background image

Document LS10129-001NF-E  Rev: C
7/25/2018   ECN: 18-323

Addressable Fire Alarm Control Panel

NFW-50X

Manual

Summary of Contents for NOTIFIER NFW-50X

Page 1: ...Document LS10129 001NF E Rev C 7 25 2018 ECN 18 323 Addressable Fire Alarm Control Panel NFW 50X Manual ...

Page 2: ...rovide adequate warning of a fire Smoke detectors cannot be expected to provide adequate warning of fires caused by arson children playing with matches especially in bedrooms smoking in bed and violent explosions caused by escaping gas improper storage of flammable materials etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermin...

Page 3: ...e all electronic assemblies prior to any drilling filing reaming or punching of the enclosure When possible make all cable entries from the sides or rear Before making modifications verify that they will not interfere with battery transformer or printed circuit board location Do not tighten screw terminals more than 9 in lbs Over tighten ing may damage threads resulting in reduced terminal contact...

Page 4: ...iate version for a specific application Documentation Feedback Your feedback helps us keep our documentation up to date and accurate If you have any comments or suggestions about our online Help or printed manuals you can email us Please include the following information Product name and version number if applicable Printed manual or online Help Topic Title for online Help Page number for printed ...

Page 5: ...odule 18 N ANN I O LED Driver Module 18 N ANN LED Annunciator Module 18 N ANN RLY Annunciator Module 18 1 7 Getting Started 19 1 8 Telephone Requirements and Warnings 19 1 8 1 Telephone Circuitry 19 1 8 2 Telephone Company Rights and Warnings 19 Section 2 Installation 20 2 1 Mounting the Backbox 20 2 2 Power 23 2 2 1 AC Power and Earth Ground Connection 23 2 2 2 Battery Power 23 2 2 3 Special Appl...

Page 6: ...ne 65 Zones Installed 66 Zones Enabled 66 Zones Disabled 66 Zone Type 67 Zones Available 67 3 6 4 Loop Setup 67 Class 68 Loop Protocol 68 Device Addressing 68 3 6 5 System Setup 68 Function Keys 69 Banner 69 Time Date 70 Timers 71 NACS Notification Appliance Circuits 72 Relays 75 Canadian Option 75 Waterflow Silenceable 76 Auxiliary Power 76 Trouble Reminder 76 Language 76 Charger Enable 76 4XTM S...

Page 7: ...on 107 4 12 Programmed Zone Operation 107 4 13 Disable Enable Operation 107 4 14 Waterflow Circuits Operation 107 4 15 Detector Functions 107 4 16 Time Functions Real Time Clock 107 4 17 Synchronized NAC Operation 107 4 18 Coded Operation 108 4 19 Presignal 108 4 20 Positive Alarm Sequence 108 4 21 Special System Timers 109 4 21 1 Silence Inhibit Timer 109 4 21 2 Autosilence Timer 109 4 21 3 Troub...

Page 8: ...view 125 9 3 2 How to Calculate System Current Load 125 9 4 Calculating the Battery Size 127 9 4 1 NFPA Battery Requirements 127 9 4 2 Selecting and Locating Batteries 127 Appendix A Software Zones 128 A 1 Correlations 128 Appendix B Default Programming 133 Appendix C NFPA Standard Specific Requirements 134 C 1 MBT 1 Municipal Box Trip Silenceable 137 Appendix D Wire Requirements 138 D 1 NAC Wirin...

Page 9: ...A 232E Serial Interface Standard EIA 485 Serial Interface Standard NEC Article 250 Grounding NEC Article 300 Wiring Methods NEC Article 760 Fire Protective Signaling Systems Applicable Local and State Building Codes Requirements of the Local Authority Having Jurisdiction LAHJ NOTIFIER Documents NOTIFIER Device Compatibility Document 15378 FireWarden SLC Wiring Manual Document 52304 ONYX Series SLC...

Page 10: ...ower Limited Special application 2 5 amps max per circuit ELRs 4 7K 1 2W for Class B wiring Auxiliary Trouble Input CAUTION HIGH VOLTAGE AC Power Supervised Nonpower Limited 120 or 240 VAC 50 60 Hz 3 25 amps Battery 24 VDC supervised nonpower limited 18 AH maximum USB Port J20 for firmware updates local programming using a personal computer and FS Tools utility or a thumb drive To disable ground f...

Page 11: ...641 ANN BUS TB9 TB10 SLC Loop TB12 Battery Connector J15 nfw50xannperi wmf N ANN 80 LCD Text Annunciator Doc 52986 N ANN I O LED Driver Doc 151243 N ANN S PG Printer Driver Doc 151424 CHG 75 Charger Doc 51315 N ANN R LED LED Display Doc 53317 N ANN RLY 10 Form C Relay Card Doc 53318 4XTM Reverse Polarity Module J12 J13 IPOTS COM POTS and IP Communicator Doc LS10184 000GE E J6 CELL CAB N GSM Commun...

Page 12: ... special application power 3 0 amps total 24 VDC output circuit current in alarm condition Four programmable function keys for ease of maintenance Two programmable relay outputs and one fixed trouble relay Synchronization output for remote power supply applications special application Built in Programmer 80 character LCD display backlit Real time clock calendar with daylight savings time control H...

Page 13: ...ecial Application Auxiliary Power TB4 TB5 Two 2 Class B NAC circuits or two 2 Class A circuits Special Application filtered power Power limited circuitry NAC wiring requirements refer to NAC Wiring on page 139 Nominal operating voltage 24 VDC Current limit fuseless electronic power limited circuitry Maximum signaling current per circuit 2 5 amps special application 250 mA regulated for NACs see Fi...

Page 14: ...l turn off to conserve batteries Key Panel Mounted on the main circuit board the key panel includes a window for the LCD display and LED indicators as listed below The key panel which is visible with the cabinet door closed has 30 keys including a 16 key alpha numeric pad similar to a telephone keypad TB5 TB8 TB11 Figure 1 1 Current Availability powerdistes50 wmf Refer to the battery calculations ...

Page 15: ...itched telephone network It also allows remote programming or interrogation of the control panel using the FS Tools Upload Down load utility and a hard wired ethernet IP connection Any personal computer with Windows 7 or greater 32 or 64 bit and FS Tools software may serve as a Service Terminal This allows download of the entire program or upload of the entire program history file walktest data cu...

Page 16: ...stors are included with each module Refer to the specific module documentation for specific information Power Supervision Relay The UL listed End of Line power supervision relay is used to supervise the power to 4 wire smoke detectors and notification appliances EOL C R W Mounting Plate The EOL CR red and EOL CW white are single End of Line resistor plates An ELR which is supplied with each module...

Page 17: ...and up to 26 AH batteries can be housed in the BB 26 battery box Larger batteries and the charger can be housed in the NFS LBB battery box which can be mounted up to 20 feet away from the control panel Refer to the CHG 75 Manual for additional information CHG 120 Battery Charger The CHG 120 is capable of charging up to 120 AH lead acid batteries with the NFW 50X FACP The FACP battery charger must ...

Page 18: ...5 serial interface employing the ANN BUS communication format The devices are powered via two additional wires from either the host FACP or remote UL listed filtered regulated power supply The function buttons keyswitch and piezo sounder may be individually enabled and disabled through the FACP software Refer to ANN 80 100 Options on page 94 for a description of this feature and programming inform...

