N05010/N10010 DAMPER ACTUATORS FOR MODULATING AND FLOATING/2-POSITION CONTROL

 

INSTALLATION 

 CAUTION 

To avoid personal injury (electrical shock) and to 
prevent equipment damage, before installation, 
you must remove power. 

 
These actuators are designed for single-point mounting. 
 

Mounting Instructions 

All information and steps are included in the Installation 
Instructions (Product Literature No.: MU1B-0276GE51) 
supplied with each actuator. 
 

Mounting Position 

The actuators can be mounted in any position (IP54 is 
dependent upon orientation; see Fig. 9). Choose a mounting 
position permitting easy access to cables and controls. 
 

IP54

IP54

IP54

IP54

 

Fig. 9. Mounting for IP54 

 

NOTE:

  Further, in order to guarantee IP54, only original 

Honeywell grommets may be used. 

 

Anti-Rotation Bracket and Screws 

If the actuator is to be mounted directly on a damper shaft, 
use the anti-rotation bracket and screws included in the 
delivery package. The min. distance between the center of 
the damper shaft and the middle of the anti-rotation bracket is 
85 mm; a max. of 108 mm is allowed (see also Fig. 15). 
 
Depending upon the specifics of your mounting site, the 
actuator may shift in position slightly while tightening the 
screws at the top of the shaft adapter. The anti-rotation 
bracket features a T-piece with a 5-mm-long shank to 
accommodate for this movement. It is important to ensure 
that this play is not impeded. 
 

Universal Shaft Adapter 

The universal shaft adapter can be used for shafts of various 
diameters and shapes (round: 8...16 mm and square: 
6...13 mm). 
 

WIRING 

 CAUTION 

To avoid personal injury (electrical shock) and to 
prevent equipment damage, before wiring, you 
must remove power. 

 

Connecting to the Power Supply 

In order to comply with protection class II, the power source of 
24 V actuators must be reliably separated from the network 
power supply circuits as per DIN VDE 0106, part 101. 
 

Access Cover 

IMPORTANT 

Once the access cover has been removed, please 
take care to avoid damaging any of the parts now 
accessible. 

 
The access cover can be unscrewed and removed in order to 
gain access to the terminal block(s) and perform wiring. 
 

1

2

S6

 S5

 S3

 S2

 S1

1  

 2 

  3

   4

   5

1  

 2 

  3

   4

   5

S6

 S5

 S3

 S2

 S1

removable access cover

 

Fig. 10. Access cover 

 

 5 

EN0B-0478GE51 

R0105 

Summary of Contents for N05010

Page 1: ... hereinafter apply to operation under nominal voltage conditions Power consumption N05010 5 VA 2 W N10010 5 VA 2 W Control signal Modulating 0 10 V Floating 2 Position 24 Vac dc Ambient limits Ambient operating limits 20 60 C 5 140 F Ambient storage limits 30 80 C 22 176 F Relative humidity 5 95 non condensing Safety Protection standard IP54 Protection class II as per EN 60730 1 Overvoltage catego...

Page 2: ...ction selection switch Power Off Behavior If power is removed the shaft adapter remains in position Service Off If the function selection switch is set to the Service Off position then all rotary movement is cancelled and all control signals are ignored thus allowing the actuator to be manually operated safely Floating 2 Position Run Mode Without Feedback Signal If however the function selection s...

Page 3: ...havior in the 2 position mode control signal at switch settings terminal 3 terminal 4 0 2 10 V Dir Service Off Rev 10 0 2 V 24 Vac open CW stops CCW 24 Vac 24 Vac dc CCW stops CW Table 3 Shaft adapter behavior in the modulating mode control signal at switch settings terminal 3 terminal 4 0 2 10 V Dir Service Off Rev 10 0 2 V open totally CCW stop totally CCW open 24 Vac dc 50 stop 50 open totally ...

Page 4: ...ing the actuator to ignore the control signal at terminal 3 whereupon it will instead move to a position of 50 of its maximum stroke see Table 3 Feedback If correspondingly wired see Fig 11 Fig 12 and Fig 13 the actuator provides via terminal 5 a feedback signal pro portional to the actual position of the shaft adapter MANUAL ADJUSTMENT IMPORTANT To prevent equipment damage you must remove power o...

Page 5: ...acket is 85 mm a max of 108 mm is allowed see also Fig 15 Depending upon the specifics of your mounting site the actuator may shift in position slightly while tightening the screws at the top of the shaft adapter The anti rotation bracket features a T piece with a 5 mm long shank to accommodate for this movement It is important to ensure that this play is not impeded Universal Shaft Adapter The un...

Page 6: ...ng wiring diagrams Table 4 Signals at terminals mode ter minal modulating floating 2 position 1 24 V power unused or with feedback 24 V power unused or with feedback 24 V power 2 common common common 3 0 2 10 V control 24 V control signal 24 V control signal 4 24 V override 24 V control signal 24 V control signal 5 0 2 10 V feedback unused or with feedback 0 10 V unused or with feedback 0 10 V NOT...

Page 7: ...rder no A7211 2073 Contains 10 anti rotation brackets 20 screws Spare Parts Kit Order no A7211 2071 Contains 1 anti rotation bracket screws 2 universal terminal blocks 2 strain relief clamps 2 grommets 2 adjustable end stops In order to guarantee IP54 only original Honeywell grommets may be used 7 EN0B 0478GE51 R0105 ...

Page 8: ... Service Off N05010 134 85 108 66 62 41 Fig 15 Dimensions in mm Automation and Control Solutions Honeywell GmbH Böblinger Straße 17 D 71101 Schönaich Phone 49 7031 63701 Fax 49 7031 637493 http europe hbc honeywell com Subject to change without notice Printed in Germany Manufacturing location certified to EN0B 0478GE51 R0105 ...