74
Notifier SLC Wiring Manual —
P/N 51253:U5 12/20/2017
Canadian Versions of SLC Devices
FSA-5000
FSA-5000A
Intelligent FAAST XS aspiration smoke detector, covers up to 5,000 square
feet. FlashScan mode.
FSA-8000
FSA-8000A
Intelligent FAAST XM aspiration smoke detector, covers up to 8000 square
feet. Supports FlashScan and CLIP mode. (An earlier model was CLIP mode
only).
FSA-20000
FSA-20000A
Intelligent FAAST XT aspiration smoke detector, covers up to 28,800 square
feet. FlashScan mode.
FSA-20000P
FSA-20000P
Intelligent FAAST XT PRO aspiration smoke detector, covers up to 28,800
square feet through addressable pipes. FlashScan mode UL-/ULC-listed
model.
Bases
B300-6
B3006A
Standard U.S. Low-Profile base (6", 15.24 cm). White.
B300-6-IV
B3006A-IV
Standard U.S. Low-Profile base (6", 15.24 cm). Ivory.
B210LP
B210LPA
Standard U.S. Low-Profile base (6", 15.24 cm).
B501
B501 (Manufactured 1/2018
or later); B501A
(manufactured before 2018)
Standard European flangeless base (4", 10.16 cm). White.
B501-IV
B501-IV
Ivory version of B501.
B501-BL
B501-BL
Black version of B501.
B710LP
B710LPA
Standard U.S. Low-Profile base (6", 15.24 cm). Discontinued.
B501BH, B501BHT
B501BHA, B501BHTA
Sounder base, includes B501/A Sounder base with temporal sounder (UL
8th Edition) Discontinued.
B501BH-2, B501BHT-2
N/A
Sounder base, includes B501/A Sounder base with temporal sounder (UL
9th Edition) Discontinued.
B224RB
B224RBA
Low Profile Intelligent relay base.
B224BI
B224BIA
Low Profile Intelligent isolator base.
B710HD
B710HDA
Base for a hostile environment detector.
B200S
B200SA, B200SCOA
Addressable sounder base.
B200SCOA provides
CO detector markings in English/French, for
Canadian applications only.
B200SR
B200SRA
Sounder base.
Note: Because the low-frequency bases are designed for a UL requirement,there is no ULC-listed version of B200S-LF/B200SR-LF
Monitor and Zone Interface Modules
FMM-1
FMM-1A
Used for normally open contact alarm initiating devices, such as manual pull
stations, four-wire smoke detectors, heat detectors, waterflow, and
supervisory devices.
FZM-1
FZM-1A
Used to interface with two-wire smoke detectors in addition to normally open
contacts.
FDM-1
FDM-1A
Provides two independent 2-wire Initiating Device Circuits (IDCs) at two
separate, consecutive addresses. Wire supervised IDCs as NFPA Style B
(Class B) or Style D (Class A) circuits. The modules come with a
thermoplastic cover for mounting to a 4-inch (10.16 cm) square mounting
box.
FMM-101
FMM-101A
Functionally similar to the FMM-1 Monitor Module, but offered in a smaller
package for mounting directly in the electrical box of the device being
monitored. (Class B input circuit only.)
Pull Stations
NBG-12LX
NBG-12LX
An addressable manual pull station with key-lock reset feature. The
addressable module is housed within the pull station.
N/A
N-MPS Series
Addressable manual pull stations with hex key reset feature. The
addressable module is housed within the pull station.
Control Modules
FCM-1
FCM-1A
Control Module, NAC: Addressable Control Module used as Notification
Appliance Circuits (NACs) to power and supervise compatible, UL-listed
notification appliances. Wired supervised NACs as NFPA Style Y (Class B)
or Style Z (Class A). The modules come with a thermoplastic cover for
mounting to a 4-inch (10.16 cm) square mounting box.
FCM-1-REL
FCM-1-RELA
Control Module for releasing applications. FlashScan only.
FRM-1
FRM-1A
Relay Control Module is similar to the FCM-1 except used as a Form-C
control relay module.
UL-listed SLC Device
ULC-listed SLC Device
Description