background image

20

Notifier FirstCommand Series Manual —

 P/N LS10001-001NF-E:H 1/8/2018

Product Description

Optional Equipment

1.5  Optional Equipment

NFC-BDA-25/70V Audio Amplifier Modules

An optional second audio amplifier can be plugged into connectors J10 & J11 located in the upper right of the main control board in the 
NFC-50/100. This amplifier also provides 50 watts of power at 25 V

RMS

 or 70 V

RMS

, depending on the model, and can therefore be used 

to expand system power to 100 watts (providing dual 50 watt speaker circuits) or it can be used as a backup amplifier. The output is  
power-limited (Class 2) and speaker circuit connections to it are provided on the main control board and optional speaker circuit 
expander module. The circuit can be wired for Style Y (Class B) or Style Z (Class A) operation.

LEDs are provided to indicate Amplifier Supervision (green indicates amplifier is functional) and Circuit Trouble (yellow indicates field 
wiring fault or amplifier fault). The LEDs are only visible with the panel door open.

NFC-CE6 Circuit Expander Module

This optional module plugs into connector P1 in the upper middle of the main control board. The NFC-CE6 adds three primary speaker 
circuits to the NFC-50/100. The NFC-CE6 adds three secondary circuits to the system when the NFC-BDA-25/70V Audio Amplifier 
Module is also installed.

NFC-XRM-70V Transformer 70.7 V

RMS

This optional module plugs into connector J12 of the main control board and provides conversion for the integral audio amplifier from 
25 V

RMS

 to 70.7 V

RMS

 at full rated 50 watts output power.

NFC-FFT Fire Fighter Telephone

The NFC-FFT has a telephone handset and user interface that allows an operator to communicate with remotely located telephone hand-
sets in a building. It is housed in its own cabinet with key lock. It requires an external operator interface power connection (24 volts DC) 
from the NFC-50/100 main console or it may be powered from an external 24 VDC power supply such as HP300ULX. The NFC-FFT 
provides supervision, annunciation, and control for the local handset and for up to 24 remote telephone handsets. It provides indications 
of phone activation and corresponding trouble conditions. Refer to the 

NFC-FFT Fire Fighter Telephone

 manual. Not for use in UL2572 

Mass Notification or Canadian applications. 

NFC-50DA Distributed (Remote) Audio

The NFC-50DA is a 50-watt audio amplifier (audio booster) with its own cabinet and key lock. It requires an external data bus connec-
tion and an external audio riser connection from the NFC-50/100 main console. The unit comes standard with 4 speaker circuits. An 
option card, NFC-CE4, provides 4 more speaker circuits for a total of 8. Speaker circuits are activated/de-activated manually or automat-
ically by the NFC-50/100 main console. The unit is capable of either 25 V

RMS

 or 70.7 V

RMS

 operation. Refer to the 

NFC-50/125DA Dis-

tributed Audio

 manual. Not for use in Canadian applications. 

NFC-125DA Distributed (Remote) Audio

The NFC-125DA is a 125-watt audio amplifier (audio booster) with its own cabinet and key lock. It requires an external data bus con-
nection and an external audio riser connection from the NFC-50/100 main console. The unit comes standard with four (4) speaker cir-
cuits. An option card, NFC-CE4, provides 4 more speaker circuits for a total of eight (8). Speaker circuits are activated/de-activated 
manually or automatically by the NFC-50/100 main console. The unit is capable of 25 V

RMS

 operation. Refer to the 

NFC-50/125DA 

Distributed Audio

 manual. Not for use in Canadian applications. 

NFC-50/100DA Distributed (Remote) Audio

The NFC-50/100DA is a 50/100-watt audio amplifier (audio booster) with its own cabinet and key lock. It requires an external data bus 
connection and an external audio riser connection from the NFC-50/100 main console. The NFC-50/100DA is capable of producing up 
to 100 watts of audio power. The amplifier functions as 50 watts with 50 watts as backup, 100 watts with no backup or 100 watts with 50 
watts backup using NFC-BDA-BU. The unit comes standard with 8 speaker circuits. Speaker circuits are activated/de-activated manu-
ally or automatically by the NFC-50/100 main console. The unit is capable of either 25 V

RMS

 or 70.7 V

RMS

 operation. Refer to the 

NFC 

Distributed Audio

 manual. Not for use in Canadian applications. 

NFC-RM Remote Microphone

The NFC-RM has a hand held microphone and is housed in its own cabinet with keyed lock. It requires an external data bus connection, 
an external audio riser connection, and an external operator interface power connection (24 volts DC) from the NFC-50/100 main con-
sole. ALL CALL paging can be broadcast over the speaker circuits by depressing the microphone's push-to-talk switch. Not for use in 
UL2572 Mass Notification or Canadian applications.

NFC-RPU Remote Page Unit

The NFC-RPU has a hand held microphone and 8 message buttons. It is housed in its own cabinet with a keyed lock or thumb lock 
(requires AHJ approval). It also has a 9th button that will activate a monitor module mounted inside the cabinet. This may be used for 
HVAC shutdown applications when the monitor module is connected to the FACP SLC polling loop. The remote page unit requires an 
external data bus connection, an external audio riser connection, and an external operator interface power connection (24 volts DC) from 
the NFC-50/100 main console. ALL CALL paging can be broadcast over the speaker circuits by depressing the microphone's push-to-

NOTE:

Any combination of up to eight audio boosters comprised of NFC-50DA, NFC-125DA, and NFC-50/100DA can be used in the 

system. Their external data bus addresses must be unique and must be sequential. Addresses are set via dipswitches on each unit's PC 
board. Refer to Section 2.14 on page 48.

