RP-2001 Series Manual —
P/N 52985:D5 1/26/2017
99
Template 2: Single Hazard - Cross-Zone With Manual Release
FACP Configuration Templates
B.2 Template 2: Single Hazard - Cross-Zone With Manual
Release
Table Legend:
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on
corresponding output circuit).
C
x =
cross-zone where
x
is the number of the Release Solenoid. All inputs with the same Release
Solenoid number must be active at the same time to turn on the corresponding solenoid output
circuit
Input Zone Types:
•
Zone 1 = 2-wire smoke
•
Zone 2 = Fire
•
Zone 3 = Waterflow - activation delayed for 60 seconds (Waterflow Delay set to 60 secs.)
•
Zone 4 = Manual Release
•
Zone 5 = Pull Station
•
Zone 6 = Supervisory
Output Circuit Types:
•
Output 1 = Alarm NAC, silenceable, coded for steady on
•
Output 2 = Waterflow NAC - activation delayed for 60 seconds (Waterflow Delay set to 60
sec), silenceable, coded for steady on
•
Output 3 = Release Solenoid 1 (unsupervised for shorts)
•
Output 4 = Supervisory Bell NAC, silenceable, coded for steady on
Timers
•
Soak Timer 1 - set for 10 minutes
•
Soak Timer 2 - set for 10 minutes
•
Waterflow Delay Timer - set for 60 seconds
•
AC Loss Delay Timer - set for 2 hours
Operation
•
Activation of both Input Zone 1 (2-Wire Smoke)
and
Zone 2 (Fire) at the same time,
or
Zone
4 (Manual Release)
or
Zone 5 (Pull Station) will operate the Release Solenoid 1 Output #3.
Release Solenoid will turn off water release following time-out of the 10 minute Soak Timer 1.
Activation of any one of these zones will operate Alarm NAC Output #1
•
Activation of Input Zone 3 (Waterflow) will operate the Waterflow NAC Output #2. There is a
60 second FACP initiated delay in activation since Waterflow Delay Timer is set to 60 seconds
•
Activation of Input Zone 6 (Supervisory) will operate the Supervisory Bell NAC Output #4
Template 2: CROSS-ZONE WITH MANUAL RELEASE SWITCH
INPUT ZONES
1
2
3
4
5
6
OUTPUT CIRCUITS
2-WIRE SMOKE
FIRE
WATERFLOW
MANUAL
RELEASE
PULL
STATION
SUPV.
#1 ALARM NAC
X
X
X
X
#2 WATERFLOW NAC
X
#3 RELEASE SOLENOID 1
C1
C1
X
X
#4 SUPV. BELL NAC
X