3.4 Web Portal Setup

To receive events and configuration information for use in tools such as the Inspection Manager, the 
BACNET-GW-3 must be associated with a specific site, as follows:

1. In the navigation tree section of the gateway configuration tool, select 

Additional Properties > 

Web Portal Setup

.

2. Enter the information in the text boxes in the right-hand column. The user name and password are 

the same as those used to access the eVance web site. The web portal name must be unique for the 
eVance account to register this web portal. The web portal description is used in eVance to identify 
this specific gateway.

3. Click 

Apply

. When successfully completed, a dialog box displays. 

4. Click 

OK

. The “Assign the Web Portal…” dialog box displays. 

5. From the customer drop-down list, select the appropriate customer for this site. The web portal 

displays the node number(s) for the connected FACP(s). 

6. Select the appropriate building for each node using its drop-down list.

There are additional selections for “<Unassigned – Delete Equipment>” and “Unassigned” options. 
In both of these cases, the panel’s points will not be configured on eVance and, with the Delete 
Equipment option, the existing equipment for that node will be deleted from eVance.

7. Click 

Apply

. A commissioning prompt displays.

8. Click 

Yes

. The gateway communicates with each connected panel and sends a list of all the 

configured points to eVance. Because these points are defined in eVance, they are displayed when a 
new test session is created.

Summary of Contents for NOTIFIER BACNET-GW-3

Page 1: ...C6 P N LS10014 000NF E C6 ECN 17 0185 Document LS10014 000NF E 5 5 2017 Rev BACNET GW 3 Installation and Operation Manual BACNET GW 3 Installation and Operation Manual ...

Page 2: ...ector may not provide adequate warning of a fire Smoke detectors cannot be expected to provide adequate warn ing of fires caused by arson children playing with matches especially in bedrooms smoking in bed and violent explosions caused by escaping gas improper storage of flammable materi als etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases...

Page 3: ...o can damage circuits Remove all electronic assemblies prior to any drilling filing reaming or punching of the enclosure When possible make all cable entries from the sides or rear Before making modifications verify that they will not interfere with battery transformer and printed circuit board location Do not tighten screw terminals more than 9 in lbs Over tightening may damage threads resulting ...

Page 4: ...ave any comments or suggestions about our on line help or manuals please e mail us at FireSystems TechPubs honeywell com On Line Help Please include the following information Product name and version number if applicable Topic title The content you think should be corrected improved Detailed suggestions for correction improvement Documents Please include the following information Document part num...

Page 5: ... 1 Connecting the BACNET GW 3 15 Figure 2 5 BACNET GW 3 Connections 15 Table 2 1 Connection Specifications 15 Figure 2 6 BACNET GW 3 LEDs 16 Table 2 2 LED Definitions 16 2 3 2 Connecting to a Standard NCM 17 Figure 2 7 Routing Power and Communication to a Standard NCM 17 Table 2 3 Standard NCM Connections 17 2 3 3 Connecting to an HS NCM 18 Figure 2 8 Routing Power and Communication to an HS NCM 1...

Page 6: ...Values 29 Appendix B BACnet PIC Statement 31 B 1 Product Description 31 B 2 BACnet Standardized Device Profile Annex L 31 B 3 BACnet Interoperability Building Blocks Supported Annex K 31 B 4 Segmentation Capability 31 B 5 Standard Object Types Supported Life Safety Point Life Safety Zone 32 B 6 Standard Object Types Supported Multi State Input Standard Object Types 34 B 7 Supported Binary Output 3...

Page 7: ... information between eVance and the connected FACPs NFN network or high speed NFN network This information is for maintenance purposes only 1 3 BACnet Clients The BACnet client must conform to BACnet Standard Annex J for IP and support device objects binary output objects and multi state input or life safety points zones It is also required to write to notification objects and receive confirmed un...

Page 8: ...ntranet IP network connection is used with the architectures described in Figures 1 1 and 1 2 Figure 1 1 Single Panel Architecture Figure 1 2 NFN Network Architecture BACnet IP Client FACP NUP IP Network Ethernet Ethernet BACNET GW 3 FACP FACP IP Network BACNET GW 3 FACP BACnet IP Client BACnet IP Client HS NCM or NCM NFN Network Ethernet Ethernet Ethernet ...

Page 9: ...ing IP ports must be available to the BACNET GW 3 1 7 2 IP Restrictions The following IP restrictions apply to the BACNET GW 3 Must have a static IP address DHCP is not supported Web access via an HTTP proxy server is not supported Port Type Direction Purpose 80 TCP In Web Based Configuration 443 TCP In HTTPS Communications 4016 UDP In Upgrades 47808 UDP Both BACnet ...

