RP-2001 Series Manual —
P/N 52985:D5 1/26/2017
83
Read Status
Operating Instructions
Alarm/Shorted Condition
When in audible Walktest, the panel responds to each new alarm and activates its programmed
control outputs for four seconds, for
any
mapped NAC (silenceable or non-silenceable activation).
It also stores each alarm in the walktest history file which can be sent to an optional printer. The
stored display will be the same as if the device actually activated except the colon (
:
) in the time
stamp is replaced with an asterisk (
*
).
Open Condition
Initiating Device Circuits as well as all main circuit board NACs are monitored for fault conditions
during Walktest mode. When a new trouble condition occurs, the FACP will activate all NACs
programmed for Walktest, then shut them off after eight seconds.
While in Walktest, the trouble relay is activated and the system Trouble indicator flashes (as in all
of the Program and status change operations). The alarm relay is not activated.
4.15 Read Status
Read Status functions do not require a password. The control panel will continue to provide fire
protection while in Read Status mode. This mode can be entered while the control panel is in alarm
or trouble. If a new alarm occurs during these functions, the Read Status is exited to prevent
confusion.
Read Status Entry
When the operator presses the control panel
Enter
key, the LCD will display the following:
Pressing
1
, while this screen is being displayed, will cause the control panel to enter the Read
Status mode which allows the user to view and print the programmed features and status of the
control panel.
The following screens will be displayed:
4.15.1 FACP Configuration
Pressing
1
while viewing Read Status Screen #1 will display the type of configuration programmed
into the FACP (refer to “FACP CONFIG (Application Templates)” on page 51). As an example, if
Template 7 was programmed as the FACP configuration, the following screen will be displayed:
1=READ STATUS MODE
2=PROGRAMMING MODE
READ STATUS
1=FACP CONFIG
2=INPUT ZONES
3=OUTPUT CIRCUITS
READ STATUS
1=CROSS INPUT ZONES
2=ON-BOARD RELAYS
3=SYSTEM SETTINGS
Read Status Screen #1
Read Status Screen #3
READ STATUS
1=TIMERS
2=DAYLIGHT SAVINGS
3=HISTORY
Read Status Screen #2
READ STATUS
1=PRINT
2=ANN-BUS
Read Status Screen #4
READ FACP CONFIG
TEMPLATE 7
SINGLE HAZARD
3 ZONE