30
www.honeywell.com
NetAXS™ NX4S1 Installation
System Configuration
5.4 RS-232 Connection
This connection supports one NetAXS™ Access Controller panel for each COM port. It has been
reviewed by UL. However, because UL has reviewed the NetAXS™ panel only as a standalone
system, the computer terminal and NetAXS™ gateway panel appear in this section only to illustrate
the installation and programming of the NetAXS™ panel.
Figure 20: RS-232 Connection
COM 1
COM 2
CBL50 (RS-232) 50 Ft. Max.
CBL50
(RS-232)
50 Ft. Max.
DIP Switch Settings
S1 - S5: Panel Address
S6: OFF
NetAXS
Panel
NetAXS
Panel
It is recommended to Earth Ground (EG)
each NetAXS enclosure individually
Request To Send (RTS)
Signal Ground (GND)
Receive Data (RXD)
Transmit Data (TXD)
Clear To Send (CTS)
CBL50 (RS-232)
RS-232
RJ-45
(DB9)
8
2
5
3
2
4
3
5
7
7
9-Pin COM 1 or COM 2 to RJ-45 on NetAXS Panel
Terminal
EG
EG