66
Notifier FirstCommand Series Manual —
P/N LS10001-001NF-E:H 1/8/2018
Programming
Programmed Activation by FACP
•
For non-General Alarm applications where input devices and/or messages are mapped to specific zones, Message 1 must be
removed from Zone 00 programming.
FACP Message Assignment - Speaker Specific
The NFC-50/100 has the capability of generating up to fourteen different messages. Any one of the fourteen messages can be pro-
grammed to each of the speaker circuit zones Z32 through Z56.
Example 1:
If an addressable device programmed to Zone 35 is activated and no other devices are active, the message programmed for
Zone 35 will be generated over speaker circuit 3.
Example 2:
If an addressable device (address 09 in example below) programmed to Zone 35 is activated and a second addressable
device (address 15 in example below) programmed to Zone 36 is activated, the highest priority message programmed to either Zone 35
or Zone 36 (Message 3 in example below) will be generated over speaker circuits 3 and 4. If an addressable device (address 21 in exam-
ple below) programmed to Zone 32 is then activated, the highest priority message programmed to Zone 32, 35, or 36 (Message 1 in
example below) will be generated over all speaker circuits.
FACP Message Assignment - Zone Specific
The FACP can be programmed to allow a specific addressable input device to generate one of fourteen messages over any speaker cir-
cuit. Any one of the fourteen messages can be programmed to each of the available zones (Zone 1 through Zone 99). In the following
example, assume that Zone 5 is programmed to Message 1, Zone 7 is programmed to Message 2, and Zone 35 is not programmed to a
message.
Addressable Pull Station
Programmed to
Message 3
Zone 35
activate
Speaker Circuit 3
e
c
c
e
x
1
.w
m
f
Addressable Pull Station
(address 21)
Programmed to
Zone 32
Message 4
(lowest priority of the three)
Message 3
(2nd highest priority of the three)
Message 1
(highest priority of the three)
Addressable Pull Station
(address 09)
Zone 35
Programmed to
Zone 36
Programmed to
Addressable Pull Station
(address 15)
activate
activate
activate
Speaker Circuit 1
Speaker Circuit 2
Speaker Circuit 3
Speaker Circuit 4
Speaker Circuit 5
Speaker Circuit 6
Speaker Circuit 7
Speaker Circuit 8
Speaker Circuit 9
Speaker Circuit 10
Speaker Circuit 11
Speaker Circuit 12
Speaker Circuit 13
Speaker Circuit 14
Speaker Circuit 15
Speaker Circuit 16
Speaker Circuit 17
Speaker Circuit 18
Speaker Circuit 19
Speaker Circuit 20
Speaker Circuit 21
Speaker Circuit 22
Speaker Circuit 23
Speaker Circuit 24
e
c
c
e
x
2
.w
m
f
Summary of Contents for Notifier FirstCommand Series
Page 84: ...84 Notifier FirstCommand Series Manual P N LS10001 001NF E H 1 8 2018 Notes ...
Page 86: ...Cut along dotted line ...
Page 88: ...Cut along dotted line ...
Page 92: ...92 Notes ...
Page 94: ...Cut along dotted line ...
Page 96: ...NOTIFIER 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 www notifier com ...