84
RP-2001 Series Manual —
P/N 52985:D5 1/26/2017
Operating Instructions
Read Status
4.15.2 Input Zones
Pressing
2
while viewing Read Status Screen #1 will cause the following screens to be displayed:
Pressing the down arrow key will allow the selection of Zones 4-6.
The operator selects the zone which is to be viewed by pressing the number corresponding to the
desired zone in each screen. For example, if
1
is pressed in the first screen, the display will change
to a screen similar to the following:
Pressing the down arrow key, while viewing the screen shown above, will allow the operator to
view additional programming information about the selected device, such as:
•
Enable/Disable Status
•
Device Type
•
Output Circuit MAP
•
Adjective/Noun descriptor
4.15.3 Output Circuits
Pressing
3
while viewing Read Status Screen #1 will display the following screens:
The operator can press
1
to view the programmed options for Output 1,
2
to view the programmed
options for Output 2,
3
to view the programmed options for Output 3, or
4
to view the programmed
options for Output 4.
The resulting screens will display the following information:
•
Enable/Disable Status
•
Circuit Type
•
Silenceable/Nonsilenceable
•
Auto Silence Enable/Disable and time delay (in minutes)
•
Silence Inhibit Enabled/Disabled
•
Coding Selection (Temporal, Steady, etc.)
4.15.4 Cross Input Zones
Pressing
1
while viewing Read Status Screen #2 will display the following screens:
READ INPUT ZONES
1=ZONE 1
2=ZONE 2
3=ZONE 3
READ INPUT ZONE 1
NORMAL PULL STATION
PRESS TO VIEW
READ STATUS
1=FACP CONFIG
2=INPUT ZONES
3=OUTPUT CIRCUITS
Read Status Screen #1
READ OUTPUTS
1=OUTPUT 1
2=OUTPUT 2
3=OUTPUT 3
READ OUTPUTS
1=OUTPUT 4
Read Outputs Screen #2
Read Outputs Screen #1
READ STATUS
1=CROSS INPUT ZONES
2=ON-BOARD RELAYS
3=SYSTEM SETTINGS
Read Status Screen #2
CROSS INPUT ZONES
1=RELEASE 1
2=RELEASE 2
Cross Input Zone Screen