Summary of Contents for Notifier FirstCommand Series

Page 1: ...Document LS10001 001NF E Rev H 1 8 2018 ECN 18 117 Notifier FirstCommand NFC 50 100 NFC 50 100E Instruction Manual ...

Page 2: ... may not provide adequate warning of a fire Smoke detectors cannot be expected to provide adequate warning of fires caused by arson children playing with matches especially in bedrooms smoking in bed and violent explosions caused by escaping gas improper storage of flammable materials etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a p...

Page 3: ...o do so can damage circuits Remove all electronic assemblies prior to any drilling filing reaming or punching of the enclosure When possible make all cable entries from the sides or rear Before making modifications verify that they will not interfere with battery transformer or printed circuit board location Do not tighten screw terminals more than 9 in lbs Over tighten ing may damage threads resu...

Page 4: ...he appropriate version for a specific application Documentation Feedback Your feedback helps us keep our documentation up to date and accurate If you have any comments or suggestions about our online Help or printed manuals you can email us Please include the following information Product name and version number if applicable Printed manual or online Help Topic Title for online Help Page number fo...

Page 5: ...2 External Audio Input 29 2 5 3 NAC Follower Input 29 2 5 4 Night Ring 30 2 6 Output Circuits 30 2 6 1 Relays 30 MNS Active Relay TB1 30 Trouble Relay TB2 31 AC Power Loss Relay TB3 31 2 6 2 Speaker Circuits 31 2 6 3 Notification Appliance Circuit 32 2 6 4 Speaker Volume Control 33 2 6 5 FACP Data Bus 34 NFW 100X 34 FireWarden 100 2 34 NFS2 640 and NFS 320 35 ACS Mode Wiring 35 2 7 NFC LOC Local O...

Page 6: ...ecific 66 FACP Message Assignment Zone Specific 66 FACP Programming Menus 67 3 6 2 NFS2 640 and NFS 320 68 FACP Programming 68 Section 4 Operating Instructions 70 4 1 Main Control Panel Keypad Labels 70 4 2 NFC 50 100 Switch Functions 70 4 3 LED Indicators 71 4 4 Operation 72 4 4 1 Paging from the Microphone 72 4 4 2 Manual Message Control 72 4 4 3 Fire Alarm Response System Configured for Fire On...

Page 7: ...raw 78 6 3 1 Overview 78 6 3 2 How to use Table 6 2 to calculate system current draws 78 6 4 Calculating the Battery Size 80 6 4 1 NFPA Battery Requirements 80 6 4 2 Selecting and Locating Batteries 80 Appendix A Digital Voice Messages 81 Appendix B Wiring Requirements 82 Appendix C Canadian Applications 83 C 1 Audio Room Isolator Modules 83 C 1 1 Description 83 C 1 2 Panel Programming 83 C 1 3 Ap...

Page 8: ...naling Systems UL 1971 Signaling Devices for Hearing Impaired UL 2572 Communication and Control Units for Mass Notification Systems CAN ULC S524 01 Standard for Installation of Fire Alarm Systems CAN ULC S527 11 Standard for Control Units for Fire Alarm Systems This Class A digital apparatus complies with Canadian ICES 003 Cet appareil numérique de la classe A est conforme à la norme NMB 003 du Ca...

Page 9: ...pander NFC 50DA 50W remote amplifier NFC RPU remote page unit NFC RM remote microphone remote consoles distributed audio NFC 125DA 125W remote amplifier NFC LOC local operator console CHG 120 charger CHG 75 charger external battery charger J7 TB24 TB12 TB22 nfcperi wmf NAC Circuit TB19 visual only NFC FFT firefighter telephone NFC 50 100DA 50 100W remote amplifier ...

Page 10: ...6 Circuit Expander Connector Display Board connector Speaker Volume Control Override Style Y Class B or Style Z Class A Supervised Power Limited Class 2 Special application 0 25 amps max 4 7KΩ ELR 1 2W required for Style Y Class B wiring Primary Secondary Speaker Circuits Style Y Class B or Style Z Class A Supervised Power Limited Class 2 50W integrated output power Use of secondary circuit requir...

Page 11: ...rce other than main control board J2 Connection to main control board P2 Microphone connector J1 USB connector connection to a PC for downloading messages Refer to Section 3 5 5 on page 63 Basic System Connections Display Board Section 1 2 2 disp wmf SW2 Distributed Audio Switch set to UP position if any NFC 50 125DAs are installed in the system Default is the DOWN position JP2 External Data Bus t...

Page 12: ... tional CMD inputs 1 8 fire alarm control panels or can be used with the NFC 50 125DA panel to distribute audio in systems that require more than 100 watts For Canadian applications refer to Appendix C on page 83 1 1 Product Features Modular design for maximum system flexibility and easy expansion Removable terminal blocks for ease of servicing and module replacement 50 watts of 25 VRMS audio powe...

