90
NFW-50X Manual —
P/N LS10129-001NF-E:C 7/25/2018
Programming
Master Programming Level
ANN-LED Options
Pressing
2
for Module Options while viewing the ANN XXX Address Screen when the ANN-LED option
is selected, will display the following screens:
The first screen indicates that the N-ANN-LED at the selected ANN-BUS address is programmed to annunciate Alarms, Troubles and
Supervisories for Zones 000 through 009. The programming can be changed using ANN-LED Address Screen 2.
Pressing
1
while viewing ANN-LED Address Screen #2 will program the annunciator module to annunciate either Point (addressable
device address) information or Zone information. Each press of the
1
key will toggle the display between
Point
and
Zone
.
Pressing
2
while viewing ANN-LED Address Screen #2 will program the annunciator module to annunciate only Alarms or Alarms,
Troubles and Supervisories (ATS). Each press of the
2
key will toggle the display between
Alarms
and
ATS
.
Pressing
1
while viewing ANN-LED Address Screen #3 will select the Point or Zone range to be annunciated (refer to the tables in “
ANN-RLED Zone Option - Alarm Only
” on page 90 and “N-ANN-RLED Point Option - Alarm Only” on page 91). Pressing the
1
key
will display an additional screen where the range can be selected.
•
If Zone has been selected, and Alarms Only are to be annunciated, he new screen will give the options of annunciating Zone 000 -
029 or 030 - 049. Two N-ANN-LED modules are required to annunciate all zones in this configuration.
•
If Zone has been selected, and Alarms, Troubles and Supervisories are to be annunciated, the new screen will give the options of
annunciating Zone 000 - 009, 010 - 019, 020 - 029, 030 - 039, or 040 - 049. Five N-ANN-LED modules are required to annunciate
all zones in this configuration.
•
If Points has been selected, and Alarms Only are to be annunciated, the new screen will give the options of annunciating Points 001
- 030 and 031 - 050. Two N-ANN-LED modules are required to annunciate all points in this configuration.
•
If Point has been selected, and Alarms, Troubles and Supervisories are to be annunciated, the new screens will give the options of
annunciating Points 001 - 010, 011 - 020, 021 - 030, 031 - 040 or 041 - 050. Five N-ANN-LED modules are required to annunciate
all points in this configuration.
N-ANN-RLED Zone Option - Alarm Only
If
Zone
is selected as the module option, and the module is programmed to annunciate
alarms only
, the first ten LEDs on the N-ANN-
RLED module will display the system status information. The remaining 30 LEDs on the first module and the last 30 LEDs on the sec-
ond module will display the active/alarm status of each zone in the Zone Range programmed for that particular module. The LED assign-
ments for each N-ANN-LED module will be as follows.
Alarm Silenced
NAC 1 Fault
NAC 2 Fault
Not Used
Not Used
Earth Fault
Battery Fault
Charger Fault
Disabled
Maintenance
Zone 000
Active/Alarm
Zone 001
Active/Alarm
Zone 002
Active/Alarm
Zone 003
Active/Alarm
Zone 004
Active/Alarm
Zone 005
Active/Alarm
Zone 006
Active/Alarm
Zone 007
Active/Alarm
Zone 008
Active/Alarm
Zone 009
Active/Alarm
Zone 010
Active/Alarm
Zone 011
Active/Alarm
Zone 012
Active/Alarm
Zone 013
Active/Alarm
Zone 014
Active/Alarm
Zone 015
Active/Alarm
Zone 016
Active/Alarm
Zone 017
Active/Alarm
Zone 018
Active Alarm
Zone 019
Active/Alarm
Zone 020
Active/Alarm
Zone 021
Active/Alarm
Zone 022
Active/Alarm
Zone 023
Active/Alarm
Zone 024
Active/Alarm
Zone 025
Active/Alarm
Zone 026
Active/Alarm
Zone 027
Active/Alarm
Zone 028
Active/Alarm
Zone 029
Active/Alarm
Table 3.4 N-ANN-RLED Module #1
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Zone 030
Active/Alarm
Zone 031
Active/Alarm
Zone 032
Active/Alarm
Zone 033
Active/Alarm
Zone 034
Active/Alarm
Zone 035
Active/Alarm
Zone 036
Active/Alarm
Zone 037
Active/Alarm
Zone 038
Active/Alarm
Zone 039
Active/Alarm
Zone 040
Active/Alarm
Zone 041
Active/Alarm
Zone 042
Active/Alarm
Zone 043
Active/Alarm
Zone 044
Active/Alarm
Zone 045
Active/Alarm
Zone 046
Active/Alarm
Zone 047
Active/Alarm
Zone 048
Active Alarm
Zone 049
Active/Alarm
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Table 3.5 N-ANN-RLED Module #2
ANN XXX
1=ENABLED YES
2=MODULES INSTALLED
3=AUTO-CONFIGURE
ANN-BUS XXX Screen #2
ANN-LED - ADDR X-1
ZONES 000-009
ALARM, TRBL, SUPV
ANN-LED Address Screen #1
ANN-LED - ADDR X-1
1=POINT/ZONE ZONE
2=ALARM/ATS ATS
ANN-LED Address Screen #2
ANN-LED - ADDR X-1
1=RANGE ZN000-009
ANN-LED Address Screen #3