Page 10: ... Systems Ninth Edition UL 2017 General Purpose Signaling Devices and Systems First Edition UL 2572 Mass Notification Systems First Edition Underwriters Laboratories Canada CAN ULC S527 11 Standard for Control Units for Fire Alarm Systems Third Edition CAN ULC S559 13 Standard for Equipment for Fire Signal Receiving Centres and Systems Second Edition Installation This product is intended to be inst...

Page 11: ...patible with the following equipment Table 1 1 Compatible Equipment Type Equipment Fire Panels NFS 320 NFS2 640 NFS2 3030 Network Cards NCM W NCM F HS NCM W HS NCM SF HS NCM MF HS NCM WSF HS NCM WMF HS NCM MFSF Gateways NFN GW EM 3 PC NFN Gateways NFN GW PC F NFN GW PC W NFN GW PC HNMF NFN GW PC HNSF NFNGW PC HNW Other Products DVC MODBUS GW NCA 2 NWS 3 VESDA HLI GW ...

Page 12: ...Product Overview Compatible Equipment 12 BACNET GW 3 Installation and Operation Manual P N LS10014 000NF E C6 5 5 2017 ...

Page 13: ...N 75665 Used to connect the BACNET GW 3 board to an HS NCM board Network Components High speed Network Communication Module HS NCM Used to facilitate network communication between the BACNET GW 3 and a high speed NFN network sold separately OR Network Communication Module NCM Used to facilitate network communication between the BACNET GW 3 and an NFN network sold separately OR Compatible FACP with...

Page 14: ...eypad Removed Install bracket on 1 2 standoffs Place the board s tab in the bracket slot and screw the board to the top of the standoffs May be stacked in front of or behind another board using standoffs of adequate length to clear the rear board Mounting Studs Board Mount in 4th column of the NFS2 640 Series chassis Mount chassis to backbox before installing the board in rear position May be moun...

Page 15: ...sted 24 VDC regulated power supply Nominal Voltage 24 VDC Regulated Current 125 mA Locate in same cabinet or use close nipple fitting J1 USB B 2 Locate in same cabinet or use close nipple fitting J2 USB A 2 Locate in same cabinet or use close nipple fitting J3 Ethernet 2 Line Impedance 100 ohm Max Distance 328 083 ft 100 m J4 NUP A 2 RS 232 Locate in same cabinet or use close nipple fitting All wi...

Page 16: ...ot Used D7 USB B Active Lit indicates a device is connected to the USB B port J1 D8 NUPA TX Blinks when data is sent on the NUP A port J4 D9 USB A Active Lit indicates a device is connected to the USB A port J2 D10 NUPB TX Not Used D11 DATA Blinks to indicate data transmission to or from the Ethernet port J3 D12 LINK Active Lit indicates an Ethernet connection D22 WDT FAIL Active Lit indicates the...

Page 17: ...ard NCM Figure 2 7 Routing Power and Communication to a Standard NCM Table 2 3 Standard NCM Connections Type Connection NCM W Twisted pair wire NCM F Fiber optic cable TB2 24V In From External Power Source to TB2 Out to NCM NCM BACNET GW 3 Connect Either Cable to Either NUP Connector on the NCM Communication from NUP A J4 Only 24 VDC ...

Page 18: ...ction HS NCM W Twisted pair wire HS NCM SF Single mode fiber optic cable HS NCM MF Multimode fiber optic cable HS NCM WSF Twisted pair wire Single mode fiber optic cable HS NCM WMF Twisted pair wire Multimode fiber optic cable HS NCM MFSF Multimode fiber optic cable Single mode fiber optic cable TB2 For Communications Connect USB A to B OR USB B to A BACNET GW 3 24V In From External Power Source t...

Page 19: ...FACP 2 3 5 Connecting to the PNET 1 Surge Suppressor Figure 2 10 Connecting to the PNET 1 FACP From FACP NUP Connector NUP Cable Provides Both Power and Communication To NUP A J4 only Not Used BACNET GW 3 Panel is shown for illustrative purposes only The BACNET GW 3 is mounted within the FACP cabinet and connected with the NUP connection located on the FACP Ground J3 PNET 1 BACNET GW 3 ...