Page 13: ...C Loss Relay TB3 Form C relay contact rating 2 0 amps 30 VDC resistive 0 5 amps 30 VAC resistive NAC Output TB19 Terminals 1 B 2 A 3 A 4 B One 1 Style Y Class B or Style Z Class A circuit Power limited circuitry Class 2 supervised Nominal operating voltage 24 VDC Maximum signaling current for special application power 2 0 amps Maximum signaling current for regulated power 200mA Current limit fusel...

Page 14: ...sure only CMD5 TB7 Terminals 1 2 are input terminals for contact closure only CMD6 TB7 Terminals 3 4 are input terminals for contact closure only CMD7 TB8 Terminals 1 2 are input terminals for contact closure only CMD8 TB8 Terminals 3 4 are input terminals for contact closure only Power limited Class 2 and supervised circuitry Normal Operating Voltage Range 10 5 VDC 29 VDC Maximum Voltage 29 VDC N...

Page 15: ...ower Supply Calculations for additional current draw by option cards that must be consid ered when determining total standby and alarm currents NOTE Zero impedance to ground will cause a ground fault TB20 TB21 TB19 TB24 TB23 TB17 Primary 50W Speaker Circuit 50W max 3 3 amps from supply Secondary 50W Speaker Circuit Optional Amplifier Installed NAC Circuit 2 0 amps max Aux Power 0 5 amp max Speaker...

Page 16: ...r circuit wiring is supervised during standby background music and alarm Output Power 50 watts total Frequency Range 800 2 800 Hz Maximum total capacitance 250 µF Note that the total capacitance for the speaker outputs must not exceed the maximum of 250 µF End of Line Resistor required for Style Y Class B speaker circuit 15 KΩ 1 watt P N ELR 15K TB13 on the main control board ACS ANN EIA 485 elect...

Page 17: ...Note Console assignments are shown here as an example only SPEAKER ZONE 1 SPEAKER ZONE 2 SPEAKER ZONE 3 SPEAKER ZONE 4 SPEAKER ZONE 5 SPEAKER ZONE 6 SPEAKER ZONE 7 SPEAKER ZONE 8 SPEAKER ZONE 9 SPEAKER ZONE 10 SPEAKER ZONE 11 SPEAKER ZONE 12 SPEAKER ZONE 13 SPEAKER ZONE 14 SPEAKER ZONE 15 SPEAKER ZONE 16 SPEAKER ZONE 17 SPEAKER ZONE 18 SPEAKER ZONE 19 SPEAKER ZONE 20 SPEAKER ZONE 21 SPEAKER ZONE 2...

Page 18: ...ndicators visible with door and dress panel open MCB Trouble yellow Integral 50W amplifier electronics fault Option Card Trouble yellow NFC CE6 card missing NFC BDA 25 70V card missing NFC BDA 25 70V electronics fault Amplifier Over Current Fault yellow Missing or incorrect EOL resistor Short circuit on volume control module 1 4 Components Main Control Board The NFC 50 100 main control board conta...

Page 19: ...or two 12AH or two 18AH batteries Batteries The cabinet provides space for up to 18 Amp Hour batteries charged by integral Power Supply Battery Charger with all options installed Dress Panel The Dress Panel is supplied standard with the system It mounts to the cabinet with two supplied screws The Dress Panel protects the user from high voltages and circuit boards from accidental damage Trim Ring A...

Page 20: ... The unit is capable of either 25 VRMS or 70 7 VRMS operation Refer to the NFC 50 125DA Dis tributed Audio manual Not for use in Canadian applications NFC 125DA Distributed Remote Audio The NFC 125DA is a 125 watt audio amplifier audio booster with its own cabinet and key lock It requires an external data bus con nection and an external audio riser connection from the NFC 50 100 main console The u...

Page 21: ...ers Audio File The 520 Hz audio file is available for download at esd notifier com Speakers For a complete list of speakers that can be used in a Notifier FirstCommand system with the above specifications refer to the current ver sion of the Device Compatibility document p n 15378 NOTE Any combination of up to eight remote consoles comprised of NFC RM s NFC RPU s and NFC LOC s can be used in the s...

Page 22: ... wiring should be in accor dance with the National and or Local codes for fire alarm systems Refer to Figure 2 4 for knockouts that cannot be used 2 2 Backbox Installation Removing the Dress Panel 1 Open the door and lift the door off the pin hinges 2 Loosen the two 2 screws that secure the dress panel to the backbox Then lift up to swing the dress panel open 3 Disconnect the ground wire from the ...

Page 23: ...tener in the wall with the screw head protruding 3 Place backbox over the top screw level and secure 4 Mark and drill the left and right upper and lower mounting holes Note Outer holes closest to sidewall are used for 16 O C stud mounting 5 Install remaining fasteners and tighten 6 Carefully reinstall the chassis assembly and dress panel by reversing the steps above Use appropriate precautions to ...

Page 24: ...TR CE B is available for semi flush mount installations Figure 2 4 Cabinet Dimensions Knockout Locations 9050udencl wmf Semi Flush Mounting Do not recess box more than 3 875 into wall to Hinge Slot for Dress Panel Hinge Slot for Dress Panel Semi flush mounting hole Mounting slots for optional Trim Ring Do not use these knock outs ...

