Zones/Panel Circuits Status Holding Registers
Register Mapping
The holding register addresses and the panel circuits contained in these addresses are detailed in
.
Table 5.7 Panel Circuits
The maximum panel circuit points by fire panel is described in
Register Address
Panel Circuits
49111–49118
P1.1–P1.8
49119–49126
P2.1–P2.8
49127–49134
P3.1–P3.8
49135–49142
P4.1–P4.8
49143–49150
P5.1–P5.8
49151–49158
P6.1–P6.8
49159–49166
P7.1–P7.8
49167–49174
P8.1–P8.8
49175–49182
P9.1–P9.8
49183–49190
P10.1–P10.8
49191–49198
P11.1–P11.8
49199–49206
P12.1– P12.8
Table 5.8
Supported Circuits by Panel
Panel
Max. Panel Circuits Points
NFS-320
Not Supported
NFS-640
8
NFS2-640
Not Supported
NFS-3030
12
NFS2-3030
Not Supported