Page 20: ...000NF E C6 5 5 2017 2 4 System Power 2 5 Testing and Maintenance Testing and maintenance should be performed according to the Testing and Maintenance section of NFPA 72 and CAN ULC S536 Table 2 5 Power Requirements Power Requirement Input Voltage Nominal 24 VDC Input Current 24 VDC 125 mA ...

Page 21: ...s on resetting and reviewing the IP settings of the BACNET GW 3 3 2 Configuring the BACNET GW 3 3 2 1 Logging into the Web Page Log into the BACNET GW 3 as follows 1 Start the web browser 2 Navigate to the IP address of the gateway default http 192 168 1 2 3 If a security warning appears select the option to continue anyway Refer to 3 3 Security Certificate for more information 4 Log into the web ...

Page 22: ... 2 Basic Configuration Tool Layout Figure 3 1 Basic Configuration Tool Layout Click to Enter or Change Text Navigation Tree Additional Properties see 3 2 5 Node List see 3 2 6 Click to View Sub items Main Menus see 3 2 3 Click for Product Information see 3 2 4 Click for Drop down List Click to Apply Changes Error Log see 3 2 7 ...

Page 23: ...Browse to or search for the backup file on the PC running the browser Click Open and then Send An on screen message indicates a successful restoration Send PFX Key File Opens a dialog box allowing the user to upload an SSL Certificate File Browse for the file enter the password if required and click Send Refer to 3 3 Security Certificate for additional information Delete Objects Database Opens a d...

Page 24: ...nd time information after the gateway synchronizes the clock with the SNTP server Gateway Properties Notification Type Select the operating mode for the gateway from the drop down menu Multi State Life Safety Network Number Enter the base network number for the gateway Note If using more than one BACNET GW 3 on the same network separate network numbers by at least 100 BACnet Port Enter the port nu...

Page 25: ...ary Domain Name System DNS server Alternate DNS Server Enter the IP address of the alternate DNS server NFN Settings General Information Connection Port Displays the type of connection port used Serial USB etc Connection Type Describes how the gateway is connected to the NFN network NCM Version Displays the NCM version number Note This property does not appear when there is no NFN connection NCM S...

Page 26: ...perty label toggles between Show All Nodes and Show Online or Mapped Nodes depending on the mode selected Select Yes to display the list of nodes in the mode indicated by the property label Node List An asterisked field is present to the right of the list of all nodes that the BACNET GW 3 can monitor Up to 14 nodes can be monitored Select Yes to enable monitoring of the node Select No to disable m...

Page 27: ...way must be provided The certificate is specific to the specified IP address If the IP address is changed a new certificate will be required In addition the certificates have an expiration date Once the certificate expires a new certificate needs to be sent to the gateway If the certificate expires a different warning is displayed by the browser The security certificate must be in the PFX format T...

Page 28: ...the eVance account to register this web portal The web portal description is used in eVance to identify this specific gateway 3 Click Apply When successfully completed a dialog box displays 4 Click OK The Assign the Web Portal dialog box displays 5 From the customer drop down list select the appropriate customer for this site The web portal displays the node number s for the connected FACP s 6 Sel...

Page 29: ...lash drive to a PC and create a file named default ldc The contents of the file is not significant however ensure that the file does not have an additional hidden file extension This file will be automatically deleted from the flash drive by the gateway 2 Eject the flash drive from the PC 3 Disconnect power from the gateway 4 Disconnect the communication cable to the gateway USB port if present an...

Page 30: ...30 BACNET GW 3 Installation and Operation Manual P N LS10014 000NF E C6 5 5 2017 ...

Page 31: ...d BACnet client workstations B 2 BACnet Standardized Device Profile Annex L BACnet Operator Workstation B OWS BACnet Building Controller B BC BACnet Advanced Application Controller B AAC BACnet Application Specific Controller B ASC BACnet Smart Sensor B SS BACnet Smart Actuator B SA B 3 BACnet Interoperability Building Blocks Supported Annex K B 4 Segmentation Capability Segmented requests support...

Page 32: ...m Life Property Critical Process Alarm Life Property Medical Emergency 3 IssFault Security Trouble Fire Trouble Non Fire Trouble Fire Device or Zone Disabled Non Fire Device Disabled 7 IssActive Non Fire Activation 22 IssSupervisory Supervisory Equipment Supervisory Guard s Tour Event State BACnet Enumeration BACnet Event State NFN State 0 EsNormal Normal 1 EsFault Security Trouble Fire Trouble No...