Page 25: ...nnect devices A separate Earth Ground connection must be made to ensure proper panel operation and lightning and tran sient protection Do not use conduit for the Earth Ground connection since this does not provide reliable protection Remove the two keps nuts from the grounding stud in the backbox Connect the incoming earth ground wire to supplied cable 71073 with a wire nut Position the ring termi...

Page 26: ...he stud Apply AC power to the panel only after the system is completely installed and visually checked Note that AC power must be applied to the panel before installing the battery interconnect cable refer to the fol lowing section Figure 2 6 Earth Ground Connection eccgnd wmf grounding stud keps nuts Grounding Cable 71073 grounding stud Equipment Ground ...

Page 27: ... is in alarm See page 78 for calculation of the correct battery rating 2 4 Auxiliary DC Power Output Connections The Special Application Auxiliary DC power output is power limited Class 2 WARNING RISK OF PERSONAL INJURY BATTERY CONTAINS SULFURIC ACID WHICH CAN CAUSE SEVERE BURNS TO THE SKIN AND EYES AND CAN DESTROY FABRICS IF CONTACT IS MADE WITH SULFURIC ACID IMMEDIATELY FLUSH THE SKIN OR EYES WI...

Page 28: ...series with its OUT terminals which are used in the reverse polarity configuration to open the outgoing NAC circuit during an NFC 50 100 trouble condition In standby this generates a NAC trouble at the host FACP feature is bypassed in alarm condition These contacts do not open during AC loss at the NFC 50 100 however they are fail safe meaning that a complete loss of power there will open the circ...

Page 29: ...00 Auxiliary Power output and the control module with an EOL relay EOLR 1 3 End of Line resistor supplied with modules 2 5 2 External Audio Input The display provides connection to various ancillary sources See Sections 2 5 4 on page 30 3 5 2 on page 61 and 4 4 15 on page 76 for more information 2 5 3 NAC Follower Input For fire only applications the NAC follower input may be used to trigger the o...

Page 30: ...2 2 for electrical specifications to the external audio input 2 6 Output Circuits 2 6 1 Relays MNS Active Relay TB1 The main control board provides a Form C MNS Active relay The MNS Active Relay will transfer state when any Mass Notification MNS event occurs The system must be enabled for Mass Notification in programming for use of this relay from FACP NAC or NAC Follower output or previous device...

Page 31: ...BDA 25 70V and NFC CE6 The integral amplifier and optional amplifier each provide audio for one Speaker Circuit The circuit can be wired Style Y Class B or Style Z Class A Each supervised and power limited Class 2 circuit is capable of 50 watts of power Refer to the Notifier Device Compatibility Document for a listing of compatible speakers Shielded cable is not required however shielded cable wil...

Page 32: ...ted 24 VDC visual notification appliances only Circuit is supervised and power limited Class 2 Refer to the Notifier Device Compatibility Document for a listing of compatible notification appliances ELR 4 7K 1 2W for Class B Style Y wiring TB19 Polarized Bell Polarized Strobe Polarized Horn Figure 2 16 NAC Wiring Style Y Class B eccnac wmf TB19 Polarized Bell Polarized Strobe Polarized Horn Figure...

Page 33: ...he SP SVC in the speaker circuit Any speakers placed after the SP SVC module will be able to be attenuated 3 An end of line resistor ELR must be installed on the last speaker connected to the SP SVC 4 Attach wires according to the label on the terminal block The DC input output terminals are interchangeable If the SP SVC is the last unit in the Speaker Volume Control Override circuit then an ELR m...

Page 34: ...n 100 2 The FireWarden 100 2 FACP communicates with the NFC 50 100 over the ACS or ANN BUS annunciator link Wiring must be con nected between Terminal TB9 on the FACP and Terminal TB13 on the NFC 50 100 panel 24V SLC ANN BUS PRI ANN BUS SEC A B TB9 TB10 A B Figure 2 19 Connection for NFW 100X to NFC 50 100 NFC 50 100 to other ANN devices esecc wmf NFW 100X TB9 or TB10 B A B A A B ACS SHIELD SLC SL...

Page 35: ...s wired over the ACS annunciator link a monitor module must be used to monitor mass notification events Wire the monitor module to the NFC at TB1 MNS Active Relay in addition to the Data Bus wiring shown above Refer to FACP Program ming on page 68 for information on type IDs Figure 2 21 ACS Connection for NFS2 640 or NFS 320 to NFC 50 100 to other ACS devices located down stream NFS2 640 or NFS 32...

Page 36: ...own below For the external audio riser when the LOC is the last device termination ELR 15K must be connected to pins 5 and 6 on TB5 T taps and multiple home runs to the main control board are not allowed for the external data bus or the external data riser CAUTION EXTERNAL WIRING CONNECTIONS THE NFC LOC IS A SEPARATE DEVICE NOT PART OF THE NFC 50 100 ASSEMBLY J12 TB15 J9 RTZM Rev ECC MCB PCA B A B...

Page 37: ...12 TB15 J9 RTZM Rev ECC MCB PCA B A B A B A B A TB24 TB12 TB22 TB3 TB4 TB5 external operator interface power 24VDC external data bus external audio riser locwirea2 wmf Figure 2 24 Local Operator Console Wiring Class A Style Z TB2 JP2 shown jumpered on pins 2 and 3 NFC 50 100 main control board NFC LOC display board ...

