NetAXS™ Standalone Operation
NetAXS™ Panel Defaults
NetAXS Access Control Unit NX4L1 Installation Guide
,
7-901099, Revision A
61
A.4.5 Door Status Inputs
The panel has a Door Status input for each door. The default condition is a two-state
input configured as a Normally Closed contact.
The following are the default door status input associations:
A.4.6 ACFAIL and Panel Tamper Inputs
The panel has the following two additional generic inputs that can be used as generic
inputs or as either External Power Fail or Enclosure Tamper inputs. The default
condition is a two-state input configured as Normally Closed. Input 14 is a special
case, since it reports in as two inputs (inputs 14 and 20). Input 14 can be used as a
generic input, but input 20 is used for the Enclosure Tamper alarm. An active External
Power Fail input indicates that the system is operating from the battery current, not
from the primary input power. An inactive External Power Fail input indicates that the
system is operating from the primary input power.
Door Status input
Panel input
Reports as...
1
SP2
Input 2
1
SP4
Input 4
1
SP6
Input 6
1
SP8
Input 8
Generic input
Panel input
Reports as...
Generic/External Power Fail
SP9
Input 13
Generic/Enclosure Tamper
SP10
Inputs 14 and 20