Configuration
Configuring the BACNET-GW-3
24
BACNET-GW-3 Installation and Operation Manual – P/N LS10014-000NF-E:C6 5/5/2017
3.2.4 Product Information
The product information displays when initially opening the configuration tool. It can also be accessed by
clicking the first entry in the navigation tree (see
). After configuring the settings, click
Apply
in
the lower right corner of the window.
Table 3.2 Product Information
Label
Property
Value
BACnet
Gateway
Type
Displays the gateway type by name.
Version
Displays the gateway version number.
Board Type
Displays the hardware model type.
Kernel Version
Displays additional software version information.
Boot Version
Displays additional software version information.
Current Time/Date
Displays the current date and time information after the gateway
synchronizes the clock with the SNTP server.
Gateway
Properties
Notification Type
Select the operating mode for the gateway from the drop-down menu:
• Multi State
• Life Safety
Network Number
Enter the base network number for the gateway.
Note:
If using more than one BACNET-GW-3 on the same network,
separate network numbers by at least 100.
BACnet Port
Enter the port number that is used for BACNET-GW-3 communications.
Network Update
Time
Enter the time of day (24-hour format) at which the gateway will query
the network each day.
Foreign
Device
Configuration
Foreign Device
• Select
Yes
if the gateway will operate in Foreign Device Mode.
• Select
No
if the gateway will not operate in Foreign Device Mode.
IP Address
Enter the IP address to be used in Foreign Device Mode.
Port
Enter the value for the IP port to be used for communication in Foreign
Device Mode.
Register Time
Enter the polling time (in seconds) to be used in Foreign Device Mode.