Master Programming Level
Programming
The
Lock Enable
option allows the programmer to select whether or not any installed N-ANN-80 or N-ANN-100 annunciator must be
unlocked by its key before any annunciator key presses will function. Pressing
2
while viewing the ANN-80/100 Options Screen #1
causes the display to toggle between
Lock Enable Yes
(annunciator must be unlocked for keys to function) and
Lock Enable No
(lock
position is ignored). Refer to the table on page 46 for permissible settings.
The Acknowledge Button Enable
(ACK BTN ENABLE)
option allows the programmer to select whether the Ack/Step button on any
installed N-ANN-80 or N-ANN-100 annunciator will function normally or always be ignored. Pressing
3
while viewing the ANN-
80/100 Options Screen #1 causes the display to toggle between
Ack Btn Enable Yes
(Ack/Step button functions normally) and
Ack Btn
Enable No
(Ack/Step button never functions).
The Silence Button Enable
(SIL BTN ENABLE)
option allows the programmer to select whether the Silence button on any installed N-
ANN-80 or N-ANN-100 annunciator will function normally or always be ignored. Pressing
1
while viewing the ANN-80/100 Options
Screen #2 causes the display to toggle between
Sil Btn Enable Yes
(Silence button functions normally) and
Sil Btn Enable No
(Silence
button never functions).
The Reset Button Enable (
RST BTN ENABLE
) option allows the programmer to select whether the Reset button on any installed N-
ANN-80 or N-ANN-100 annunciator will function normally or always be ignored. Pressing
2
while viewing the ANN-80/100 Options
Screen #2 causes the display to toggle between
Rst Btn Enable Yes
(Reset button functions normally) and
Rst Btn Enable No
(Reset but-
ton never functions).
The Drill Button Enable (
DRL BTN ENABLE
) option allows the programmer to select whether the Drill button on any installed N-ANN-
80 or N-ANN-100 annunciator will function normally or always be ignored. Pressing
3
while viewing the ANN-80/100 Options Screen
#2 causes the display to toggle between
Drl Btn Enable Yes
(Drill button functions normally) and
Drl Btn Enable No
(Drill button never
functions).
3.6.9 Password Change
The factory set passwords, which have been programmed into the control panel, can be changed by select-
ing the Password Change option. Pressing
1
while viewing Programming Screen #4 will cause the follow-
ing screen to be displayed:
Press
1
to change the Master Programming Level password,
2
to change the Maintenance Level password or
3
to change the Remote
Download password.
Note that the passwords will not be displayed on LCD annunciators.
The following screen will appear when any change option is selected:
A flashing cursor will appear in the center of the display. Enter a new eight digit password (such as 10101010 for the Master Level).
After the eighth digit is entered, the following screen will be displayed:
Re-enter the new password to accept the change. The display will return to the initial Password Change Screen.
Invalid Password
If a password is entered incorrectly, the panel will display
Invalid Message
and a code.
The programmer may hit the escape key and re-enter the password correctly. However, if the password has been forgotten, record the 20-
character code and contact NOTIFIER Technical Services. After proper authentication, the master password will be supplied to the pro-
grammer.
PROGRAMMING
1=PASSWORD CHANGE
2=CLEAR PROGRAM
3=PROGRAM CHECK
Programming Screen #4
PASSWORD CHANGE
1=MASTER
2=MAINTENANCE
3=REMOTE DOWNLOAD
Password Change Screen
ENTER NEW EIGHT DIGIT
PASSWORD
Enter Password Screen
VERIFY NEW PASSWORD
Password Change Screen
INVALID PASSWORD
Invalid Password Screen