IDR-M Mimic Installation & Commissioning Manual
Intr
oduction
2
997-412-000-3, Issue 3
June 2005
1.2
System Design and Planning
It is assumed that the system, of which the
IDR-M mimic is a part, has been designed by
a competent fire alarm system designer in
accordance with the requirements of EN54
Part 14 and any other local codes of practice
that are applicable.
1.3
General
The IDR-M mimic can be used with the following
fire control panels:
a. ID2000 Series.
b. ID3000 Series.
c. ID50.
The IDR-M mimic can have up to eight IDR-MD
Driver boards. Each Driver board has:
a. 64 output channels, arranged in two banks
of 32. Each bank has four groups of eight
outputs, and each group can drive either
LEDs or relays, dependant upon a jumper
link selection on the board. The groups are
configured independently (i.e. on the same
bank and/or board, some groups may drive
LEDs and others relays). Outputs within a
group cannot be configured independently.
b. 8 I/O lines. These can be configured to drive
additional relays or to read switches (first
board only), depending upon the
configuration method used during
commissioning (see below).
Installation
The IDR-M mimic is easy to install providing the
recommended procedures described in this
manual are followed. To avoid inadvertent
contamination of the mimic PCB assemblies, the
manufacturer recommends they be installed in
the enclosure only after all other trades have
completed their tasks.
Commissioning
To commission the IDR-M mimic, follow the
recommended procedures described in this
manual. The IDR-M mimic can be configured
by one of two methods:
a. Setting hardware switches to relate the
mimic displays to zonal events. In this case
the IDR-M mimic can only indicate the
status of one stand-alone fire control panel.
b. Use of the IDR Configuration Tool to set
software rules which relate the mimic
displays to zonal or non-zonal events. The
Tool provides a higher level of flexibility than
that available using the hardware switches.
Only fit the mimic display
PCB assemblies after all
the other trades have
completed their tasks!