Page 19: ...ies with and ahead of all other equipment attached to the same telephone line If there are any questions concerning these instructions consult the telephone company or a quali fied installer about installing the RJ31X jack and alarm dialing equipment Refer to CELL MOD CELL CAB N on page 29 for an illustration of the proper installation of this equipment Important The DACT must not be used to dial ...

Page 20: ... on page 21 2 Install center top fastener in the wall with the screw head protruding 3 Place backbox over the top screw level and secure 4 Mark and drill the left and right upper and lower mounting holes Note Outer holes closest to sidewall are used for 16 O C stud mounting 5 Install remaining fasteners and tighten 6 When the location is dry and free of construction dust install the chassis circui...

Page 21: ...e 2 2 NFW 50X Cabinet Mounting 9050udencl wmf Semi Flush Mounting Do not recess box more than 3 875 into wall to avoid covering venting holes on top of box Hinge Slot for optional Dress Panel Hinge Slot for optional Dress Panel Semi flush mounting hole Mounting slots for optional Trim Ring ...

Page 22: ...ounting the Backbox An optional Trim Ring P N TR CE B is also available for semi flush mount installations 6 537 16 6cm 5 207 13 23cm 16 822 42 73 cm 19 26 48 92 cm Figure 2 3 NFW 50X Cabinet Dimensions nfw50cab wmf Height Depth Width Left Side Right Side Top Bottom ...

Page 23: ...the panel s susceptibility to transients generated by lightning and electrostatic discharge Apply AC power to the panel only after the system is completely installed and visually checked Note that AC power must be applied to the panel before installing the battery interconnect cable refer to the following section 2 2 2 Battery Power The batteries must be sealed lead acid type Before connecting the...

Page 24: ...e Device Compati bility Document for a listing of compatible notification appliances The NACs which are located on the main circuit board may be expanded via the FCPS Series field charger power supplies The following sections describe the configuration and wiring of Class B and Class A Notification Appliance Circuits on the NFW 50X main circuit board 24V PWR1 Figure 2 5 Special Application Power O...

Page 25: ...larized Horns Polarized Strobes Notification Appliance Circuit polarity shown in alarm state Dummy Load all unused circuit TB5 es50nacy wmf Polarized Strobes circuit number NAC 1 NAC 2 TB4 NAC2 NAC1 2 Class A Notification Appliance Circuits supervised and power limited Polarized Horns Polarized Horns Notification Appliance Circuit polarity shown in alarm state Polarized Bells Polarized Strobes Pol...

Page 26: ...0X to the sync input of the FCPS 24S6 8 Power Sup ply The 24 VDC signal from TB8 follows that is mimics the signal on NAC1 This allows the devices connected to the power supply to be synchronized with the devices connected to NAC1 on the FACP The Remote Synchronization Output is power limited and supervised refer to UL Power limited Wiring Requirements on page 27 and can be wired in Class B or Cla...

Page 27: ...t one installed closest to the backbox A typical wiring diagram for the NFW 50X is shown below RTN OUT COMMUNICATOR DISPLAY 24V RTN OUT BATTERY N L2 EARTH H L1 USB A C NO NC C NO NC C NC NO SUPV TRBL ALRM ANN LC SLC RMT SYNC ANN BUS PRI ANN BUS SEC NAC2 NAC1 Figure 2 10 Typical UL Power limited Wiring Requirements Power limited Circuits Class 2 Power limited Circuits Class 2 AC Power Grounding Stu...

Page 28: ...ion necessary SW3 2 position dip switch Factory Settings Do not change unless instructed to do so by Honeywell Figure 2 11 Communicator Installation Customer Premises Equipment and Wiring Telephone Line FACP with IPOTS COM mounted interally Network Service Provider s Facilities Network Demarcation Point RJ31X Jack Unused RJ 11 Jack Unused RJ 11 Jack Telephone Telephone Telephone Answering System F...

Page 29: ...onitoring service Local Energy Municipal Box Service NFPA 72 Auxiliary Fire Alarm Systems Supervisory Current 5 0 mA Trip Current 350 mA subtracted from notification appliance power Coil Voltage 3 65 VDC Maximum Coil Resistance 14 6 ohms Maximum allowable wire resistance between panel and trip coil 3 ohms Municipal Box wiring can leave the building Remote Station Service NFPA 72 Remote Station Fir...

Page 30: ...med for the factory default settings Alarm Relay 1 Trouble Relay 2 and Supervisory Relay 3 8 When the installation has been complete enable the 4XTM module by sliding the disconnect switch to the left 9 Test system for proper operation Figure 2 15 4XTM Transmitter Module Connect to FACP J12 J13 Disconnect Switch shown in disconnect position TBL Jumper Remote Alarm power limited Remote Trouble powe...

Page 31: ...f 4XTM FACP main circuit board es2004xtmf wmf Jumper JS3 NOTE When a 4XTM is installed enable supervision in panel programming Jumper JS3 on the FACP main circuit board can be used to configure the FACP supervisory relay for operation with the 4XTM module Relay 3 at TB3 must be programmed as a supervisory relay Jumpering pins 2 3 on JS3 will allow the 4XTM to generate a trouble if the supervisory ...

Page 32: ...llel Printer Interface Module The total worst case current is calculated as follows Wiring Configuration Figure 2 17 illustrates the wiring between the FACP s Primary ANN BUS and ANN BUS devices Maximum Resistance Ohms 2 0 Volts Total Worst Case Current Draw amps Maximum Wire Length feet Maximum Resistance Ohms x 500 6 000 feet maximum Rpu where Rpu Ohms per 1 000 feet for various Wire Gauges see ...

Page 33: ...igure 2 19 illustrates the powering of ANN BUS devices from an auxiliary power supply such as the FCPS 24S6 8 when the total ANN BUS power requirements exceed the panel s DC Power Output capability TB1 4 3 2 1 Figure 2 18 Secondary ANN BUS wiring to ANN BUS Device ANN BUS Device NFW 50X ANN BUS and power wiring are supervised and power limited 24 VDC nonresettable Secondary ANN BUS es50toann802 wm...

Page 34: ...cation Installation Ensure that all power AC and DC has been removed from the FACP before installing the annunciator Opening Closing Annunciator The following procedure details the steps used to open the annunciator in order to access the terminal block and DIP switches refer to figure below 1 Turn the key switch to the ON Unlocked position by turning the key counter clockwise 2 Push in the snap l...

Page 35: ... can be used as a guide to wire the annunciator Make certain all power has been removed from the FACP prior to annunciator installation 1 Route wires from hole in backplate through wiring channel and then to N ANN 80 terminal block TB1 2 Remove appropriate amount of wire insulation 3 Connect the wiring from the FACP ANN BUS to annunciator TB1 terminals 3 A 4 B Make certain to connect A to A and B ...

Page 36: ... seconds Note that the FACP will provide no indication of an N ANN 80 trouble To clear the N ANN 80 trouble condition enable the ANN BUS and program the address corresponding to the address set on the N ANN 80 at the FACP N ANN 100 Remote Fire Annunciator Specifications Operating Voltage 24 VDC Current Standby 20 mA Alarm 25 mA Ambient Temperature 32 F to 120 F 0 C to 49 C Max Wiring Distance from...

Page 37: ...igure feature allows the programmer to quickly bring all installed ANN BUS modules online refer to Auto Configure on page 93 5 Connect a printer to the N ANN S PG Parallel or Serial connectors refer to Figure 2 21 Only one printer can be connected Specifications Operating Voltage 24 VDC Current Alarm and Standby 45 mA Ambient Temperature 32 F to 120 F 0 C to 49 C Max Wiring Distance from FACP 6 00...

Page 38: ...25 cable One end of the cable will plug into the DB 25 connector on the PRN printer and the other end plugs into the parallel connector on the N ANN S PG module Note that the 9 pin DB 9 port on the N ANN S PG is used to connect a serial printer The 25 pin port is used for a Centronics parallel printer cable Connect either a serial or parallel printer but not both at the same time Setting Printer O...

Page 39: ...necting LEDs and the DIP switch for selecting the ANN BUS ID number Specifications Max ANN BUS Voltage 24 VDC Max Current Alarm 200 mA Standby 35 mA Each LED 10 mA Operating Temperature 32 F to 120 F 0 C to 49 C For indoor use in a dry location only 1 10 11 20 21 30 31 40 LED Out LED Power not used LED Out LED Power not used LED Out LED Power not used LED Out LED Power not used ANN BUS ID Address ...

Page 40: ...r Internal resistors are sized so that there is approximately 10 mA of current for each LED No series resis tors are required LED outputs can be mapped to output circuits Refer to the programming section titled ANN I O Options on page 87 of this manual The LEDs are wired as illustrated in Figure 2 24 Note that the illustration depicts only connectors P1 and P2 Wiring is identical for P3 LEDs 21 30...

Page 41: ...ioleds2 wmf LED1 LED2 LED3 LED4 LED5 LED6 LED7 LED8 LED9 LED10 LED Power no connection Pin 1 2 3 4 5 6 7 8 9 10 11 12 LED11 LED12 LED13 LED14 LED15 LED16 LED17 LED18 LED19 LED20 LED Power no connection P1 P2 Cathode LEDs Anode Cathode LEDs Anode Pin 1 2 3 4 5 6 7 8 9 10 11 12 Figure 2 25 N ANN LEDs shown in possible stacked configuration ann ledstacked wmf ...

Page 42: ...the N ANN LED Installation Docu ment 53317 for more information N ANN LED Board Layout and Connection to FACP Figure 2 27 illustrates the N ANN LED board showing locations of screw terminals for connection to the FACP and the DIP switches for selecting the ANN BUS ID number Figure 2 26 Exploded View of N ANN LED ann led wmf TB1 J1 SW1 JP2 ANN BUS 1 2 3 4 5 6 7 8 Figure 2 27 N ANN LED Board Layout ...

Page 43: ... inside the ROME Series enclosure Refer to the N ANN RLY Installation Document 53318 for instructions on chassis mounting or to the ROME Series Installation Document 53530 for mounting in the separate backbox mounting holes mounting hooks through mounting slots grounding wire N ANN RLY ANN MBRLY mounting bracket mounting holes mounting holes FACP Backbox Installation using ANN MBRLY mounting brack...

Page 44: ...NN BUS Setup on page 86 for programming information Printer Configuration Refer to the documentation supplied with the printer for pertinent information about printer setup Set the printer s options as listed in the following table TB1 J1 SW1 JP2 ANN BUS 1 2 3 4 5 6 7 8 TB6 TB3 TB5 TB4 TB2 Figure 2 29 N ANN RLY Board Layout and Connection to FACP N ANN RLY Primary ANN BUS 24 VDC 24 VDC ANN BUS and...

Page 45: ...mation out to next SLC device Figure 2 30 FWSG SLC Connection es50toWG wmf NFW 50X FWSG mounting plate NOTE The FWSG as part of the wireless network has been tested for compliance with the Federal Communications Commission FCC requirements of the United States Government It has not been evaluated for use outside the USA Use of this system outside the USA is subject to local laws and rules to which...

Page 46: ...l Delay Timer Y Refer to AC Loss Delay on page 72 0 23 hours 1 3 hours Remote Download Y Refer to FS Tools Upload Download on page 119 Remote Download Proprietary No Remote Download Proprietary Yes Remote Download Proprietary Yes for Proprietary system intended to protect only contiguous properties Control Module Delay N Refer to Control Module Delay on page 72 Control Module Delay 0 factory defau...

Page 47: ...ic custom programs using a Windows based computer and the FACP USB connection For programs requiring a large amount of data entry this method may be preferred The FS Tools programming utility can be downloaded from www notifier com for this purpose The System Normal screen will be displayed in a programmed system with no active alarms troubles or supervisories as illustrated below Read Status mode...

Page 48: ...ter completing the wiring of addressable devices to the SLC apply power to the control panel If the addressable devices have not yet been programmed into the FACP their LEDs will not flash and the following trouble message will be displayed 3 4 Programming Screens Description The options available when the Enter key is pressed are Read Status Programming The Read Status and Programming options hav...

Page 49: ...mpts the control panel to poll all devices installed on the SLC loop The primary purpose of autoprogramming is to allow the installer a fast and easy way to bring the system on line as quickly as possible The first time the system is powered up it should be autoprogrammed If the system is already programmed and Autoprogram is initiated the system will only add default values for newly installed de...

Page 50: ...play the following screen which allows the programmer to add a new detector address to programming A flashing cursor will appear in the position of the first asterisk to the left The programmer keys in the three digit detector address such as 005 The screen will then ask whether the detector being added is wireless Select 1 for wired detector or 2 for wireless detector When the choice is selected ...

Page 51: ...g will be displayed If the selected address has been added to programming device summary screens will be displayed These screens allow the programmer to view all device settings at a single glance Pressing the left or right arrow keys will allow the programmer to rapidly view the devices at the previous or next address if installed If a detector such as a photoelectric detector with the selected a...

Page 52: ...he Trouble LED and Disable LED Type To select the type of detector being programmed press the 2 key while viewing the Edit Detector Screen 2 This will cause the control panel to display the following Detector Type Screens Pressing the down arrow key will display additional detector types as indicated in the following table Detector Type Action When Activated Smoke Photo Fire Alarm User Defined 1 s...

Page 53: ... assigning the same zone to it in this example Z001 Program an output such as a control module for PAS activation by assigning zone Z047 to it This control module may be connected to a signaling device used to indicate a PAS condition do not use a Notification Appliance Circuit for this purpose Enable zones Z001 and Special Purpose Zone PAS 047 and set the PAS delay timer to some value With the pr...

Page 54: ...ired the display will read Wireless No Fore more information on the SWIFT wireless network refer to the SWIFT manual LS10036 000NF E Sounder Base The Sounder Base selection allows the programmer to enter different values if the selected detector is mounted in an addressable sounder base Pressing 2 while viewing Edit Detector Screen 5 will display the following If the selected detector has been ins...

Page 55: ...r corresponding to the adjective that is to be used as a descriptor for the location of the detector currently being programmed When an adjective has been selected it will appear at the top of the display as indicated by the asterisks Pressing 2 while viewing the Noun Adjective Screen will cause the following screen s to be displayed Note that the keyboard down arrow key must be pressed to see all...

Page 56: ...ro key is then pressed a second time with no intervening key actions the entire field is replaced with the field entered for the previous device programmed and the cursor moves to the last character of the field Recall function The Recalled Adjective or Noun field may now be changed letter by letter If the zero key is pressed again with no other intervening key actions and the last character in th...

Page 57: ...ng the panel keypad key in the module address such as 005 When the last digit is keyed in the following confirmation that the module has been deleted will be displayed Edit Module Screen for Monitor Module The programmer can change a modules existing or factory default programming by pressing 3 in the Modules Screen The following screen will be displayed A flashing cursor will appear in the positi...