Page 38: ...umper must be on pins 2 and 3 of JS4 as shown below For the external audio riser when the NFC RPU is the last device termination ELR 15K must be connected to pins 4 and 5 on TB2 T taps and multiple home runs to the main control board are not allowed for the external data bus or the external data riser B A B A B A main control board RPU board TB24 TB12 TB22 TB1 TB3 TB2 external operator interface p...

Page 39: ...Remote Page Unit Installation B A B A B A B A main control board RPU board TB24 TB12 TB22 TB1 TB3 TB2 external operator interface power 24VDC external data bus external audio riser rpuwirea wmf Figure 2 26 Remote Page Unit Wiring Class A Style Z JS4 shown jumpered on pins 2 and 3 ...

Page 40: ...he external data bus or the external data riser 2 10 NFC 50DA NFC 125DA NFC 50 100DA Distributed Audio Amplifiers SW2 on the NFC 50 100 s display board must be set to the UP position if any remote audio boosters are installed on the system Refer to the NFC Distributed Audio Amplifier Manual LS10027 001NF E for installation instructions B A A B A B main control board RM board TB24 TB12 TB22 TB3 dat...

Page 41: ... not touch anything If mul tiple external devices are used in the system then the shields must pass through connect to the outgoing shield using wire nuts without touching anything else For Class A Style Z installations the shield from the last external operator interface must be connected to the same NFC 50 100 terminal that the shield originated from NOTE Never use a cable shield as an enclosure...

Page 42: ... limited circuit wiring must enter and exit the cabinet through different knockouts and or conduits A typical wiring diagram for the NFC 50 100 with two speaker circuits is shown below Figure 2 31 Typical Wiring Diagram for UL Power limited Requirements Power limited Circuits Class 2 ecculpwr wmf Power limited Circuits Class 2 Power limited Circuits Class 2 AC Power Nonpower limited Circuit Power ...

Page 43: ...lifier Module with the screws removed in Step 1 It is important to secure the module with the metal screws in order to help protect against electrical transients 4 Plug the supplied power cable into J10 on the main control board then into J1 on the audio amplifier Plug the supplied control cable into J11 on the main control board then into J2 on the audio amplifier 5 Configure the slide switches S...

Page 44: ...opulated on 70V boards NOT USED LED1 Power BDA Power BDA Control Connect J1 to J10 Connect J2 to J11 J12 TB15 J9 RTZM Rev ECC MCB PCA P1 J12 TB15 J9 RTZM Rev ECC MCB PCA 1 Attach four standoffs p n 42227 at locations indicated 2 Align amplifier over standoffs Attach with four screws 3 Attach power harnesses included with amplifier refer to Figure 2 35 Power and Control Harness Connections Amplifie...

Page 45: ...aker circuit configurations with optional amplifier and optional NFC CE6 circuit expander Applications Without Backup Control cable p n 75690 Align tab with notch in board connector Tab Power cable p n 75689 Align cable connectors over spaces and pins Align where there is no pin Figure 2 35 Control and Power Cables Figure 2 36 Enable Switches SW6 is shown enabled Do not enable Figure 2 37 FAIL TES...

Page 46: ... or Class A Outputs Optional amplifier supplies all secondary circuits NFC CE6 adds 3 primary and 3 secondary circuits No backup Primary 50W amp Secondary Figure 2 41 Primary Secondary with Expander and Optional Amplifier CE6 5 6 7 8 TB20 on main control board TB21 on main control board TB1 on NFC CE6 primary power TB4 on NFC CE6 secondary power TB2 on NFC CE6 primary power TB5 on NFC CE6 secondar...

Page 47: ...what other option modules are installed See the NFC XRM 70V Installation Document Refer to the drawing below 50W circuit 1 2 3 4 Primary with Expander and Backup 50W for primary 50W for backup Four Class B or Class A Outputs NFC CE6 adds 3 primary speaker circuits Optional Amplifier is the backup Primary Figure 2 43 Primary with Expander and Optional Amplifier Backup CE6 Primary Backup 50W amp Bac...

Page 48: ...te that these four 4 consoles occupy two 2 data bus addresses each The second address is already reserved in the system for each console Up to eight 8 distributed amplifiers NFC 50DA and NFC 125DA can be used in the system Their external data bus addresses must also be unique and sequential All addressing must also be set in user programming Refer to Section 3 2 3 on page 55 Bus Address Device Dip...

Page 49: ...ed in the cabi net Pay close attention when setting addresses Bus Address Device Dipswitch Setting on NFC 50DA SW1 Dipswitch Setting on NFC 125DA SW1 Dipswitch Setting on NFC 50 100DA SW3 20 External Amp 1 21 External Amp 2 22 External Amp 3 23 External Amp 4 24 External Amp 5 25 External Amp 6 1 2 3 4 5 6 ON 1 2 3 4 5 ON 1 2 3 4 5 6 7 8 ON 1 2 3 4 5 6 ON 1 2 3 4 5 ON 1 2 3 4 5 6 7 8 ON 1 2 3 4 5 ...

