50
NFW-50X Manual —
P/N LS10129-001NF-E:C 7/25/2018
Programming
Master Programming Level
When Autoprogramming is completed, the control panel will display the type and quantity of each device installed on the SLC loop sim-
ilar to the following display:
In the preceding example, the display indicates that the SLC Loop has 55 addressable detectors, 35 monitor modules and 30 control
modules installed.
Pressing the
ESC
key will return the display to Programming Screen #1.
3.6.2 Point Program
The Point Program option allows the programmer to add a new addressable device to the SLC loop, delete
an existing device from the loop or change the programming for an existing device. Pressing
2
, while view-
ing Programming Screen #1, will select the Point Program option and display the following screens:
Detector Programming
Pressing
1
, while viewing the Point Program Screen, will allow the programmer to add, delete or change the programming of an address-
able detector. The following screen will be displayed by the control panel:
Add Detector
Pressing
1
while viewing the Detector Screen will display the following screen which allows the programmer to add a new detector
address to programming:
A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in the three digit detector address, such
as 005. The screen will then ask whether the detector being added is wireless.
Select
1
for wired detector or
2
for wireless detector. When the choice is selected, the following screen will be displayed:
Press the down arrow key to view additional choices. Press the number corresponding to the desired selection to program that type to the
newly added detector. If the selected detector is a multi-criteria Fire (Photo)/CO detector, select
1
for
Fire CO.
When the type has been
selected, the following screen will be displayed:
# OF DET LOOP1 055
# OF MON LOOP1 035
# OF CON LOOP1 030
Autoprogram Result Screen #1
PROGRAMMING
1=AUTOPROGRAM
2=POINT PROGRAM
3=ZONE SETUP
Programming Screen #1
POINT PROGRAM
SELECT TYPE
1=DETECTOR
2=MODULE
Point Program Screen
DETECTOR
1=ADD
2=DELETE
3=EDIT
Detector Screen
ADD DETECTOR
ENTER DETECTOR#
Add Detector Screen
ADD DETECTOR
1=DETECTOR
2=DETECTOR:WIRELESS
Add Detector Screen
DETECTOR TYPE
1=SMOKE(PHOTO)
2=USER-DEFINED-1
3=SMOKE(ION)
DETECTOR TYPE
1=FIRE CO
2=USER-DEFINED-12
through
ADD DETECTOR
DETECTOR# 005
IS ADDED