40
BACNET-GW-3 Installation and Operation Manual – P/N LS10014-000NF-E:C6 5/5/2017
Panel Circuits (BINARY_OUTPUT)
(Panel# x 10) + (circuit# - 1) + 350
Annunciators (MULTI_STATE_INPUT or LIFE_SAFETY_POINT)
(ANNUN# + 699)
Zones (MULTI_STATE_INPUT or LIFE_SAFETY_ZONE)
ZONE (0 - 499) => (ZONE# + 1500)
ZONE (500-999) => (ZONE# + 2000)
Logic Zones (MULTI_STATE_INPUT or LIFE_SAFETY_ZONE)
LZONE (1 to 499) => (ZONE# + 3499)
LZONE (500 to 999) => (ZONE# + 4000)
LZONE (1000 to 1499) => (ZONE# + 6500)
LZONE (1500 to 2000) => (ZONE# + 7000)
Special Zones (MULTI_STATE_INPUT or LIFE_SAFETY_ZONE)
FZONE (0-47) => (ZONE# + 6400)
Trouble Zones (MULTI_STATE_INPUT or LIFE_SAFETY_ZONE)
TZONE (1-99) => (ZONE# + 5540)
Releasing Zones (MULTI_STATE_INPUT or LIFE_SAFETY_ZONE)
RZONE (0-9) => (ZONE# + 6500)
DAA Speaker Circuit
(DAA# - 1) x 4 + (Spk# - 1) + 6600
Input, Output, and ZoneNotify (NOTIFICATION_CLASS)
These objects will always be the same object ID on each device. You do not need to add the Node
Number offset.
INPUTNOTIFY = 1
OUTPUTNOTIFY = 2
ZONENOTIFY = 3