PAGE - 14
Installation manual
LCD6000
NOTIFIER ITALIA
Doc. M-184.1-LCD6000T-ENG Rev A.2
LCD6000_manu
RS.485 serial Line
The LDC6000 panel is connected to the control unit through the RS.485 serial line.
The RS.485 line must be installed in “MULTI-POINT” configuration (daisy chain).
Each peripheral must be programmed with an address from 1
16. Refer to the installation manuals of each peripheral.
Installation in “Multi-Point” configuration (Daisy Chain)
separate power
Connect two wires from the RS.485
terminals of the control unit (LIN+
and LIN- terminals) to the
correspondent terminals of the first
device on the line.
Continue the wiring from the first
device to the subsequent one, and
so on.
Install the line end resistance (120-
150
, 0.5W) on both the control
unit terminals and the terminals of
the last line device.
The maximum admitted length from
the control unit to the last device is
1.5km.
Use screened cable of appropriate
section 9574 or 9575 Belden type
AM-4000
17
+24V GND
EOL= 120
LCD-6000T
16
11
1
2
3
4
+24V GND
EOL= 120
31
30
LCD-6000T
1
2
3
4
5
5
GND
+24V
AM-4000
17
+24V GND
EOL= 120
LCD-6000T
16
11
1
2 3
4
+24V GND
EOL= 120
LCD-6000T
1
2
3
4 5
5
6 7
6 7
AM-6000
9
+24V GND
EOL= 120
LCD-6000T
8
7
1
2 3
4
+24V GND
EOL= 120
LCD-6000T
1
2
3
4 5
5
6 7
6 7
Typical RS.485 Multi-point connection (Daisy Chain) separate power
Note: Terminals 6 and 7 are not used on the LCD600T panel