86
NFW-50X Manual —
P/N LS10129-001NF-E:C 7/25/2018
Programming
Master Programming Level
3.6.8 Annunciators
Pressing
3
while viewing Programming Screen #3 will cause the control panel to display the following
screens:
A printer module, graphic annunciator module, LCD annunciator module, LED annunciator module, and relay module can be pro-
grammed into the NFW-50X system. These devices communicate with the FACP over the ANN-BUS terminals on the control panel.
ANN-BUS Setup
Two ANN-BUS circuits are available on the NFW-50X. Press
1
to configure the Primary ANN-BUS or
press
2
to configure the Secondary ANN-BUS. The following screens will be displayed for either ANN-
BUS circuit where
(XXX)
indicates either
Primary
or
Secondary
..
ANN-BUS Enabled
The ANN-BUS must be enabled if any modules are connected to the ANN-BUS terminals. To enable the ANN-BUS, press
1
while
viewing ANN-BUS screen #1 so that the display reads
ANN (XXX) Enabled Yes.
Each press of the
1
key will cause the display to toggle
between
ANN
(XXX) Enabled Yes
and
ANN (XXX) Enabled No
.
Modules Installed
If an ANN-BUS module is installed, press
2
for
Modules Installed
to select ANN-BUS addresses for the
module(s). The only difference between the two programming screens are the addresses. The Primary Bus
module addresses will have a prefix of “1-” while the Secondary Bus module addresses will have a prefix
of “2-”. The following screen will be displayed for either bus circuit.
Pressing the down arrow key will allow the programmer to view additional screens displaying Addresses 1-8. To select one or more
addresses for the installed module(s), press the number key corresponding to the module address in each screen. The following screen
will be displayed for each address:
Pressing
1
for
Type
will display the following screens:
Press the number corresponding to the module/device type that is installed with the selected address.
If ANN-I/O, ANN-LED, or ANN-RLY is the selected module type, the following ANN-BUS Address Screen will be displayed:
PROGRAMMING
1=HISTORY
2=COMMUNICATOR
3=ANNUNCIATORS
Programming Screen #3
ANN-BUS SELECT
1=PRIMARY
2=SECONDARY
3=ANN-BUS OPTIONS
ANN-BUS SELECT
1=PRIMARY
2=SECONDARY
3=ANN-BUS OPTIONS
Annunciators Screen
ANN XXX
1=ENABLED NO
2=MODULES INSTALLED
3=AUTO-CONFIGURE
ANN-BUS Screen #1
ANN XXX
1=CLASS A NO
ANN-BUS Screen #2
ANN XXX
1=ENABLED NO
2=MODULES INSTALLED
3=AUTO-CONFIGURE
ANN-BUS (XXX) Screen #1
ANN-BUS MODULES
1=ADDR. X-1 NONE
2=ADDR. X-2 NONE
3=ADDR. X-3 NONE
ANN-BUS Modules Screen #1
ANN-BUS MODULE X-1
ANN-BUS ADDRESS
1=TYPE NONE
ANN-BUS Address Screen
Module Type Screen #1
Module Type Screen #2
Module Type Screen #3
ANN-BUS MODULE TYPE
1=NOT INSTALLED
2=ANN-80 MODULE
3=ANN-100 MODULE
ANN-BUS MODULE TYPE
1=ANN-I/O MODULE
2=ANN-S/PG MODULE
3=ANN-LED MODULE
ANN-BUS MODULE TYPE
1=ANN-RLY MODULE
NOTE:
If the module type selected is the
ANN-80, ANN-100, or ANN-S/PG,
or if
Not Installed
is selected, the ANN-BUS Address Screen
shown on the previous page will be displayed following the module selection. The options selected for each of these modules will be the
same for all modules of the same type (refer to “
ANN-BUS MODULE X-1
ANN-BUS ADDRESS
1=TYPE ANN-I/O
2=MODULE OPTIONS
ANN-BUS Address Screen