background image

N05010/N10010 DAMPER ACTUATORS FOR MODULATING AND FLOATING/2-POSITION CONTROL 

Adaption 

Adaption is a function in which the actuator re-maps its feed-
back signal and control signal in accordance with repositioned 
mechanical end limits (see also Fig. 6) and thus recognizes 
their new positions. 
 

fi

nal posit

io

of

actuat

or

 (

%

 of

 max.)

fi

n

a

l posit

ion of

 act

uat

or (de

g

rees)

0

95

0

10.0

control signal (volts)

new position of UPPER

mechanical end limit

new position of LOWER

mechanical end limit

be

for

e a

da

pt

ion

aft

er 

ad

ap

tio

n

0

(before)

100

(before)

0

(after)

100

(after)

 

Fig. 6. Adaption (function selection switch set to 

"0...10 V") 

 
Adaption will be carried out whenever the actuator is in the 
modulating mode or the floating plus feedback mode or the 2-
position plus feedback mode and 

  the user powers up (from a totally powerless condition) the 

actuator; or 

  the user sets the function selection switch to the 

"Service/Off" setting for at least 2 seconds and then back 
to its previous setting; or 

  the control signal's value rises up into the upper dead 

band (i.e. to more than the max. control signal minus 
0.24 V) or drops down into the lower dead band (i.e. to 
less than the min. control signal plus 0.24 V), after which 
the shaft adapter must then remain at the respective 
(upper or lower) mechanical end limit for at least 3 
seconds. However, in this case, the actuator will then 
recognize the position of only the respective (upper or 
lower) mechanical end limit. 

 

Overriding 

An override is a condition in which a 24 V signal is applied to 
terminal 4 of an actuator in the modulating mode, thus 
causing the actuator to ignore the control signal at terminal 3, 
whereupon it will instead move to a position of 50% of its 
maximum stroke (see Table 3). 
 

Feedback 

If correspondingly wired (see Fig. 11, Fig. 12, and Fig. 13), 
the actuator provides, via terminal 5, a feedback signal pro-
portional to the actual position of the shaft adapter. 

MANUAL ADJUSTMENT 

IMPORTANT 

To prevent equipment damage, you must remove 
power or set the function selection switch to the 
"Service/Off" position before manual adjustment. 

 
After removing power or setting the function selection switch 
to the "Service/Off" position, the gear train can be disengaged 
using the declutch button, permitting the shaft adapter to be 
manually rotated to any position. If you have wired the 
actuator for feedback signal, then, after adaption, the 
feedback signal will follow the new position. 
 

Limitation of Rotation Stroke 

Two adjustable mechanical end limits are provided to limit the 
angle of rotation as desired (see Fig. 7). The mechanical end 
limits must be securely fastened in place. 
 

 

Fig. 7. Mechanical end limits 

 
To ensure tight closing of the dampers, the shaft adapter has 
a total rotation stroke of 95°. 
 
After adjusting the mechanical end limits, the user should 
trigger adaption (see section "Adaption"). 
 

INTERNAL END SWITCHES 

NOTE:

  Only those actuators for which "-SW2" has been 

specified when ordering (e.g.: "N05010-SW2") 
feature internal end switches. 

 
The internal end switches "A" and "B" are changeover 
switches which are activated when the shaft adapter moves 
past a position of 5° and 85°, respectively (see also Table 5). 
 

-2.5°

92.5°

10°

15°

90°

85°

80°

75°

changeover switch A activated

when shaft adapter moves past 5°

changeover switch B activated

when shaft adapter moves past 85°

 

Fig. 8. Internal end switch triggering points 

EN0B-0478GE51 R0105 

Summary of Contents for N05010

Page 1: ... hereinafter apply to operation under nominal voltage conditions Power consumption N05010 5 VA 2 W N10010 5 VA 2 W Control signal Modulating 0 10 V Floating 2 Position 24 Vac dc Ambient limits Ambient operating limits 20 60 C 5 140 F Ambient storage limits 30 80 C 22 176 F Relative humidity 5 95 non condensing Safety Protection standard IP54 Protection class II as per EN 60730 1 Overvoltage catego...

Page 2: ...ction selection switch Power Off Behavior If power is removed the shaft adapter remains in position Service Off If the function selection switch is set to the Service Off position then all rotary movement is cancelled and all control signals are ignored thus allowing the actuator to be manually operated safely Floating 2 Position Run Mode Without Feedback Signal If however the function selection s...

Page 3: ...havior in the 2 position mode control signal at switch settings terminal 3 terminal 4 0 2 10 V Dir Service Off Rev 10 0 2 V 24 Vac open CW stops CCW 24 Vac 24 Vac dc CCW stops CW Table 3 Shaft adapter behavior in the modulating mode control signal at switch settings terminal 3 terminal 4 0 2 10 V Dir Service Off Rev 10 0 2 V open totally CCW stop totally CCW open 24 Vac dc 50 stop 50 open totally ...

Page 4: ...ing the actuator to ignore the control signal at terminal 3 whereupon it will instead move to a position of 50 of its maximum stroke see Table 3 Feedback If correspondingly wired see Fig 11 Fig 12 and Fig 13 the actuator provides via terminal 5 a feedback signal pro portional to the actual position of the shaft adapter MANUAL ADJUSTMENT IMPORTANT To prevent equipment damage you must remove power o...

Page 5: ...acket is 85 mm a max of 108 mm is allowed see also Fig 15 Depending upon the specifics of your mounting site the actuator may shift in position slightly while tightening the screws at the top of the shaft adapter The anti rotation bracket features a T piece with a 5 mm long shank to accommodate for this movement It is important to ensure that this play is not impeded Universal Shaft Adapter The un...

Page 6: ...ng wiring diagrams Table 4 Signals at terminals mode ter minal modulating floating 2 position 1 24 V power unused or with feedback 24 V power unused or with feedback 24 V power 2 common common common 3 0 2 10 V control 24 V control signal 24 V control signal 4 24 V override 24 V control signal 24 V control signal 5 0 2 10 V feedback unused or with feedback 0 10 V unused or with feedback 0 10 V NOT...

Page 7: ...rder no A7211 2073 Contains 10 anti rotation brackets 20 screws Spare Parts Kit Order no A7211 2071 Contains 1 anti rotation bracket screws 2 universal terminal blocks 2 strain relief clamps 2 grommets 2 adjustable end stops In order to guarantee IP54 only original Honeywell grommets may be used 7 EN0B 0478GE51 R0105 ...

Page 8: ... Service Off N05010 134 85 108 66 62 41 Fig 15 Dimensions in mm Automation and Control Solutions Honeywell GmbH Böblinger Straße 17 D 71101 Schönaich Phone 49 7031 63701 Fax 49 7031 637493 http europe hbc honeywell com Subject to change without notice Printed in Germany Manufacturing location certified to EN0B 0478GE51 R0105 ...

Reviews: