E ACTUATOR Fig 11 Routing Copper Tubing Near Trunnion Pivot Multiple Actuators Multiple actuators must be...

Page 6: ...u Control Your World Home and Building Control Honeywell Limited Honeywell Limitée 155 Gordon Baker Road North York Ontario M2H 2C9 95 6076 1 96 Printed in U S A Home and Building Control Honeywell Inc Honeywell Plaza P O Box 524 Minneapolis MN 55408 0524 ...