Page 58: ...dress will be displayed as illustrated in the following Enable Disable Module To Enable or Disable the monitor module press the 1 key while viewing the Edit Module Screen 2 Each press of the key will toggle the screen between Enabled Yes and Enabled No If Enabled No is selected the module will not be polled by the control panel preventing the module from reporting alarms and troubles to the panel ...

Page 59: ... Tornado Alert 1 General Purpose Signaling latching User Defined 9 same as previous Tornado Alert Phone Active Phone LCD display only User Defined 10 same as previous Phone Tamper Supervisory nonlatching tracking User Defined 11 same as previous Tamper Supervisory Supervisory latching User Defined 12 same as previous Supervisory Supervisory AR 2 2 For entries ending in AR AR refers to AutoResettab...

Page 60: ... digit number corresponding to the zone that is to be assigned to this device The cursor moves to the next Z designation Continue entering zone assignments or the remaining zones can be left blank or programmed as general alarm zones Z00 When all desired changes have been made press the Enter key to store the zone assignments The display will return to the Edit Monitor Screen 4 Noun Adjective The ...

Page 61: ...tion at the bottom of the screen Recall Increment Function In addition the user may use the Recall Increment function at any time when the cursor is on the first letter of the Adjective or Noun field as follows If the zero key is pressed a 0 is placed in the first letter position If the zero key is then pressed a second time with no intervening key actions the entire Adjective field is replaced wi...

Page 62: ... Disable the control module press the 1 key while viewing the Edit Control Screen 2 Each press of the key will toggle the screen between Enabled Yes and Enabled No If Enabled No is selected the module will not be polled by the control panel preventing the module from activating its output devices The control panel will indicate a system trouble condition and the Disable LED will turn on if any dev...

Page 63: ...zone A flashing cursor will appear on the first 0 to the left Enter the three digit number corresponding to the zone that is to be assigned to this device The cursor moves to the next Z designation Continue entering zone assignments or the remaining zones can be left blank or programmed as general alarm zones Z000 When all desired changes have been made press the Enter key to store the zone assign...

Page 64: ...y to move the cursor one position to the right and repeat the process to enter the next character To enter a space press the QZ key four times until a blank appears in the desired position When all characters have been entered press the Enter key to store the information The display will return to the Edit Control Screen 4 dis playing the new information at the bottom of the screen Recall Incremen...

Page 65: ...ewing Programming Screen 2 will access the Zone Setup screens as illustrated below Enable Pressing 1 for Enable while viewing Zone Setup Screen 1 will display the following screen This screens allows the programmer to enable zones one at a time A flashing cursor appears next to the Z prompting the programmer to enter a three digit zone number 001 049 When the third digit is entered the zone will b...

Page 66: ... on page 74 for a description of this feature Pressing 1 while viewing the Special Purpose Zone Screen 2 will cause the display to change to Local Alm 46 On Each press of the 1 key will cause the display to toggle between Local Alm 46 On and Local Alm 46 Off When Zone 46 is programmed On a Local Alarm activation of any smoke detector will cause Zone 046 to activate By assigning Zone 046 to a contr...

Page 67: ...zone type to the selected zone Any signaling devices programmed to the same zone can be silenced by pressing the Alarm Silence key or by using the auto silence feature To program a waterflow circuit as nonsilenceable refer to System Setup on page 68 Zones Available Pressing 2 while viewing Zone Setup Screen 3 will display the following screen The display will show all of the zones that are still a...

Page 68: ...le Relays This option allows programming of two onboard relays for activation by various control panel events such as alarm trouble supervisory etc Canadian Option This option allows the programming of certain options to Canadian specifications Waterflow Silenceable This option provides the ability to silence any output circuit activated by a monitor module programmed as a waterflow type Auxiliary...

Page 69: ...zation TB8 on the FACP s main circuit board can also be disabled through pro gramming of a function key To disable remote synchronization press the 3 key while viewing the Function Keys Screen 2 Each press of the key will toggle the screen between Rem Sync Disb Yes and Rem Sync Disb No Banner The top line of the display which appears when the control panel is in normal mode can be changed by using...

Page 70: ...LR key to delete the entire entry and beginning again Date To change the date press 2 while viewing the Time Date Screen The following screen will be displayed A flashing cursor is located toward the top left of the display Below the cursor is the current date To change the date enter the two digit month followed by the two digit day and then the two digit year 17 for 2017 18 for 2018 etc The curs...

Page 71: ...isplay will return to the Delay Screen which will indicate the new delay time Pre signal Delay The factory default setting for Pre signal delay is 000 for no delay To select a Pre signal delay of 001 to 180 seconds for all devices pro grammed for Pre signal press 2 while viewing Timer Screen 1 The following screen will be displayed A flashing cursor is positioned in the lower left corner of the di...

Page 72: ...e options for the NACs on the control panel main circuit board can be configured by pressing 2 while viewing System Setup Screen 2 The following screens will be displayed The Notification Appliance Circuits can be configured independently by pressing 1 for NAC 1 or 2 for NAC 2 The following screens will be displayed for each selection Enabled Pressing 1 while viewing NAC Screen 1 will cause the di...

Page 73: ...wing NAC Screen 2 The following screens will be displayed To disable the Auto Silence feature press 1 for No while viewing Auto Silence Screen 1 To enable the Auto Silence feature press the number corresponding to the time delay which will elapse before Auto Silence activates This information will be stored in memory and the display will return to NAC Screen 2 Coding only for NACs not programmed a...

Page 74: ...activated and the countdown timer has stopped counting due to the Acknowledge switch being pressed the countdown timer will restart and the NACs will respond as outlined in step 2 NACs that are already in 2nd stage activation will not be affected 8 Any control modules assigned to special Zone 049 will be activated either by direct mapping of an input device programmed to Zone 049 or if the timer c...

Page 75: ...m Setup Screen 3 will configure the FACP to comply with Canadian requirements The display will change to Canadian Opt On Each press of the 1 key will cause the display to toggle between Canadian Opt On and Canadian Opt Off Refer to the table on page 46 for permissible settings Important For Canadian Applications this option must be set to ON prior to any other panel programming The Canadian Option...

Page 76: ...le Rem 24 which enables this feature for resound at either 4 or 24 hours respec tively Each press of the 2 key will cause the display to toggle between Trouble Rem 4 or Trouble Rem 24 Refer to the table on page 46 for permissible settings Language The language option is used to change the text on the panel display to either English or French Pressing the 3 key will cause the display to offer a cho...

Page 77: ...rn to the History Screen 3 6 7 Communicator The communicator settings allow the user to configure the settings for the pre installed IPOTS COM and CELL MOD CELL CAB N if installed in the system Pressing 2 while viewing the Programming Screen 3 will cause the following Communicator options to be displayed Communicator Installed The pre installed communicator provides communication to a central stat...

Page 78: ...etting is Phone Line X super vised Supervision must be set to Yes if the selected transmission path is POTS Pressing 1 for Supervision while viewing the POTS Line X Screen 2 will change the screen to read Supervision No Each press of the 1 key will toggle the option between Supervise Yes and No Refer to the table on page 46 for permissible settings Gains The Gains value is the telephone s transmit...

Page 79: ...n the IP Set tings screen will display the following Enter the 4 digit PIN provided by AlarmNet and press Enter The display will indicate that it is sending the PIN to AlarmNet for verifica tion Ethernet Fault The Ethernet Fault Time is the duration of the communication loss between the FACP and the ethernet infrastructure Pressing 1 on the IP Settings Screen 2 will display the following Select th...

Page 80: ...ommunicator will be contacting A maximum of 20 characters can be entered with valid entries being 0 9 and A C where A B and C 2 seconds pause A flashing cursor will appear in the lower left corner of the screen Enter the first digit then press the right arrow key to move the cursor to the right one position Enter the second digit and repeat the process until all digits are entered Press the Enter ...

Page 81: ...onnection select 2 for Ethernet from the Comm Path Screen The following screens will display Enable To enable the Ethernet connection press 1 while viewing the Ethernet Options Screen 1 to change the display to Enabled Yes Each press of the 1 key will cause the display to toggle between Enabled Yes and Enabled No Central Station Account Press 2 on Ethernet Options Screen 1 to display the following...

Page 82: ... 2013 Dual Path Refer to the table on page 46 for permissible settings The Supervision Interval is the time from the check in at AlarmNet to the FACP Select Dual Path when Ethernet and Cellular communications will be used Select Sole Path when only Ethernet or Cellular is used NFPA 2010 Dual Path Supervision Interval 24 Hours NFPA 2010 Sole Path Supervision Interval 5 min NFPA 2013 Dual Path Super...

Page 83: ...e tables on the following pages list all of the Events and their default Event Codes for the various Communication Formats The information shown in Table 3 3 is automatically programmed for the Central Station phone number Event Codes when the Ademco Contact ID or SIA Format is selected Enter 0s for an Event Code Setting to disable the report Disabled reports will not get called to the Central Sta...

Page 84: ...EF 5 111 Zone Point FA FH HEAT CONVENTIONAL 114 Zone Point KA KH MON USER DEF 6 114 Zone Point KA KH MEDIC ALERT 100 Zone Point MA MH MON USER DEF 7 100 Zone Point MA MH HAZARD ALERT 150 Zone Point PA PH MON USER DEF 8 150 Zone Point PA PH TORNADO ALRT 150 Zone Point PA PH MON USER DEF 9 150 Zone Point PA PH TAMPER 144 Zone Point TA TH MON USER DEF 11 144 Zone Point TA TH MON SUPERVISORY 200 Zone ...

Page 85: ... YA YR NAC 2 FAULT 322 002 002 YA YR 24 VDC FAULT 300 000 000 YP YQ ACS FAULT 333 000 000 EM EN LCD 80F FAULT 330 000 000 EM EN PRI ANN BUS FAULT 333 000 000 ET ER SEC ANN BUS FAULT 333 000 000 ET ER PRI ANN CLASS A 333 000 000 ET ER REMOTE SYNC DIS 520 000 000 ET ER NAC 1 DISABLE 521 001 001 ET ER NAC 2 DISABLE 522 002 002 ET ER MEMORY FAULT 304 000 000 CHARGER FAULT 300 000 000 YP YQ OPTION CARD...

Page 86: ...1 8 To select one or more addresses for the installed module s press the number key corresponding to the module address in each screen The following screen will be displayed for each address Pressing 1 for Type will display the following screens Press the number corresponding to the module device type that is installed with the selected address If ANN I O ANN LED or ANN RLY is the selected module ...

Page 87: ...s information or Zone information Each press of the 1 key will toggle the display between Zone and Point Pressing 1 while viewing the ANN I O Address Screen 3 will select the Point range to be annunciated refer to the tables in ANN I O Zone Option on page 88 and ANN I O Point Option on page 89 If Point has been selected each press of the 2 key for Range will change the points to be annunciated wit...

Page 88: ...e 032 4 Trouble Zone 033 5 Alarm Silenced Zone 034 6 Earth Fault Zone 035 7 Battery Fault Zone 036 8 Charger Fault Zone 037 9 NAC Fault Zone 038 10 Disabled Zone 039 11 Zone 000 Zone 040 12 Zone 001 Zone 041 13 Zone 002 Zone 042 14 Zone 003 Zone 043 15 Zone 004 Zone 044 16 Zone 005 Zone 045 17 Zone 006 Zone 046 18 Zone 007 Zone 047 19 Zone 008 Zone 048 20 Zone 009 Zone 049 21 Zone 010 Not Used 22 ...

Page 89: ... 032 Active Alarm 13 Point 003 Active Alarm Point 033 Active Alarm 14 Point 004 Active Alarm Point 034 Active Alarm 15 Point 005 Active Alarm Point 035 Active Alarm 16 Point 006 Active Alarm Point 036 Active Alarm 17 Point 007 Active Alarm Point 037 Active Alarm 18 Point 008 Active Alarm Point 038 Active Alarm 19 Point 009 Active Alarm Point 039 Active Alarm 20 Point 010 Active Alarm Point 040 Act...

Page 90: ... 021 030 031 040 or 041 050 Five N ANN LED modules are required to annunciate all points in this configuration N ANN RLED Zone Option Alarm Only If Zone is selected as the module option and the module is programmed to annunciate alarms only the first ten LEDs on the N ANN RLED module will display the system status information The remaining 30 LEDs on the first module and the last 30 LEDs on the se...

Page 91: ...005 Active Alarm Zone 006 Active Alarm Zone 007 Active Alarm Zone 008 Active Alarm Zone 009 Active Alarm Zone 005 Trouble Zone 006 Trouble Zone 007 Trouble Zone 008 Trouble Zone 009 Trouble Zone 005 Supervisory Zone 006 Supervisory Zone 007 Supervisory Zone 008 Supervisory Zone 009 Supervisory Table 3 6 N ANN LED Module 1 Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not ...

Page 92: ... Point 050 Active Alarm Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used First N ANN LED Module Point Range 001 010 Alarm Silenced NAC 1 Fault NAC 2 Fault Not Used Not Used Earth Fault Battery Fault Charger Fault Disabled Maintenance Point 001 Active Alarm Point 002 Active Alarm Point 003 Active Alarm Point 004 Active Alarm Point 005 Active Alarm Point 001 ...

Page 93: ...es and automatically program the device type and address into the system For the Auto Configure to work the selected ANN BUS must be enabled the annunciators must be connected powered and a unique address must be set on each annunciator Pressing 3 while viewing ANN BUS XXX Screen 1 will begin the Auto Configure process and cause the following screen to be displayed Class A This option applies to t...

Page 94: ...0 or 2 0 Stop Bits ANN LED Options This option allows the programmer to configure the optional N ANN LED annunciator Pressing 2 while viewing the ANN BUS screen will display the following screens The Piezo Enable option allows the programmer to select whether the piezo sounder on any installed N ANN LED module will ever sound Pressing 1 while viewing the ANN LED Options Screen causes the display t...

Page 95: ...t ton never functions The Drill Button Enable DRL BTN ENABLE option allows the programmer to select whether the Drill button on any installed N ANN 80 or N ANN 100 annunciator will function normally or always be ignored Pressing 3 while viewing the ANN 80 100 Options Screen 2 causes the display to toggle between Drl Btn Enable Yes Drill button functions normally and Drl Btn Enable No Drill button ...

Page 96: ...ve been programmed to any of these zones Use the up and down arrow keys to view all the NAC zones without input assignments for NAC 1 and NAC 2 Pressing 2 while viewing the Program Check Screen 1 will display a screen similar to the following The Zone No Input screen allows the programmer to view the zones which have not been programmed to at least one input device not including general alarm Zone...