Page 50: ...essing External Data Bus Devices 26 External Amp 7 27 External Amp 8 Bus Address Device Dipswitch Setting on NFC 50DA SW1 Dipswitch Setting on NFC 125DA SW1 Dipswitch Setting on NFC 50 100DA SW3 1 2 3 4 5 6 ON 1 2 3 4 5 ON 1 2 3 4 5 6 7 8 ON 1 2 3 4 5 6 ON 1 2 3 4 5 ON 1 2 3 4 5 6 7 8 ON ...

Page 51: ...rd Securely configure networks and firewalls Assess security risks Develop a Disaster and Recovery Plan Develop a Backup and Recovery Strategy Install configure and maintain anti virus software on all computers which access the panel Keep the operating system updated and maintain version compatibility with the panel Deliver all required system information upon delivery to the system owner Train en...

Page 52: ...rd The default password for the NFC 50 100 is 0000 New Password It is recommended that the password be changed to increase system security Valid passwords contain four digits from 0000 9999 Verify New Password Re enter the new password for confirmation Inactivity Timeout Select the amount of time 5 minutes 10 minutes 20 minutes 30 minutes or 60 minutes the system is allowed to remain idle before a...

Page 53: ...Canadian requirements See Appendix C for more information Class A Style Z Select enable if all circuits on the NFC will operate in Class A Style Z or disabled if all circuits will operate in Class B Style Y Canadian Isolator Modules If audio isolator modules are required in the system select enabled Refer to Audio Room Isolator Mod ules on page 83 for more information AC Loss Delay The reporting o...

Page 54: ... the NFC and the maximum number that can be connected to each NAC Make sure that the NAC maximum current is not exceeded Aux Power Selects whether this power is Constant or Resettable use from TB17 Speaker Volume Control NAC If the Cooper Wheelock SP SVC module is installed on TB23 of the main control board allowing man ual volume setting for telephone paging and background music for a specific sp...

Page 55: ...alled at addresses 4 6 8 10 12 14 16 and 18 as either Local Operator Console or Remote Microphone Note that the NFC RPU and NFC RM are both considered remote microphones Refer to Section 2 14 Addressing External Data Bus Devices for information on dipswitch settings Note that Address 2 is reserved for the POC Mic Gain is the microphone s transmitting volume control The gain number is automatically...

Page 56: ...e system 70VAC Option For every programmed 50W remote amplifier select whether a 70V transformer has been Installed or Not Installed 70V operation is not available on the 125W model 3 2 4 Message Buttons Message Buttons Assignment Message buttons 1 14 can be used to broadcast prerecorded messages over the system They must be designated as Fire Evacuation or Mass Notification in the Assignment fiel...

Page 57: ... Send to Panel button to save changes to the panel Selecting the Load Defaults button will apply default programming to the given page To then save the applied default settings to the panel press the Send to Panel button The Main Menu button will disregard any programming selections and jump back to the main menu screen Changes made to panel programming will not be applied until complete log out o...

Page 58: ...ecording must then be disabled Simply click the Disable Recording button 3 3 2 USB File Options The NFC system allows software files to be saved shared and transferred via the computer s USB port The program file must be named CONFIG TXT When saving the program file to USB it is vital that no other files with the same name exist on the drive The existing file will be completely overwritten Only fi...

Page 59: ... The Speaker Circuit Button Assignment page reflects what has been programmed into the Address Assignment page Refer to Speaker Circuit Address Assignment on page 55 Based on the example above the NFC system s primary operator console has four 4 pro grammed speaker circuits a remote amplifier at address 20 has two 2 speaker circuits and a second remote amplifier at address 21 has three 3 speaker c...

Page 60: ...n shows the system s event history A maximum of 100 events can be viewed starting with the most recent This information can be erased by clicking the Clear History button Clicking the Print button will activate the print dialog box Print options are selected in this box Note that the Date and Time in the heading of the print screen correspond to those of the panel and not the computer The Unit ID ...

Page 61: ...ed to control the recording erasing process When in Local Record mode the display board s LEDs will function as follows 3 5 2 External Audio Input The external audio input allows customized pre recorded messages to be loaded into a message slot 1 Wire a speaker cable with 1 8 mini plug Radio Shack p n 42 2454 to EXT Audio GND and IN terminals on the display board 2 Plug the mini plug into the Line...

Page 62: ... start recording When the PC message is done press zone button 19 again to stop recording The yellow zone LED 2 will stay lit until completed The green LED for zone button 2 will light after the recording is complete Enter programming mode again and deselect Message Record Mode 3 5 3 Microphone Messages can be recorded into the system using the onboard microphone 1 Enter programming mode at the ma...

Page 63: ...User Message Messages stored in message slots 1 14 can be erased 1 Enter programming mode at the main control board 2 Enable Recording Mode in the system s message recording programming section Refer to Section 3 5 1 on page 61 The display board will then light the green zone 1 14 LEDs for all message slots that contain messages 3 Press zone button 24 on the display board then zone button 1 14 for...

Page 64: ...the user if there is no message stored blank in the selected message slot location 4 Repeat steps 1 through 3 for any addition messages to be read or close VL software if finished Moving a Message to a Different Slot To move a message from one message slot location to another first read the desired message from its current message location into the PC and then write this message file from the PC t...

Page 65: ...on is when one or more devices programmed to Zones 33 through 40 is also activated If the newly activated zone is programmed to a message with a higher priority then Zone 32 the higher pri ority message will be generated to all circuits Note 2 Messages have a priority scheme with Message 1 having the highest priority and Message 14 having the lowest priority For example If an addressable device ac...

