NFW-50X Manual —
P/N LS10129-001NF-E:C 7/25/2018
81
Master Programming Level
Programming
The Communication Format is determined by the type of receiver that the Communicator is transmitting to.
Consult your Central Station
for proper selection or consult our factory representatives. For any format chosen, the control panel automatically programs all of the
event codes.
Select the Communication Format by pressing the corresponding number key while viewing the Comm Format screen. The following
table describes each format:
Test Time Interval
Pressing
1
while viewing POTS (XXX) Comm Path #4 will cause the following screens to be displayed:
The test report sent to the Central Station phone number may be sent once every 6, 8, 12, or 24 hours. Select the desired Test Time Inter-
val by pressing the corresponding digit in the screens shown above. Refer to the table on page 46 for permissible settings.
24 Hour Test Time
Pressing
2
while viewing POTS (XXX) Comm Path #4 will cause the following screen to be displayed:
Use the 24 Hour Test Time screen to program the time that the Communicator will transmit the 24 Hour Test to the Central Station. A
flashing cursor will appear in the lower left corner of the screen. Enter a four digit number representing the test time using military time
(0000 = midnight and 2359 = 11:59PM).
Ethernet
To configure the communication method to contact central station as an ethernet connection, select
2
for
Ethernet
from the Comm Path Screen. The following screens will display.
Enable
To enable the Ethernet connection, press
1
while viewing the Ethernet Options Screen #1 to change the display to
Enabled Yes
. Each
press of the
1
key will cause the display to toggle between
Enabled Yes
and
Enabled No.
Central Station Account
Press 2 on Ethernet Options Screen #1 to display the following:
Enter the
City ID
,
Central Station ID
, and
Account Code
all provided by the monitoring station..
Screen Selection
Communication Format Description
ADEMCO CONTACT ID
Contact ID, DTMF, 1400/2300 ACK
SIA 8
Security Industry Association, 8 messages per call
SIA 20
Security Industry Association, 20 messages per call
Table 3.2 Communication Formats
POTS XXX COMM PATH
1=TEST TIME INT 24
2=24HR TEST TIME 0100
POTS Comm Path Screen #4
TEST TIME INTERVAL
1=24 HOURS
2=12 HOURS
3=8 HOURS
Test Time Interval Screen #1
TEST TIME INTERVAL
1=6 HOURS
Test Time Interval Screen #2
POTS XXX COMM PATH
1=TEST TIME INT 24
2=24HR TEST TIME 0100
POTS Comm Path Screen #4
24 HOUR TEST TIME
RANGE 0000-2359
24 Hour Test Time Screen
XXX COMM PATH
1=POTS
2=ETHERNET
3=CELLULAR
Comm Path Screen #1
ETHERNET OPTIONS
1=ENABLED NO
2=CS ACCOUNT
Ethernet Options Screen #1
ETHERNET OPTIONS
1=SUPV. SETTINGS
NFPA 2010 DUAL PATH
Ethernet Options Screen #2
ETHERNET OPTIONS
1=ENABLED YES
2=CS ACCOUNT
Ethernet Options Screen #1
CS ACCOUNT
1=CITY ID 0000
2=CS ID 0000
3=ACCT CODE 000000
Central Station Account Screen
NOTE:
When using Ethernet as the primary and Cellular as secondary, the three CS account codes must be the same for both paths.