22
www.honeywell.com
NetAXS™ NX4S1 Installation
Installation
Use the following DIP switch configurations to set the panel address.
Note:
Address 0 is not a valid setting for standard operations.
Table 3 DIP Switch Settings
S1
S2
S3
S4
S5
S6
Selection
on
off
off
off
off
Address 1 (default)
off
on
off
off
off
Address 2
on
on
off
off
off
Address 3
off
off
on
off
off
Address 4
on
off
on
off
off
Address 5
off
on
on
off
off
Address 6
on
on
on
off
off
Address 7
off
off
off
on
off
Address 8
on
off
off
on
off
Address 9
off
on
off
on
off
Address 10
on
on
off
on
off
Address 11
off
off
on
on
off
Address 12
on
off
on
on
off
Address 13
off
on
on
on
off
Address 14
on
on
on
on
off
Address 15
off
off
off
off
on
Address 16
on
off
off
off
on
Address 17
off
on
off
off
on
Address 18
on
on
off
off
on
Address 19
off
off
on
off
on
Address 20
on
off
on
off
on
Address 21
off
on
on
off
on
Address 22
on
on
on
off
on
Address 23
off
off
off
on
on
Address 24
on
off
off
on
on
Address 25
off
on
off
on
on
Address 26
on
on
off
on
on
Address 27
off
off
on
on
on
Address 28
on
off
on
on
on
Address 29
off
on
on
on
on
Address 30
on
on
on
on
on
Address 31
off
NetAXS™ Multidrop
on
NetAXS™ Gateway