Page 66: ...e 1 in example below will be generated over all speaker circuits FACP Message Assignment Zone Specific The FACP can be programmed to allow a specific addressable input device to generate one of fourteen messages over any speaker cir cuit Any one of the fourteen messages can be programmed to each of the available zones Zone 1 through Zone 99 In the following example assume that Zone 5 is programmed...

Page 67: ...ng Mode by pressing the 2 key The following screen will be displayed Entering the Master level password default 00000 will cause the following screen to appear Select the Zone Setup option by pressing 3 The following screens will be displayed Pressing 3 while viewing Zone Setup Screen 3 will cause the following screen to be displayed Zone 5 and Zone 35 Zone 7 and Zone 35 Addressable Pull Station a...

Page 68: ... Annunciator Group M must be selected for annunciator address number 1 in FACP programming using VeriFire Tools FACP Programming The NFS2 640 or NFS 320 must be programmed to operate with the NFC 50 100 The following table summarizes the steps involved in programming the FACP ACS Annunciator The NFC 50 100 communicates with the FACP via the ACS link Enable the ACS Annunciator as described in the N...

Page 69: ...ed to A1p11 and A1p40 A general alarm will play message 1 and activate an all call on the FirstCommand VeriFire Tools must be used for speaker and circuit and message control IMPORTANT Messages have a priority scheme with Message 1 having the highest priority and Message 14 having the lowest priority The highest priority message will always be generated over all activated speaker circuits FireVoic...

Page 70: ...for equal priority then the ALL CALL will only occur when the system is not already in use System in Use LED is not on remote console active LED is not on Refer to the SYSTEM CONTROL button description When the operator completes the page any previously interrupted emergency broadcast will resume Previously initiated emergency broadcast will also resume after the push to talk PTT switch is held fo...

Page 71: ...is selected those fault LEDs represent the main console status Trouble Silence This button is used to manually silence the local trouble sounder Console Lamp Test This button is used to test the console LEDs and local sounder When pressed all LEDs temporarily light and the local sounder is turned on temporarily 4 3 LED Indicators Refer to Figure 1 3 NFC 50 100 Keypad on page 17 Fire System Active ...

Page 72: ...rcuits are off and all relays are in their normal state 4 4 1 Paging from the Microphone 1 The NFC 50 100 main console must be in control of the system to perform a page If the green System in Use LED is lit press the SYSTEM CONTROL button The NFC 50 100 is ready to page once the System in Use LED turns off and the System Control LED lights steady If the System Control LED is already lit this acti...

Page 73: ...tton the system will Turn the appropriate speaker zone LED s on steady Turn the appropriate speaker circuit s on Turn the appropriate message LED on steady Turn the appropriate audio amplifier s on Turn the 24 VDC aux power output on if programmed Turn the speaker volume control override on Turn the System in Use LED on steady Activate the MNS active relay if the system is programmed for mass noti...

Page 74: ...System Configured for Combo Fire Mass Notification with Fire Priority If the restoral is for a fire alarm only under this configuration then the system will respond as in Section 4 4 4 above If the restoral is for a mass notification alarm alert only under this configuration then the system will respond as in Section 4 4 8 above and additionally will Signal the FACP of the restoral using the FACP ...

Page 75: ...ssociated peripheral console fault LED turns on steady For a distributed amplifier fault the associated distributed fault LED turns on steady For distributed amplifier faults the following will occur on the display when the operator uses the DIAGNOSTIC button to select a dis tributed amplifier for more specific indication For a power fault the AC power LED turns off For a ground fault the ground f...

Page 76: ...display board terminal TB5 can serve as any one of the following A background music input A message recording input from an audio source A general paging input from a paging microphone or telephone system A night ring input from a telephone system The function of the external audio input must be selected in programming Refer to External Audio Input on page 61 For external audio input electrical re...

Page 77: ...d programming utility 3 Configure the NFC 50 100 for Single Zone operation Refer to Section 3 Programming on page 51 4 Record any new voice messages as described in Section 4 Operating Instructions on page 70 5 3 System Requiring Greater Than 100 Watts of Audio Power 1 Install backbox and chassis assembly as described in Section 2 Installation on page 22 2 Connect the external Audio Riser and exte...

Page 78: ...e to power the system during a primary power loss To calculate the non fire alarm load on the secondary power source use Calculation Column 1 in Table 6 3 The NFC 50 100 must support a larger load current during a fire alarm condition and primary power loss To calculate the fire alarm load on the secondary power source use Calculation Column 2 in Table 6 3 When calculating current draw and the bat...

Page 79: ... in alarm 1 max X 0 100 1 max X 0 235 NFC CE6 Speaker Circuit Expander 1 max X 0 020 1 max X 0 189 NFC LOC Local Operator Console 2 2 Maximum combined total of eight 8 operator interface devices X 0 085 X 0 100 NFC RM Remote Microphone 2 X 0 050 X 0 064 NFC RPU Remote Page Unit 2 X 0 050 X 0 068 NFC 50DA NFC 125DA NFC 50 100DA Remote Amplifiers3 3 Maximum combined total of eight 8 remote amplifier...

