IDR-2P, -2A & -6A Repeaters User Manual
Operation
30
997-411-000-9, Issue 9
March 2008
4.5.3.2 Set Function
This option ensures that the IDR-6A repeats
the panel display in the correct manner.
Use the
and
pushbuttons to select the
required function (or cancel):
a. Standard. Select this if the Panel Settings
of the panel being repeated are set to
Standard using local zones or using
network zones.
b. VdS. Select this if the Panel Settings of the
panel being repeated are set to VdS using
local zones or using network zones.
c. AFNOR. This option is for use only with F-
NF3000 fire control panels.
Selecting either Standard or VdS you are now
prompted to select one of the following options:
a. PANEL Zones (Loop/Address). Select this
if the Panel Settings of the panel being
repeated are set to Standard or VdS using
local zones.
b. NETWORK Zones (Loop/Address). Select
this if the Panel Settings of the panel being
repeated are set to Standard or VdS using
network zones.
If the function has been changed, press the
pushbutton to confirm and return to the
User Menu.
4.5.3.3 Access Level for MUTE BUZZER
This option selects the access level at which
the MUTE BUZZER pushbutton can be
operated (level 2 = keyswitch operation).
Use the
and
pushbuttons to select the
required level, then press the
pushbutton
to return to the User menu.
Configuration Menu:
1:Set Language
2:
3:Access Level for MUTE BUZZER
4:Silence/Resound pushbutton function
User Tue 05-Nov-2001 11:20:07
Set Function
Configuration Menu:
1:Set Language
2:Set Function
3:
4:Silence/Resound pushbutton function
User Tue 05-Nov-2001 11:20:07
Access Level for MUTE BUZZER