Page 97: ...wing example for a detector A flashing cursor will appear in the bottom left corner of the display prompting for the three digit device address When the third digit is enter 001 for example a screen will appear which will allow enabling or disabling of the selected point as illustrated in the following example Pressing 1 repeatedly will cause the display to toggle between Enabled Yes and Enabled N...

Page 98: ...ilar to the following to be displayed The example above indicates that NAC 1 has been programmed to Zones 005 010 012 015 and 017 but no input devices have been programmed to any of these zones Use the up and down arrow keys to view all the NAC zones without input assignments for both NAC 1 and NAC 2 Pressing 2 while viewing the Program Check screen will display a screen similar to the following T...

Page 99: ...will be displayed which allows the viewing of all untested system points and their status relating to the current walktest session The up and down arrow keys will allow viewing of all untested points If a point is tested while it is being displayed the screen will update and display the next untested point The first line indicates the total number of untested points The second line displays inform...

Page 100: ... the right after each entry When the fourth digit of the year has been entered the display will return to the Time and Date Screen which will show the new date The clock can be configured to display 12 hour AM PM or 24 hour military time Pressing 3 while viewing the Time Date screen will cause the display to toggle between 12HR and 24HR Select 12HR for 12 hour display or 24HR for 24 hour display T...

Page 101: ...an output device connected to the control module can be used to indicate a PAS condition in the control panel Do not assign Zone 047 to a Notification Appliance Circuit when using this zone to indicate a PAS condition Pressing 2 will cause the display to change to Pre signal 48 On Each press of the 2 key will cause the display to toggle between Pre sig nal 48 On and Pre signal 48 Off When Zone 048...

Page 102: ... RESET IN SYSTEM message to be displayed on the LCD and sends the same message to the printer and history file It also per forms a lamp test by turning on all LEDs except the Ground LED piezo sounder and LCD display segments after the Reset key is released Any alarm or trouble that exists after a reset will resound the system 4 1 5 Function Keys F1 F4 The four function keys are user programmable T...

Page 103: ...n of a trouble will cause the following The piezo to pulse 1 second On and 1 second Off The system Trouble LED to flash one second On and one second Off The trouble relay to activate TROUBL with device type noun adjective address and trouble description will appear on the LCD display The same message along with the time and date is sent to the optional printer and the history buffer Communicate th...

Page 104: ...r and history file If all troubles clear and there are no supervisory or fire conditions active in the system the system returns to normal mode operation and the System Normal message is shown on the LCD display and sent to the history and printer files The auto restore feature will restore cleared troubles even if the troubles were never acknowledged Note that pressing the Alarm Silence key when ...

Page 105: ...a CO alarm condition Device type identifier in this example CAR MONOXIDE indicates a CO detector Second line in display ADJ refers to the user programmed adjective descriptor from library list resident in the control panel or custom entry via PC NOUN refers to the user programmed noun descriptor from library list resident in the control panel or custom entry via PC Third line in display Z002 indic...

Page 106: ...o software zones 4 9 Hazard Tornado Condition Operation Hazard Tornado operation is intended for Manual activation Hazard Tornado Condition operation will initiate the following events The piezo sounder pulses 1 4 second On 1 4 second Off The LCD displays a hazard message along with the device name type address adjective noun associated zones and time date Communicate the hazard condition to the C...

Page 107: ...tector is monitored by the control panel for its maintenance status If a detector is near but below the allowed alarm limit a maintenance alert message will automatically be displayed signaling that the detector is in need of servicing Automatic Test Operation An automatic test of an addressable detector is performed each minute resulting in a complete SLC loop test in approximately 5 hours if the...

Page 108: ... and control modules of associated zones will be inhibited from activating for a user programmed time delay of up to three minutes second alarm occurring anytime during the time delay will cause immediate activation of all associated outputs Presignal does not affect monitor modules programmed as waterflow supervisory process monitoring or remote switches Presignal operation requires the approval ...

Page 109: ...s automatically reset There will be no alarm indication at the FACP during the Retard period A confirmation period of 60 seconds follows during which a subsequent alarm from the same detector will cause the panel to immediately activate the appropriate outputs and indicate the alarm condition at the FACP If a different detector alarms any time during the first detector s verification period the pa...

Page 110: ...change opera tions The alarm relay is not activated 4 23 Read Status Read Status functions do not require a password The control panel will continue to provide fire protection while in Read Status mode This mode can be entered while the control panel is in alarm or trouble If a new alarm or trouble occurs during these functions the Read Status is exited to prevent confusion Read Status Entry When ...

Page 111: ...r detectors and monitor modules Zone Assignments five maximum Chamber Value Adjective Noun descriptor Silenceable Yes No for control modules Wireless Yes No for detectors only Sounder Base Yes No for detectors only Sounder Base Values and Zone Assignments for detectors only 4 23 2 Zones Pressing 2 while viewing Read Status Screen 1 will cause the following screens to be displayed From the precedin...

Page 112: ...ays Pressing 1 while viewing Read Status Screen 3 will display the following screen The operator can view the programmed option for each relay by pressing the corresponding number key 4 23 7 Program Check Pressing 2 while viewing Read Status Screen 3 will cause a screen similar to the following to be displayed Pressing 1 while viewing Program Check screen 1 will display a screen which will indicat...

Page 113: ...r ANN 80 100 Options while viewing ANN BUS Screen 2 will display the options selected for the installed N ANN 80 or N ANN 100 annunciators 4 23 10 Communicator Pressing 2 while viewing Read Status Screen 4 will display the following screens The Communicator Screen 1 indicates if an IPOTS COM has been installed Yes or No Pressing 2 for POTS Settings while viewing Communicator Screen 1 will display ...

Page 114: ...Status Screen 5 The following screens will be displayed Pressing 1 while viewing Print Screen 1 allows the user to print the History file which will detail all of the system activities since the file was last cleared from memory Pressing 2 while viewing Print Screen 1 allows the user to print the Walktest log which will detail all of the system activations during walktest since the log was last cl...

Page 115: ... to automatically perform the periodic sensitivity measurements required by NFPA Standard 72 The FACP software also provides filters to remove transient noise signals usually caused by electrical interference Maintenance Alert The software determines when the drift compensation for a detector reaches an unacceptable level that can compromise detector perfor mance When a detector reaches an unaccep...

Page 116: ...en 6 indicates whether the onboard battery charger is enabled or disabled 4 23 14 4XTM Supervision Read Status Screen 6 indicates whether 4XTMF Supervision is enabled or disabled 4 23 15 Remote Sync Read Status Screen 6 indicates whether remote synchronization is enabled or disabled READ STATUS 1 FUTURE USE 2 PRINT 3 TIME DATE Read Status Screen 5 DAYLIGHT SAVINGS ENABLED YES START MONTH MAR START...

Page 117: ... Two phone numbers must be programmed the primary Central Station phone number and the secondary Central Station phone number All system reports will be transmitted to the primary Central Station phone number Reports will automatically be sent to the secondary Central Station phone number if attempts to transmits to the primary Central Station phone number are unsuccessful If 10 total attempts to ...

Page 118: ...1 03 7 With software V1 86 8 With software V1 72 9 With DSP4016 and V1 6 Line Card 10 With software V3 9 IMPORTANT It is the installer s responsibility to ensure that the Digital Alarm Communicator Transmitter is compatible with the Central Station Receiver utilized by the monitoring service prior to installation The Compatibility Table provides a list of compatible receivers and associated softwa...

Page 119: ...om the main menu screen as shown below Pressing 3 for FS Tools Download while viewing the main menu will cause the following screen to be displayed The FS Tools Download password default 22222222 must be entered to access the FS Tools Download feature Note that the default password can be changed using the Password Change option refer to Password Change on page 95 Entering the correct password wil...

Page 120: ...f the secret code is pro hibited at the control panel Prior to allowing an upload or download of data the control panel will verify the secret code transmitted by the Service Terminal Time out at Control Panel Upon answering an incoming call on the primary Central Station phone line the control panel will listen for a modem connection signal If this signal is not received within 50 seconds the con...

Page 121: ...oard The USB Download option can be selected from the main menu screen as shown below Pressing 4 for USB Up Download while viewing the main menu will cause the following screen to be displayed The USB Upload Download password default 22222222 must be entered to access the USB Upload Download feature Note that the default password can be changed using the Password Change option refer to Password Ch...

Page 122: ...able any further downloads to a flash drive Also following 30 minutes of inactivity including up downloading the Accept Download screen will time out causing the display to return to the System Normal screen Important The program database created by the FS Tools programming utility will be called FS_50 cfg on the USB flash drive Before loading the new database into the fire panel the existing data...

Page 123: ...ollowing screen to be displayed Before upgrading any software the panel will give the option to save current programming to a flash drive Press 1 for No to bypass pro gramming backup or press 2 for Yes to save a copy of the current programming to the flash drive The USB thumb drive must be in FAT32 file system format This is typically the default format An error message will display if there is no...

Page 124: ...124 NFW 50X Manual P N LS10129 001NF E C 7 25 2018 Notes ...

Page 125: ...rimary AC power is applied The continuous sys tem current load is highest during a fire alarm condition To calculate the fire alarm load on the internal power supply use Calculation Column 1 in Table 9 3 on page 126 The secondary power source batteries must be able to power the system under both standby and fire alarm conditions upon loss of pri mary AC power To calculate the fire alarm load on th...

Page 126: ...0 00030 NH 100 NH 200 FST 851 FST 951 X 0 00030 NH 100R NH 200R FST 851R FST 951R X 0 00030 NH 100H NH 200H FST 851H FST 951H X 0 00030 ND 100 FSD 751PL X 0 00030 ND 100R FSD 751RPL X 0 00030 B501BH B501BHT5 X 0 001 B224RB X 0 00050 B224BI X 0 00045 NMM 100 FMM 1 X 0 00040 XP10 M X 0 00350 NDM 100 FDM 1 X 0 00075 NMM 100P FMM 101 X 0 000375 NZM 100 FZM 1 X 0 00027 NZM 100 6 XP6 MA X 0 00200 NOT BG...

Page 127: ... in the 7 AH to 18 AH range The control panel cabinet is capable of housing batteries up to 18 AH Batteries larger than 18 AH require a UL listed external battery charger and cabinet such as the BB 26 NFS LBB or other UL listed external battery cabinet 7 If using Gentex brand NACs the max number of devices for each NAC output is 35 The UL Max current rating published in their data sheets must be u...

Page 128: ... can be assigned to a maximum of five software zones Each software zone however may have from 1 to 50 addressable input and output devices assigned to it Monitor modules control modules and detectors comprise a group of 50 addresses each device having a unique address from 1 to 50 Be careful not to duplicate addresses between devices Refer to the following page for an example of zoning In the exam...

Page 129: ...hich are shown graphically above are also presented in Table A 1 on page 130 Input Devices Zones Output Devices ZONE 01 ZONE 02 ZONE 03 smoke 01 smoke 02 monitor 03 monitor 04 monitor 05 smoke 15 smoke 16 smoke 22 smoke 24 smoke 25 monitor 30 control 10 control 07 control 13 control 11 control 20 control 21 control 31 control 32 control 06 ...

Page 130: ... control module 1 07 control module 1 08 09 10 control module 1 11 control module 1 2 3 12 13 control module 1 14 15 smoke detector 2 2ND FLOOR 16 smoke detector 2 ROOM 210 17 18 19 20 control module 2 21 control module 2 22 smoke detector 3 3RD FLOOR 23 24 smoke detector 3 MEZZANINE 25 smoke detector 3 MECH ROOM 26 27 28 29 30 monitor module 3 31 control module 3 32 control module 3 33 34 35 36 3...

Page 131: ...are Zones ADDRESSABLE DEVICE ZONE ASSIGNMENTS Address Device Type Zone Number ADJ NOUN 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 Table A 2 Blank Programming Sheet ...

Page 132: ...relations ADDRESSABLE DEVICE ZONE ASSIGNMENTS Address Device Type Zone Number ADJ NOUN 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 Table A 3 Blank Programming Sheet ...

Page 133: ...Secondary Comm Format Ademco Contact ID Trouble Reminder 24 Hr ANN Primary Enabled No Banner ANN Primary Modules Addr 1 8 None Time Format 12 Hr ANN Secondary Enabled No Hours Setting 12 ANN Secondary Modules Addr 1 8 None Minutes Setting 00 ANN S PG Port Serial Second Settings 00 ANN S PG Baud 9600 AM PM Setting AM ANN S PG Data Bits 7 Month Setting 01 ANN S PG Parity Even Day Setting 01 ANN S PG...

Page 134: ... Transmitter Module for connection to the RS82 Remote Station Receiver See Figure C 2 Remote Station Connection Using 4XTM Module on page 135 for installation instructions for this unit NFPA 72 Auxiliary Fire Alarm System 4XTM Transmitter Module for connection to a compatible listed Local Energy Municipal Box This unit must be installed as illustrated in the section titled 4XTM Transmitter Module ...

Page 135: ...llation on page 29 for detailed information RS82 Remote Station Receiver UL listed Refer to Instruction Manual for Remote Station Receiver Model RS82 Polarity Shown is Normal Standby 4XTM Transmitter Module Cutting TBL Jumper allows the reverse polarity circuit to open with a system trouble condition if no alarm condition exists Power limited Figure C 2 Remote Station Connection Using 4XTM Module ...

Page 136: ...ill automatically activate on any Trouble condition Form C Alarm contact programmed to activate on General Alarm NFW 50X Main Board NFW 50X Addressable Fire Control Panel Notes 1 Connection between the NFW 50X and the transmitter are supervised by the transmitter 2 This NFW 50X Transmitter arrangement can be employed for NFPA 72 Proprietary Protective Signaling System 3 Potter Electric Model EFT C...

Page 137: ...C RMT SYNC ANN BUS PRI ANN BUS SEC NAC2 NAC1 24V FACP Main Circuit Board NC 100 FCM 1 Control Module 24 VDC Nonresettable SLC Loop B B red black MBT 1 brown wire white wire EOLR 1 Power Supervision Relay Alarm polarity shown To next device on SLC Loop The addressable Control Module must be programmed as Silenceable and General Alarm Gamewell Model M34 56 Local Energy Municipal Box Note 10Ω maximum...

Page 138: ...0 m 3 225 980 m 12 AWG 3 25 mm2 Genesis 4410 Signal 98230 Belden 9583 WPW999 14 AWG 2 00 mm2 Genesis 4408 4608 Signal 98430 Belden 9581 WPW995 16 AWG 1 30 mm2 Genesis 4406 4606 Signal 98630 Belden 9575 WPW991 Direct Burial Cable Isotec NP713110VNQ S 18 AWG 0 75 mm2 Genesis 4402 4602 Signal 98300 Belden 9574 WPW975 Direct Burial Cable Isotec NP714110VNQ S FLASHSCAN MODE Twisted unshielded pair 40 o...