Page 33: ...ansition Bit NFN State toOffNormal toFault Direct Reading REAL NA Alarm Proprietary Property 1001 REAL NA Drift Compensation Percent ONYX Series Panels Only Status Flags Boolean BACnet Status Flags NFN State 0 0 0 0 Normal 1 0 0 0 InAlarm Fire Alarm Security Alarm Life Property Critical Process Alarm Life Property Medical Emergency 1 1 0 0 InAlarm Fault Security Trouble Fire Trouble Non Fire Troub...

Page 34: ...Disabled Non Fire Device Disabled 2 EsOffNormal All statuses other than normal and fault Reliability BACnet Enumeration BACnet Reliability NFN State 0 reNoFaultDetected All statuses other than trouble 7 re_UnreliableOther Security Trouble Fire Trouble Non Fire Trouble Status Flags Boolean BACnet Status Flags NFN State 0 0 0 0 Normal 1 0 0 0 InAlarm Fire Alarm Security Alarm Life Property Critical ...

Page 35: ...arm Life Property Critical Process Alarm Life Property Medical Emergency 3 IssFault Security Trouble Fire Trouble Non Fire Trouble Fire Device or Zone Disabled Non Fire Device Disabled 7 IssActive Non Fire Activation 22 IssSupervisory Supervisory Equipment Supervisory Guard s Tour Event State BACnet Enumeration BACnet Event State NFN State 0 EsNormal Normal 1 EsFault Security Trouble Fire Trouble ...

Page 36: ... Transition Bit toOffNormal toFault Direct Reading REAL NA Alarm Status Flags Boolean BACnet Status Flags NFN State 0 0 0 0 Normal 1 0 0 0 InAlarm Fire Alarm Security Alarm Life Property Critical Process Alarm Life Property Medical Emergency 1 1 0 0 InAlarm Fault Security Trouble Fire Trouble Non Fire Trouble PreAlarm 1 0 0 1 InAlarm OutOfService Fire Device or Zone Disabled Non Fire Device Disabl...

Page 37: ...d rate s ______________ Point To Point modem Clause 10 baud rate s LonTalk Clause 11 medium ______________ Other ______________ B 8 1 Device Address Binding Is static device binding supported This is currently necessary for two way communication with MS TP slaves and certain other devices Yes No B 8 2 Networking Options Router Clause 6 List all routing configurations e g ARCNET Ethernet Ethernet M...

Page 38: ...C6 5 5 2017 B 8 4 Supported Non BACnet Equipment Networks This product supports communications between NOTIFIER Fire Panels and Annunciator nodes compatible with network v 5 0 and later operating in a network or stand alone configuration Refer to 1 9 Compatible Equipment ...

Page 39: ...01D025 15 x 10000 1 1 x 1000 25 1 150024 Node 201 L02M014 201 x 10000 2 1 x 1000 14 199 2011213 Node 114 Annunciator 001 114 x 10000 1 699 1140700 Node 20 ZONE0002 20 x 10000 1502 201502 Panel Node Number x 10000 Base Panel Address Generic Panel Points MULTI_STATE_INPUT or LIFE_SAFETY_POINT 506 PANEL 507 RESET 579 NETWORK_A 580 NETWORK_B 582 WALK TEST 505 CPU 500 GROUND 502 BATTERY 501 ACPOWER 503...

Page 40: ...ONE 3499 LZONE 500 to 999 ZONE 4000 LZONE 1000 to 1499 ZONE 6500 LZONE 1500 to 2000 ZONE 7000 Special Zones MULTI_STATE_INPUT or LIFE_SAFETY_ZONE FZONE 0 47 ZONE 6400 Trouble Zones MULTI_STATE_INPUT or LIFE_SAFETY_ZONE TZONE 1 99 ZONE 5540 Releasing Zones MULTI_STATE_INPUT or LIFE_SAFETY_ZONE RZONE 0 9 ZONE 6500 DAA Speaker Circuit DAA 1 x 4 Spk 1 6600 Input Output and ZoneNotify NOTIFICATION_CLAS...

Page 41: ...IES AND DISCLAIMS ANY AND ALL OTHER WARRANTIES EITHER EXPRESSED OR IMPLIED WITH RESPECT TO THE PRODUCTS TRADEMARKS PROGRAMS AND SERVICES RENDERED BY MANUFACTURER INCLUDING WITHOUT LIMITATION INFRINGEMENT TITLE MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE MANUFACTURER SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF OR AS A RESULT OF PERSONAL COMMERCIAL...

Page 42: ...World Headquarters 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 fax 203 484 7118 www notifier com ...

Reviews: