background image

1

 

N05, N10 SERIES 

NON-SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS FOR 
MODULATING AND FLOATING CONTROL 

                                                                                                                                

 PRODUCT DATA 

 

GENERAL 

This non-spring return direct-coupled damper actuator  
provides modulating and floating/2-position control for:  
•   air dampers, 
•   VAV units, 
•   air handlers, 
•   ventilation flaps, 
•   louvers, and 
•   reliable control for air damper applications with up to 10 sq ft 

/ 44 lb-in. (5 Nm) and 20 sq ft / 88 lb-in. (10 Nm) (seal- less 
damper blades; air friction-dependent). 

FEATURES  

•  

Declutch for manual adjustment 

•  

Adjustable mechanical end limits 

•  

Removable access cover for direct wiring 

•  

Mountable in any orientation 

•  

Function selection switch for selecting modulating or 

floating/2-position control 

SPECIFICATIONS 

Supply voltage

 

24 Vac/dc -15%/+20%, 50/60 Hz 

Nominal voltage

 

24 Vac/dc, 50/60 Hz 

All values stated hereinafter apply to operation under 
nominal voltage conditions. 

Power consumption

 

CN7505 

5 VA / 2 W 

CN7510 

5 VA / 2 W 

Control signal

 

Modulating (0)2...10 

Vdc 

Floating/2-Position 24 

Vac/dc 

Ambient limits 
Ambient operating limits 

-5...+140 °F (20...+60 °C) 

Ambient storage limits 

-22...+176 °F (-30...+80 °C) 

Relative humidity 

5...95%, non-condensing 

Safety

 

Protection standard 

IP54 

Protection class 

II as per EN 60730-1 

Overvoltage category 

II 

Lifetime

 

Full strokes 

60000 

Repositions 1.5 

million 

Mounting

 

Round damper shaft 

3/8 in…5/8 in. 

Square damper shaft 

1/4 in…1/2 in.; 45° steps 

Shaft length 

min. 1-5/8 in. 

 End switches (when included)

 

Rating Class 

II 

Triggering points                 5° / 85° 

Torque rating

 

44 lb-in. (5Nm) / 88 lb-in. (10Nm) 

Rotation stroke

 95° 

+ 3°  

Dimensions 

see “Dimensions” on page 8 

Weight (without cables)

 1.0 

lbs. 

Noise rating

 

35 dB(A) max. at 1 m 

 

63-6233T 

CN0B-0545CH33 R0805 

Summary of Contents for N05 Series

Page 1: ...ge 24 Vac dc 15 20 50 60 Hz Nominal voltage 24 Vac dc 50 60 Hz All values stated hereinafter apply to operation under nominal voltage conditions Power consumption CN7505 5 VA 2 W CN7510 5 VA 2 W Control signal Modulating 0 2 10 Vdc Floating 2 Position 24 Vac dc Ambient limits Ambient operating limits 5 140 F 20 60 C Ambient storage limits 22 176 F 30 80 C Relative humidity 5 95 non condensing Safe...

Page 2: ...ent is cancelled and all control signals are ignored thus allowing the actuator to be manually operated safely Floating 2 Position Run Mode Without Feedback Signal If however the function selection switch has been set to one of the two floating 2 position control settings but the actuator has not been wired for a feedback signal see Fig 12 and Fig 13 then as soon as operating power is applied the ...

Page 3: ...rol signal at switch settings terminal 3 terminal 4 0 2 10V Dir Service Off Rev 10 0 2 V open open stops stops stops open 24 Vac dc CCW stops CW 24 Vac open CW stops CCW Table 2 Shaft adapter behavior in the 2 position mode control signal at switch settings terminal 3 terminal 4 0 2 10V Dir Service Off Rev 10 0 2 V 24 Vac open CW stops CCW 24 Vac 24 Vac dc CCW stops CW Table 3 Shaft adapter behavi...

Page 4: ...r dead band i e to more than the max control signal minus 0 24 V or drops down into the lower dead band i e to less than the min control signal plus 0 24 V after which the shaft adapter must then remain at the respective upper or lower mechanical end limit for at least 3 seconds However in this case the actuator will then recognize the position of only the respective upper or lower mechanical end ...

Page 5: ... single point mounting Mounting Instructions All information and steps are included in the Installation Instructions Product Literature No 62 0224 supplied with each actuator Mounting Position The actuators can be mounted in any position IP54 is dependent upon orientation see Fig 9 Choose a mounting position permitting easy access to cables and controls Fig 8 Mounting for IP54 NOTE Further in orde...

Page 6: ...to gain access to the terminal block s and perform wiring Fig 9 Access Cover Wiring Diagrams Fig 10 CN7505 CN7510 modulating mode Wiring Diagrams Fig 11 CN7505 CN7510 floating mode Fig 12 CN7505 CN7510 2 position mode Fig 2 End switches NOTE Both of the internal end switches must be connected to the same power source Table 4 and Table 5 summarize the information presented in the preceding wiring d...

Page 7: ... NOTE All cables connected to these terminals must be equipped with spark suppression Table 5 Internal end switches terminal type of switch S1 common lead for switches A and B S2 S3 change over switch A S1 S2 opens and S1 S3 closes when shaft adapter moves CW past 5 reverts to original state when shaft adapter moves CCW past 5 S5 S6 change over switch B S1 S5 opens and S1 S6 closes when shaft adap...

Page 8: ...ional Inc Honeywell Tianjin Limited 1985 Douglas Drive North 66 BaiHe Road TEDA Golden Valley MN 55422 Tianjin 300457 P R C Honeywell Printed in China on recycled paper containing at least 10 post consumer paper fibers N05 N10 SERIES DAMPER ACTUATORS FOR MODULATING AND FLOATING CONTROL ...

Reviews: