Auxiliary DC Power Output Connections
Installation
2.3.2 Secondary Power Source (Batteries)
The batteries must be sealed lead acid type. Before connecting the batteries to the FACP,
make certain that the interconnect cable between the batteries is
not
connected. Do not con-
nect the interconnect cable until the system is completely installed.
Observe polarity when connecting the batteries. Connect the battery cable to J7 on the main control board, using the plug-in connector
and cable provided. The battery charger is current-limited and capable of recharging sealed lead acid type batteries (See Figure 2.7 for
battery orientation). The charger shuts off when the system is in alarm. See page 78 for calculation of the correct battery rating.
2.4 Auxiliary DC Power Output Connections
The Special Application Auxiliary DC power output is power-limited (Class 2).
!
WARNING: RISK OF PERSONAL INJURY
BATTERY CONTAINS SULFURIC ACID WHICH CAN CAUSE SEVERE BURNS TO THE SKIN AND EYES AND CAN
DESTROY FABRICS. IF CONTACT IS MADE WITH SULFURIC ACID, IMMEDIATELY FLUSH THE SKIN OR EYES WITH
WATER FOR 15 MINUTES AND SEEK IMMEDIATE MEDICAL ATTENTION.
-
-
+
+
Interconnect
Cable
Figure 2.7 Operating Power Connections
e
c
c
p
o
w
e
r.
w
m
f
VAC
Hot (black)
Ground (green)
Neutral (white)
Connect Earth
Ground wire to
ground stud with
grounding cable
black (-)
red (+)
18 AH
battery
18 AH
battery
TB17
Special Application Power (500 mA @ 24 VDC nominal) is non-resettable power suitable
for powering control modules and End-of Line Power supervision relays.
See Device Compatibility Document for compatible devices.
Figure 2.8 Auxiliary Power Connection
e
c
c
tb
1
7
.w
m
f
Summary of Contents for Notifier FirstCommand Series
Page 84: ...84 Notifier FirstCommand Series Manual P N LS10001 001NF E H 1 8 2018 Notes ...
Page 86: ...Cut along dotted line ...
Page 88: ...Cut along dotted line ...
Page 92: ...92 Notes ...
Page 94: ...Cut along dotted line ...
Page 96: ...NOTIFIER 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 www notifier com ...