Notifier FirstCommand Series Manual —
P/N LS10001-001NF-E:H 1/8/2018
83
Appendix C: Canadian Applications
When using the NFC in Canadian Applications, note the following:
•
The NFC-50/100 is for fire evacuation use only.
•
The NFC-50DA, NFC-125DA, and NFC-50/100DA amplifiers are not permitted for use in Canada.
•
The NFC-RPU and NFC-RM are not permitted for use in Canada.
•
The NFC-50/100 must be mounted next to the FACP.
C.1 Audio Room Isolator Modules
C.1.1 Description
The audio isolator modules described below may be used to isolate short circuits during alarm signaling.
AIM-1A
This module provides isolation to a separate circuit on an audio riser. A short circuit on an AIM-1A speaker circuit will not dis-
able other speaker circuits on the riser.
RSM-1A
This module works the same as the AIM-1A, with the exception that there is a silence button for in-suite operation. The silence
button will silence the audible signal to the module’s circuit for ten minutes during alarm. Resounding will occur automatically after ten
minutes or upon activation of a new audio alert.
C.1.2 Panel Programming
“Canadian Configuration” and “Canadian Isolator Modules” must be enabled in ECCNFC programming. Refer to “General/NAC
Options” on page 53. In addition, “NAC Type” must be set for steady operation. See “NAC Options” on page 54.
C.1.3 Applications
The following figures illustrate typical applications for audio isolator modules. Jumper settings are specified below to configure opera-
tion with speaker circuits. Jumpers are located on the back side of each module.
AIM-1A
Remove jumpers 1 & 2.
RSM-1A
Remove jumpers 1 & 2.
Jumper 3
AIM-1A
RSM-1A
v
o
ic
e
-A
IM
-1
b
a
c
k
.w
m
f
v
o
ic
e
-R
S
M
-1
b
a
c
k
.w
m
f
Figure C.1 Jumper Settings
From
NFC
Speaker
Circuit
From
NFC
Speaker
Circuit
TB19 on
NFC
NAC
(24VDC)
TB19 on
NFC
NAC
(24VDC)
AIM-1A/
RSM-1A
AIM-1A/
RSM-1A
to next module, ELR,
or Class A return
to next module, ELR, or Class A return
24V to next
device
24V to
next
device
optional
4-wire
return
Figure C.2 RSM-1A/AIM-1A Module Wiring
e
c
c
ri
s
e
rm
o
d
_
rs
m
a
im
.w
m
f
e
c
c
ri
s
e
rm
o
d
_
rs
m
a
im
u
n
s
u
p
v
.w
m
f
Supervised Speakers
Non-supervised Speakers
Summary of Contents for Notifier FirstCommand Series
Page 84: ...84 Notifier FirstCommand Series Manual P N LS10001 001NF E H 1 8 2018 Notes ...
Page 86: ...Cut along dotted line ...
Page 88: ...Cut along dotted line ...
Page 92: ...92 Notes ...
Page 94: ...Cut along dotted line ...
Page 96: ...NOTIFIER 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 www notifier com ...