NFN Gateway Embedded Installation
Network Communication Module Installation
22
NFN Gateway Installation & Operation Manual - P/N: 52306:Rev: D 06/01/07
2.5 Network Communication Module Installation
Step 1. Install the type of NCM W/F PC board you will use into the new CAB3/CAB4 cabinet or
an existing panel’s or annunciator’s cabinet.
Use the Network Control Module PC board configuration that fits your installation needs.
• NCM-W with twisted pair wire.
• NCM-F with fiber-optic cable.
Figure 2.5 NCM W/F PC Board Installation Document
Step 2. After this installation is perform
“NFN Gateway Power Connection” on page 23
When using an NCM-W/F, it can be powered by a panel/annunciators power source or the
supplied NFN gateway’s power supply (
for power supply specifications.
Figure 2.6 NCM-W/F Power Connection
NOTE:
For installation details, refer to the document that ships with NCM board.
12 Clintonville Road
Northford, CT 06472-1653 USA
203-484-7161 • FAX 203-484-7118
www.notifier.com
NCM Installation Document
Network Communications Module NCM-W, NCM-F
y
p
y
PN 51533:B 11/29/2005 05-238
1 UL 864 Compliance
1.1 Products Subject to AHJ Approval
This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire
Alarm Systems, UL 864 9th Edition.
The following products have not received UL 864 9th Edition certification and may only be used in retrofit applications.
Operation of the NCM-W, NCM-F with products not tested for UL 864 9th Edition has not been evaluated and may not
comply with NFPA 72 and/or the latest edition of UL 864. These applications will require the approval of the local
Authority Having Jurisdiction (AHJ).
•
AM2020/AFP1010
•
MIB
•
NAM-232
2 Product Overview
The Network Communications Module (NCM) provides a means for connecting specific Notifier fire alarm control
products to
NOTI•FIRE•NET™
. There are two types of NCMs available: NCM-W for connecting nodes with
twisted-pair wire, and NCM-F for connecting nodes with fiber-optic cable.
In most applications, one NCM is required per
NOTI•FIRE•NET™
node (including fire alarm control panels and
network annunciators) . Even though the NCM has two NUP ports, only one may be connected to a
NOTI•FIRE•NET™
.
node. Except in some DVC applications, do not connect two NCMs via NUP ports (aka “NUP to NUP”).
For instructions on the additional capabilities available with the DVC, refer to the
DVC Manual
.
•
Input power requirements: 24 VDC , 0.11 amps, regulated, power-limited compatible power supply UL/ULC listed
for fire protective signalling use.
•
Communications circuit requirements: Refer to the
NOTI•FIRE•NET™
Manual (Network Version 4.0 and Higher)
for wiring length and threshold information.
NOTE:
The NCM-W/F it can be powered by customer supplied external power supply, it should
be UL listed for fire protective signaling systems, power limited and regulated.
+5VDC Output
Earth
+24VDC Input
24VDC REF Input
To NCM NUP Port
5V REF Output
Red wire
Black wire
P/N 75583
NOTE:
For complete details on powering and connecting an NCM-W/F, refer to the document
that was shipped with it.