Page 80: ...ted inside the cabinet door 6 4 1 NFPA Battery Requirements NFPA requires 24 hours of standby plus 15 minutes activation for audio systems The total ampere hours required cannot exceed 26 AH with an internal charger An external charger can be used to increase the total ampere hours internal charger must be disabled 6 4 2 Selecting and Locating Batteries Select batteries that meet or exceed the tot...

Page 81: ...the nearest exit and leave the building Do not use the elevator but proceed to the nearest exit and leave the building Fire Alert Message May I have your attention please An alarm has been activated We are investigating the cause Please remain calm and stand by near the speakers for further instructions Emergency Evacuation Messages May I have your attention please May I have your attention please...

Page 82: ...gainst EMI and AFI emissions and susceptibility determine using Lite Calcs utility see note 3 3 Must also meet NFPA 72 Standards for minimum and maximum sound levels 12 18 AWG ECC CE6 speaker circuits TB1 TB6 untwisted unshielded twisted shielded see note 2 determine using Lite Calcs utility see note 3 12 18 AWG external data bus TB12 twisted shielded max loop impedance 13 2 ohms 12 18 AWG externa...

Page 83: ...cuit for ten minutes during alarm Resounding will occur automatically after ten minutes or upon activation of a new audio alert C 1 2 Panel Programming Canadian Configuration and Canadian Isolator Modules must be enabled in ECCNFC programming Refer to General NAC Options on page 53 In addition NAC Type must be set for steady operation See NAC Options on page 54 C 1 3 Applications The following fig...

Page 84: ...84 Notifier FirstCommand Series Manual P N LS10001 001NF E H 1 8 2018 Notes ...

Page 85: ...n instructions Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6 Zone 7 Zone 8 Zone 9 Zone 10 Zone 11 Zone 12 Zone 13 Zone 14 Zone 15 Zone 16 Zone 17 Zone 18 Zone 19 Zone 20 Zone 21 Zone 22 Zone 23 Zone 24 Figure 1 1 Slide in Labels Top Row of Keypad MICROPHONE TROUBLE OK TO PAGE MESSAGE 1 MESSAGE 2 MESSAGE 3 MESSAGE 4 MESSAGE 5 MESSAGE 6 MESSAGE 7 MESSAGE 8 MICROPHONE TROUBLE OK TO PAGE MNS CONTROL MNS C...

Page 86: ...Cut along dotted line ...

Page 87: ... Section Figure 1 2 Slide in Labels Bottom Row of Keypad DIAGNOSTIC REMOTE AMPS TROUBLE SILENCE AC POWER GROUND FAULT CHARGER FAULT BATTERY FAULT DATA BUS FAULT NAC FAULT NAC ACTIVE SYSTEM TROUBLE AUDIO RISER FAULT CONSOLE LAMP TEST MAIN CONSOLE ...

Page 88: ...Cut along dotted line ...

Page 89: ...ss A Style Z programming 53 Class B 20 CMD 28 see also Command Input Circuit 12 CMD Activation Contact Closure 28 CMD input style 57 CMD inputs 28 CMD1 28 see also Command Input Circuit 14 CMD2 28 see also Command Input Circuit 14 CMD3 28 see also Command Input Circuit 14 CMD4 28 see also Command Input Circuit 14 CMD5 28 see also Command Input Circuit 14 CMD6 28 see also Command Input Circuit 14 C...

Page 90: ...ring 43 NFC FFT 20 NFC LOC 21 NFC RM 20 see also Remote Microphone 13 NFC RPU 20 NFC XRM 70V 20 Installation 47 see also transformer 47 NFS2 640 programming 68 NFS 320 programming 68 Nonpower limited Circuit 42 Notification Appliance Circuit 12 28 O OK to Page LED 71 Operation 72 Option Modules 20 43 Output Circuit 30 P Paging Operation 71 Selective Zone 71 paging 72 paging timeout 54 Password Mas...

Page 91: ...le LED 72 T time out feature microphone 12 tone 12 56 duration 56 generator 12 Transformer 70 7 volt Conversion 47 trim ring 24 Trouble Relay 12 13 31 Contact Rating 13 Trouble Relay programmable 13 Trouble Response 75 Trouble Restoral 75 Trouble Silence 71 U UL Power limited Wiring 42 unit operation 53 V voice evacuation panel 12 W wiring from NFC 50 100 to FireWarden 100 2 34 NFW 100X 34 Wiring ...

Page 92: ...92 Notes ...

Page 93: ...er Section 4 LED Indicators FIRE SYSTEM ACTIVE Green LED that turns on steady when the FACP is in alarm MNS CONTROL Green LED that turns on steady when an operator has ini tiated a mass notification event by pressing the MNS Control button or by pressing an MNS message button SYSTEM CONTROL Green LED that turns on steady when the main con sole has control of the audio system SYSTEM IN USE Green LE...

Page 94: ...Cut along dotted line ...

Page 95: ...ITH RESPECT TO THE PRODUCTS TRADEMARKS PROGRAMS AND SERVICES RENDERED BY MANUFACTURER INCLUDING WITHOUT LIMITATION INFRINGEMENT TITLE MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE MANUFACTURER SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF OR AS A RESULT OF PERSONAL COMMERCIAL OR INDUSTRIAL USES OF ITS PRODUCTS This document constitutes the only warra...

Page 96: ...NOTIFIER 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 www notifier com ...

Reviews: