N05010/N10010 DAMPER ACTUATORS FOR MODULATING AND FLOATING/2-POSITION CONTROL
Wiring Diagrams
!
Modulating: 0[2]...10V, 10...0[2]V
0[2]...10V
0[2]...10V
POS out
POS 50%
Y in
GND/-
24V~/+
24V~/=
3
1
2
5
4
= override option
Fig. 11. N05010/N10010 (modulating mode)
!
Floating: Dir
0[2]...10V
POS out
= feedback option
CCW
CW
GND/-
24V~/+
24V~/=
3
1
2
5
4
Fig. 12. N05010/N10010 (floating mode)
!
2-Position: Dir
0[2]...10V
POS out
CCW
CW
GND/-
24V~/+
24V~/=
3
1
2
5
4
= feedback option
Fig. 13. N05010/N10010 (2-position mode)
END SWITCHES
(max. 230 V, 5 A)
S3
S6
S5
S1
A,B: C
A: NC
A: NO
B: NC
B: NO
S2
A
B
Fig. 14. End switches (Nxx-SW2)
NOTE:
Both of the internal end switches must be connected
to the same power source.
Table 4 and Table 5 summarize the information presented in
the preceding wiring diagrams.
Table 4. Signals at terminals
mode
ter-
minal
modulating
floating
2-position
1
24 V ~/+
(power)
unused
or
(with feedback)
24 V ~/+ (power)
unused
or
(with feedback)
24 V ~/+ (power)
2
common ~/-
common ~/-
common ~/-
3
0[2]...10 V
(control)
24 V ~/+
(control signal)
24 V ~/+
(control signal)
4
24 V ~/+
(override)
24 V ~/+
(control signal)
24 V ~/+
(control signal)
5
0[2]...10 V
(feedback)
unused
or
(with feedback)
0...10 V
unused
or
(with feedback)
0...10 V
NOTE:
All cables connected to these terminals must be
equipped with spark suppression.
Table 5. Internal end switches (Nxx-SW2)
terminal
type of switch
S1
common lead for switches A and B
S2, S3
change-over switch A (S1/S2 opens and S1/S3
closes when shaft adapter moves CW past 5°;
reverts to original state when shaft adapter
moves CCW past 5°).
S5, S6
change-over switch B (S1/S5 opens and S1/S6
closes when shaft adapter moves CW past 85°;
reverts to original state when shaft adapter
moves CCW past 85°).
EN0B-0478GE51 R0105
6