Page 139: ... brand notification appliances the UL Max current rating published in their data sheets must be used in order to maintain performance under low battery conditions with the maximum wire resistances shown in the table above NAC Load Amps Max allowable total loop resistance ohms CLASS B Max allowable wire pair length feet CLASS A Max allowable wire pair length feet AWG 12 solid AWG 14 solid AWG 16 so...

Page 140: ...ay HVAC SHUTDOWN When a shutdown event occurs the control module will both shut down the fans and activate the monitor module When the control module is active the monitor module will indicate a trouble condition at the FACP along with the label HVAC SHUTDOWN If using a NAC control module for HVAC shutdown monitor the state of the control module using an addressable monitor module programmed for T...

Page 141: ...OVRRIDE type code to the monitor module which will be used to override the HVAC SHUTDN control module and prevent the fans from turning off refer to Type Monitor under the section titled Edit Module Screen for Monitor Module on page 57 The HVAC OVRRIDE monitor module does not latch when activated Activating a switch connected to the monitor module will over ride all HVAC SHUTDN control relay modul...

Page 142: ...or point address 1 up to 50 for point address 50 F 2 Ademco Contact ID Typical Printout A typical printout from a Central Station receiver such as the Ademco 685 of alarm and trouble reports in the Ademco Contact ID Reporting Structure follows Notes 1 11 is an example of a Receiver Line Card showing which receiver and line card the message was transmitted to 2 Q which is the Event Qualifier for th...

Page 143: ...IC Audible Panic Burglar Alarms 130 130 Burglary BURG Burglary 131 Perimeter BURG Perimeter 132 Interior BURG Interior 133 24 Hour BURG 24 Hour 134 Entry Exit BURG Entry Exit 135 Day Night BURG Day Night 136 Outdoor BURG Outdoor 137 Tamper BURG Tamper General Alarms 140 140 General Alarm ALARM General Alarm 141 Polling loop open ALARM Polling Loop Open 142 Polling loop short ALARM Polling Loop Sho...

Page 144: ...stem Low Battery 303 RAM checksum bad TROUBLE RAM Checksum restore not applicable 304 ROM checksum bad TROUBLE ROM Checksum restore not applicable 305 System reset TROUBLE System Reset restore not applicable 306 Panel program changed TROUBLE Prog Change restore not applicable 307 Self test failure TROUBLE Self Test Failure 308 System shutdown TROUBLE System Shutdown 309 Battery test failure TROUBL...

Page 145: ...NG Group User CLOSING Group User 403 Automatic Open Close OPENING Automatic CLOSING Automatic 404 Late Open Close OPENING Late CLOSING Late 405 Deferred Open Close Opening not used Closing not used 406 Cancel OPENING Cancel CLOSING Cancel 407 Remote arm disarm OPENING Remote CLOSING Remote 408 Quick arm Opening not applicable CLOSING Quick Arm 409 Keyswitch Open Close OPENING Keyswitch CLOSING Key...

Page 146: ...2 24 Hour zone bypass BYPASS 24 Hour Bypass 573 Burglar bypass BYPASS Burg Bypass 574 Group bypass BYPASS Group Bypass Test Misc 600 601 Manual trigger test TEST Manually Triggered restore not applicable 602 Periodic test report TEST Periodic restore not applicable 603 Periodic RF transmission TEST Periodic Radio restore not applicable 604 Fire test TEST Fire Test restore not used 605 Status repor...

Page 147: ...Emergency NFW 50X Y Y Y Y Y Y IPOTS COM pre installed communicator Y 4XTM O Y O 2 2 One of the indicated modules is required when the IPOTS COM is not employed O O 2 O DP ES R or DP ES B O O O O O O NFS LBB 3 3 Listed separately O O O O O O N ANN LED 3 O O O O O Y N ANN 80 3 O O O O O Y N ANN S PG 3 O O O O O Y N ANN I O 3 O O O O O Y N ANN RLED 3 O O O O O Y N ANN RLY 3 O O O O O Y Where Y Yes N ...

Page 148: ...p values and restoral values for the NAC circuits on the FACP Output Circuit Terminal Trip Resistance in ohms Remote Sync 360K Remote Sync 330K NAC 1 2 360K NAC 1 2 320K ANN Bus A 270K ANN Bus B 265K Aux Power 370K Aux Power 320K SLC 125K SLC 320K Table H 1 Earth Fault Trip Values Circuit Trip Resistance in ohms Restore Value NAC 1 2 Shorts below 1 75K 2K NAC 1 2 Opens above 25K 23K Table H 2 NAC ...

Page 149: ...stem current draw 125 calculating the battery size 127 Canadian option 68 75 CELL CAB N 16 29 CELL MOD 16 29 cellular fault 79 central station 78 79 80 120 account code 80 communications 117 charger disable 76 CHG 120 see also battery charger 17 see also remote battery charger 13 CHG 75 see also battery charger 17 see also remote battery charger 13 class A 12 24 NAC wiring 25 class B 12 24 NAC wir...

Page 150: ...3 see also indicators 15 supervisory 102 trouble 102 LED driver 12 18 39 local alarm zone 66 local download 121 local energy municipal box service 29 local programming 47 local upload 121 loop setup 67 M maintenance alert 12 107 levels 115 maintenance program level 2 48 97 manual programming 47 master Program Level 1 48 master program level 1 49 medical alert 106 mode key 49 module add 57 addressi...

Page 151: ...ogram keys see also key panel 15 programming 46 47 annunciators 86 autoprogramming 47 exiting 48 factory default 133 level 1 48 level 2 48 manual 47 master level 1 49 modules 56 off line computer 47 via computer keyboard 46 via panel keypad 46 programming levels 48 programming screens 48 programming sheets 130 programming utility 15 16 56 proprietary yes see also remote upload 119 121 123 R read s...

Page 152: ...e 29 see also 4XTM module 12 16 trouble 103 trouble display 103 trouble relay 12 trouble reminder 68 109 111 trouble responses 104 two stage operation 66 74 101 type control module 62 detector 52 monitor module 58 NAC 73 type code control module 63 supervision 107 verification 12 U UL power limited wiring requirements 27 see also power limited and nonpower lim ited 24 upload 119 121 upload downloa...

Page 153: ...abels Carefully cut along the outside of each label Identify Function F1 F4 keys as desired and slide the labels into the keypad Starting at the center of the keypad next to the Function Keys slide each label into the groove towards the outer edge Slide in Labels ...

Page 154: ...154 NFW 50X Manual P N LS10129 001NF E C 7 25 2018 ...

Page 155: ...prevent silencing of NACs for five minutes after an alarm see manual To test the indicators LCD display and piezo Press and release the RESET button and check all indicators LEDs Every indicator LED should be on LCD shows all pixels on piezo sounder beeps For more information refer to the NFW 50X Series Manual Document LS10129 001NF E It is kept in the following location __________________________...

Page 156: ...Cut along dotted line ...

Page 157: ... IMPLIED WITH RESPECT TO THE PRODUCTS TRADEMARKS PROGRAMS AND SERVICES RENDERED BY MANUFACTURER INCLUDING WITHOUT LIMITATION INFRINGEMENT TITLE MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE MANUFACTURER SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF OR AS A RESULT OF PERSONAL COMMERCIAL OR INDUSTRIAL USES OF ITS PRODUCTS This document constitutes the ...

Page 158: ...NOTIFIER 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 www notifier com ...

Reviews: