78
NFW-50X Manual —
P/N LS10129-001NF-E:C 7/25/2018
Programming
Master Programming Level
POTS Settings
The POTS settings configure the system when telephone lines are used to contact central station. Pressing
2
while viewing the Communicator Screen #1 will display the following.
POTS Line (X)
If telephone lines are connected to the IPOTS-COM board at J4 (Line 1) and J5 (Line 2), their settings can be configured by pressing
1
or
2
, respectively. Pressing
1
or
2
will display the following screen. The programming options for Line 1 and Line 2 are identical.
Phone Line (X) Enable
To enable the phone line, press
1
while viewing the POTS Line (X) Screen #1 to change the display to
Enabled Yes
. Each press of the
1
key will cause the display to toggle between
Enabled Yes
and
Enabled No.
Type
To select the type, press
2
while viewing the POTS Line (X) Screen #1. The following screen will be dis-
played:
Press
1
to select Touchtone dialing,
2
to select Rotary dialing with a make/break ratio of 67/33 or
3
to select Rotary dialing with a
make/break ratio of 60/40.
Supervised Phone Line
The Supervised Phone Line feature allows the user to disable the supervision of Phone Lines when using an
alternate means of secondary transmission path. The factory default setting is Phone Line (X) super-
vised.Supervision must be set to
Yes
if the selected transmission path is POTS.
Pressing
1
for
Supervision
while viewing the POTS Line (X) Screen #2 will change the screen to read
Supervision No
. Each press of the
1
key will toggle the option between
Supervise Yes
and
No
. Refer to the
table on page 46 for permissible settings.
Gains
The Gains value is the telephone’s transmitting “volume control”. To adjust the settings, press
3
while
viewing the POTS Settings screen. The following screen will be displayed:
The Gains value can be adjusted for when the telephones lines are in use for Dialing and Reporting. Press
1
or
2
to change these values,
respectively. The following screen will display for both options.
Press
1
for
Low
,
2
for
Normal
, and
3
for
High
. After the Gains value has been selected, the display will return to the Gains Screen.
COMMUNICATOR
1=INSTALLED NO
2=POTS SETTINGS
3=IP SETTINGS
Communicator Screen #1
POTS SETTINGS
1=LINE 1
2=LINE 2
3=GAINS
POTS Settings Screen
POTS LINE X
1=ENABLED YES
2=TYPE TOUCHTONE
3=SUPERVISED YES
POTS Line X Screen
POTS LINE X
1=ENABLED YES
2=TYPE
3=SUPERVISED YES
POTS Line X Screen
TYPE
1=TOUCHTONE
2=ROTARY 67/33
3=ROTARY 60/40
Type Settings Screen
POTS LINE X
1=ENABLED YES
2=TYPE
3=SUPERVISED YES
POTS Line X Screen
POTS SETTINGS
1=LINE 1
2=LINE 2
3=GAINS
POTS Settings Screen
GAINS
1=DIALING NORM
2=REPORTING NORM
Gains Screen
GAINS
1=LOW
2=NORMAL
3=HIGH
Gains Screen