NFW-50X Manual —
P/N LS10129-001NF-E:C 7/25/2018
Programming
Master Programming Level
•
The F1 function key is automatically configured to perform a manual alarm signal activation when pressed.
•
The F2 function key is automatically configured to perform a two-stage bypass when pressed.
•
If NACs are set up for two-stage operation, the Silence Inhibit timer is automatically enabled and is fixed at 5 minutes.
•
AlarmNet supervision settings are fixed at 3 minutes and cannot be changed regardless of supervision programming selection.
Waterflow Silenceable
Pressing
2
while viewing System Setup Screen #3 will allow the programmer to configure the system for
silenceable on nonsilenceable waterflow circuits. Each press of the
2
key will toggle the display between
Waterflow Sil. No
and
Waterflow Sil. Yes
. When
Waterflow Sil. No
is selected, all output devices associated
with a waterflow type input device, will be nonsilenceable. When
Waterflow Sil. Yes
is selected, all output
devices associated with a waterflow type input device, will be silenceable.
Auxiliary Power
A Special Application 24 VDC power output is available at TB11 on the main circuit board. Pressing
1
while viewing System Setup Screen #4 displays the following:
Select the AUX 1 output. The following screen will be displayed.
Aux 1 can be programmed for Class A wiring. If Aux 1 is to be wired for Class A, press
1
. Each press of the
1
key will cause the display
to toggle between
Class A Yes
and
Class A No.
In addition, the aux power output can be programmed as resettable or non-resettable power. Non-resettable power is suitable for power-
ing annunciators while resettable power is suitable for powering smoke detectors. Each press of the
1
key will cause the display to toggle
between
Resettable Yes
and
Resettable No.
Trouble Reminder
The Trouble Reminder features causes the control panel piezo to sound a reminder ‘beep’ for alarms and
troubles, after the panel has been silenced. Refer to “Trouble Reminder” on page 68, for a detailed descrip-
tion of this feature. Pressing
2
while viewing System Setup Screen #4 will cause the display to toggle to
Trouble Rem 4
or
Trouble Rem 24
, which enables this feature for resound at either 4 or 24 hours, respec-
tively. Each press of the
2
key will cause the display to toggle between
Trouble Rem 4
or
Trouble Rem 24
.
Refer to the table on page 46 for permissible settings.
Language
The language option is used to change the text on the panel display to either English or French. Pressing the
3
key will cause the display to offer a choice of
1=English
and
2
=
French.
Charger Enable
If using an external battery charger, the FACP battery charger must first be disabled. Pressing
1
while view-
ing System Setup Screen #5 will cause the display to toggle to
Charger Enab No
, which will allow the use
of an external battery charger. Each press of the
1
key will cause the display to toggle between
Charger
Enab. No
and
Charger Enab. Yes
.
4XTM Supervision
If a 4XTM Transmitter Module is installed in the system, supervision must enabled in user programming.
Pressing
2
while viewing System Setup Screen #5 will cause the display to toggle to
4XTM Supv Enab. Yes
,
which means there is a 4XTM installed. Each press of the
2
key will cause the display to toggle between
4XTM Supv Enab. No
and
4XTM Supv Enab. Yes
. Refer to the table on page 46 for permissible settings.
Remote Sync Enable
Synchronization is a feature that controls the activation of notification appliances in such a way that all
devices will turn on and off at exactly the same time. Refer to Section 2.5, “Remote Synchronization Out-
put”, on page 26 for more information. To enable remote synchronization, press the
3
key while viewing
System Setup Screen #5. Each press of the key will toggle the screen between
Rem Sync Enab Yes
and
Rem
Sync Enab No
.
SYSTEM SETUP
1=CANADIAN OPT. OFF
2=WATERFLOW SIL. NO
System Setup Screen #3
SYSTEM SETUP
1=AUX POWER
2=TROUBLE REM 24HR
3=LANGUAGE ENGLISH
System Setup Screen #4
AUX POWER
1=AUX 1
AUX 1
1=CLASS A YES
2=RESETTABLE YES
SYSTEM SETUP
1=AUX POWER
2=TROUBLE REM 24HR
3=LANGUAGE ENGLISH
System Setup Screen #4
SYSTEM SETUP
1=AUX POWER
2=TROUBLE REM 24HR
3=LANGUAGE ENGLISH
System Setup Screen #4
SYSTEM SETUP
1=CHARGER ENAB YES
2=4XTM SPV ENAB NO
3=REM SYNC ENAB YES
System Setup Screen #5
SYSTEM SETUP
1=CHARGER ENAB YES
2=4XTM SPV ENAB NO
3=REM SYNC ENAB YES
System Setup Screen #5
SYSTEM SETUP
1=CHARGER ENAB YES
2=4XTM SUPV ENAB NO
3=REM SYNC ENAB YES
System Setup Screen #5