Register Mapping
Analog Values Input Registers
5.8 Analog Values Input Registers
are only available for 4–20 mA modules. Refer to
4.4, "Analog Values and Trending"
for details
regarding analog values.
5.9 Panel and System Troubles Input Registers
Sixty-four 16-bit registers are reserved for panel troubles and one register is assigned as an overall panel trouble indicator as shown in
.
A single bit is reserved for each trouble in the system. The assignment of bits to trouble codes is shown in
Table 5.15 Input Register Analog Values
Start Address
End Address
Analog Value (16 bits)
30001
30200
L1M1–L1M159
30201
30400
L2M1–L2M159
30401
30600
L3M1–L3M159
30601
30800
L4M1–L4M159
30801
31000
L5M1–L5M159
31001
31200
L6M1–L6M159
31201
31400
L7M1–L7M159
31401
31600
L8M1–L8M159
31601
31800
L9M1–L9M159
31801
32000
L10M1–L10M159
Table 5.16 Panel and System Troubles Input Register Addresses
Start Address
End Address
Description
35000
35000
Panel Trouble Summary
(Total number of Trouble bits set for the node)
35001
35064
Panel Troubles