LCD6000
Installation manual
PAGE - 13
LCD6000_manu-inst
Doc. M-184.1-LCD6000T-ENG Rev A.2
NOTIFIER ITALIA
Where:
Address
Select the item “Address” to assign the peripheral number to the LCD-6000T terminal device.
Use the arrow keys to select the peripheral number and press the Lists key
to confirm the datum. The useful
addresses to be assigned to the
LCD-6000T are from 1
÷
16
The address assigned to the terminal device is unique, therefore it is not possible to have several
terminals with the same address.
Buzzer volume
By selecting the item “Buzzer Volume” through the arrow keys and pressing the Lists key to confirm, the user
can program the buzzer volume in case of alarm or breakdown.
Test Led
By selecting the item “Test Led” through the arrow keys and pressing the Lists key to confirm, the panel
performs the lamp-test function.
Test LCD
By selecting the item “Test LCD” through the arrow keys and pressing the Lists key to confirm, the panel
performs the display test.