N05010/N10010 DAMPER ACTUATORS FOR MODULATING AND FLOATING/2-POSITION CONTROL

 

Wiring Diagrams 

!

Modulating: 0[2]...10V, 10...0[2]V

0[2]...10V

0[2]...10V

POS out

POS 50%

Y in

GND/-

24V~/+

24V~/=

3

1

2

5

4

= override option

 

Fig. 11. N05010/N10010 (modulating mode) 

 

!

Floating: Dir

0[2]...10V

POS out

= feedback option

CCW

CW

GND/-

24V~/+

24V~/=

3

1

2

5

4

 

Fig. 12. N05010/N10010 (floating mode) 

 

!

2-Position: Dir

0[2]...10V

POS out

CCW

CW

GND/-

24V~/+

24V~/=

3

1

2

5

4

= feedback option

 

Fig. 13. N05010/N10010 (2-position mode) 

 

END SWITCHES

(max. 230 V, 5 A)

S3

S6

S5

S1

A,B: C

A: NC

A: NO

B: NC

B: NO

S2

A

B

 

Fig. 14. End switches (Nxx-SW2) 

 

NOTE:

  Both of the internal end switches must be connected 

to the same power source. 

 
Table 4 and Table 5 summarize the information presented in 
the preceding wiring diagrams. 
 

Table 4. Signals at terminals 

mode 

ter-

minal 

modulating 

floating 

2-position 

24 V ~/+ 

(power) 

unused 

or

 

(with feedback) 

24 V ~/+ (power) 

unused 

or

 

(with feedback)

24 V ~/+ (power)

common ~/- 

common ~/- 

common ~/- 

0[2]...10 V 

(control) 

24 V ~/+ 

(control signal) 

24 V ~/+ 

(control signal) 

24 V ~/+ 

(override) 

24 V ~/+ 

(control signal) 

24 V ~/+ 

(control signal) 

0[2]...10 V 

(feedback) 

unused 

or

 

(with feedback) 

0...10 V 

unused 

or

 

(with feedback)

0...10 V 

NOTE:

   All cables connected to these terminals must be 

equipped with spark suppression. 

 

Table 5. Internal end switches (Nxx-SW2) 

terminal 

type of switch 

S1 

common lead for switches A and B 

S2, S3 

change-over switch A (S1/S2 opens and S1/S3 
closes when shaft adapter moves CW past 5°; 
reverts to original state when shaft adapter 
moves CCW past 5°). 

S5, S6 

change-over switch B (S1/S5 opens and S1/S6 
closes when shaft adapter moves CW past 85°; 
reverts to original state when shaft adapter 
moves CCW past 85°). 

 

EN0B-0478GE51 R0105 

6

Summary of Contents for N05010

Page 1: ... hereinafter apply to operation under nominal voltage conditions Power consumption N05010 5 VA 2 W N10010 5 VA 2 W Control signal Modulating 0 10 V Floating 2 Position 24 Vac dc Ambient limits Ambient operating limits 20 60 C 5 140 F Ambient storage limits 30 80 C 22 176 F Relative humidity 5 95 non condensing Safety Protection standard IP54 Protection class II as per EN 60730 1 Overvoltage catego...

Page 2: ...ction selection switch Power Off Behavior If power is removed the shaft adapter remains in position Service Off If the function selection switch is set to the Service Off position then all rotary movement is cancelled and all control signals are ignored thus allowing the actuator to be manually operated safely Floating 2 Position Run Mode Without Feedback Signal If however the function selection s...

Page 3: ...havior in the 2 position mode control signal at switch settings terminal 3 terminal 4 0 2 10 V Dir Service Off Rev 10 0 2 V 24 Vac open CW stops CCW 24 Vac 24 Vac dc CCW stops CW Table 3 Shaft adapter behavior in the modulating mode control signal at switch settings terminal 3 terminal 4 0 2 10 V Dir Service Off Rev 10 0 2 V open totally CCW stop totally CCW open 24 Vac dc 50 stop 50 open totally ...

Page 4: ...ing the actuator to ignore the control signal at terminal 3 whereupon it will instead move to a position of 50 of its maximum stroke see Table 3 Feedback If correspondingly wired see Fig 11 Fig 12 and Fig 13 the actuator provides via terminal 5 a feedback signal pro portional to the actual position of the shaft adapter MANUAL ADJUSTMENT IMPORTANT To prevent equipment damage you must remove power o...

Page 5: ...acket is 85 mm a max of 108 mm is allowed see also Fig 15 Depending upon the specifics of your mounting site the actuator may shift in position slightly while tightening the screws at the top of the shaft adapter The anti rotation bracket features a T piece with a 5 mm long shank to accommodate for this movement It is important to ensure that this play is not impeded Universal Shaft Adapter The un...

Page 6: ...ng wiring diagrams Table 4 Signals at terminals mode ter minal modulating floating 2 position 1 24 V power unused or with feedback 24 V power unused or with feedback 24 V power 2 common common common 3 0 2 10 V control 24 V control signal 24 V control signal 4 24 V override 24 V control signal 24 V control signal 5 0 2 10 V feedback unused or with feedback 0 10 V unused or with feedback 0 10 V NOT...

Page 7: ...rder no A7211 2073 Contains 10 anti rotation brackets 20 screws Spare Parts Kit Order no A7211 2071 Contains 1 anti rotation bracket screws 2 universal terminal blocks 2 strain relief clamps 2 grommets 2 adjustable end stops In order to guarantee IP54 only original Honeywell grommets may be used 7 EN0B 0478GE51 R0105 ...

Page 8: ... Service Off N05010 134 85 108 66 62 41 Fig 15 Dimensions in mm Automation and Control Solutions Honeywell GmbH Böblinger Straße 17 D 71101 Schönaich Phone 49 7031 63701 Fax 49 7031 637493 http europe hbc honeywell com Subject to change without notice Printed in Germany Manufacturing location certified to EN0B 0478GE51 R0105 ...