Section 1: Product Description
The Notifier FirstCommand NFC-50/100 is a single channel, 50 watt, 25 V
RMS
, emergency voice evacuation panel that may be used for
fire applications, mass notification applications, or both. The NFC-50/100 comes standard with one speaker circuit. The panel provides
the ability to record fourteen field programmable messages (up to 60 seconds each) with an integral microphone or from an external
audio source. An integral power supply with battery charger supplies operational power. A 50 watt audio amplifier is built into each
panel. An optional second 50 watt amplifier (NFC-BDA-25/70V) is also available for backup purposes or to provide an additional 50
watts. The backup amplifier is available in either 25 volts or 70 volts depending on which application is necessary.
Automatic activation of the NFC-50/100 by an FACP is possible via eight Command Input Circuits (CMD) or via the ACS/ANN Bus
serial communications link from the FireWarden-100X, FireWarden-100-2, NFS2-640, and NFS-320 FACPs.
Two Command Input Circuits can be independently field programmed for activation by an FACP Notification Appliance Circuit reverse
polarity or by closure of a supervised normally open contact and six Command Input Circuits activate on contact closure. CMD 1 and
CMD 2 provide terminals for NAC input and output to allow installation of the audio panel anywhere along the NAC circuit being used
to activate it.
If the message generator fails, the system automatically reverts to a backup tone generator.
Power is fed independently to each amplifier so that a short circuit in one amplifier will not shut down the other. Full output power of 50
watts per amplifier is generated while in a low battery condition. Power is not diminished when the optional 70 V
RMS
transformer mod-
ule is installed. Audio is amplified utilizing modern integrated circuits as opposed to transformer technology. This provides for very low
signal distortion for crystal clear audio.
Primary applications for the audio panels include protecting structures such as military facilities, restaurants, schools, auditoriums,
places of worship, buildings with occupancies over 50, etc. The NFC-50/100 is designed to interface directly to addressable or conven-
tional (CMD inputs 1-8) fire alarm control panels or can be used with the NFC-50/125DA panel to distribute audio in systems that
require more than 100 watts.
For Canadian applications, refer to Appendix C on page 83.
1.1 Product Features
•
Modular design for maximum system flexibility and easy expansion
•
Removable terminal blocks for ease of servicing and module replacement
•
50 watts of 25 V
RMS
audio power (expandable to 100 watts)
•
2 amp Notification Appliance Circuit (NAC) output, sync generator, or follower for protocols:
– System Sensor
– Wheelock
– Gentex
•
Optional 70.7 V
RMS
conversion transformer available for the primary amplifier (note that speaker wiring continues to be supervised
in standby, alarm and when background music is playing with this optional transformer installed)
•
Eight Command Input Circuits to activate messages 1 to 8:
– CMD1 and CMD2 are field selectable to be activated from 12 or 24 VDC Notification Appliance Circuits (reverse polarity) or
contact closures
– CMD3-CMD8 are activated by contact closures
•
Speaker Circuits
– single Style Y (Class B) or Style Z (Class A) speaker circuit
– two Style Y (Class B) or Style Z (Class A) speaker circuits (with optional NFC-BDA-25/70V Audio Amplifier installed)
– eight Style Y (Class B) or Style Z (Class A) speaker circuits (with optional NFC-BDA-25/70V
and
NFC-CE6 installed)
•
NFC-50/100 can be controlled by an FACP via the ANN/ACS (EIA-485) link. ACS compatible FACPs include the FireWarden-
100X, FireWarden-100-2, NFS2-640, and NFS-320. ANN compatible FACPs include the FireWarden-100-2.
•
Integral supervised microphone
•
Microphone time-out feature which reverts back to prerecorded message if emergency page exceeds the programmed time
•
Up to 14 recorded messages
•
14 prerecorded messages for fire, emergency, and weather alerts
•
Field-selectable message and custom message recording capability using the local microphone, a USB port, or an external audio
input
•
External Audio Input can be used for background music
•
Up to 60 second message duration for all messages
•
Integral tone generators field selectable for multiple tone types
•
Powered by integral AC power supply or batteries during AC fail
•
Programmable delay of immediate, 2 hours or 6 hours reporting of AC Loss
•
Piezo sounder for local trouble
•
100 event history log
•
Three Form-C relays:
– AC Power Loss Relay - TB1
– System Trouble Relay - TB2
– MNS Active - TB3
•
500 mA (0.5A) Special Application (auxiliary power) output for addressable modules when interfaced with compatible addressable
FACPs and End-of-Line power supervision relays
Summary of Contents for Notifier FirstCommand Series
Page 84: ...84 Notifier FirstCommand Series Manual P N LS10001 001NF E H 1 8 2018 Notes ...
Page 86: ...Cut along dotted line ...
Page 88: ...Cut along dotted line ...
Page 92: ...92 Notes ...
Page 94: ...Cut along dotted line ...
Page 96: ...NOTIFIER 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 www notifier com ...