Supported - Binary Output
BACnet PIC Statement
BACNET-GW-3 Installation and Operation Manual – P/N LS10014-000NF-E:C6 5/5/2017
35
B.7 Supported - Binary Output
Present Value
BACnet
Enumeration
BACnet
LifeSafetyState
NFN State
0
IssQuiet
Normal
1
IssPreAlarm
PreAlarm
2
IssAlarm
Fire Alarm, Security Alarm (Life/Property), Critical
Process Alarm, (Life/Property), Medical Emergency
3
IssFault
Security Trouble, Fire Trouble, Non-Fire Trouble, Fire
Device or Zone, Disabled, Non-Fire Device Disabled
7
IssActive
Non-Fire Activation
22
IssSupervisory
Supervisory (Equipment), Supervisory (Guard's Tour)
Tracking Value
BACnet
Enumeration
BACnet
LifeSafetyState
NFN State
0
IssQuiet
Normal
1
IssPreAlarm
PreAlarm
2
IssAlarm
Fire Alarm, Security Alarm (Life/Property), Critical
Process Alarm (Life/Property), Medical Emergency
3
IssFault
Security Trouble, Fire Trouble, Non-Fire Trouble, Fire
Device or Zone, Disabled, Non-Fire Device Disabled
7
IssActive
Non-Fire Activation
22
IssSupervisory
Supervisory (Equipment), Supervisory (Guard's Tour)
Event State
BACnet
Enumeration
BACnet Event State
NFN State
0
EsNormal
Normal
1
EsFault
Security Trouble, Fire Trouble, Non-Fire Trouble,
Fireevice Disabled, Non-Fire Device Disabled
2
EsOffNormal
All statuses other than normal and fault.
Reliability
BACnet
Enumeration
BACnet Reliability
NFN State
0
reNoFaultDetected
All statuses other than trouble.
7
re_UnreliableOther
Security Trouble, Fire Trouble, Non-Fire Trouble
Mode
BACnet
Enumeration
BACnet Mode
NFN State
0
IsmOff
Power-Up State
11
IsmEnabled
Set if point has been disabled and subsequently
enabled since startup.
12
IsmDisabled
Fire Device or Zone Disabled, Non-Fire Device
Disabled