RP-2001 Series Manual —
P/N 52985:D5 1/26/2017
17
Components
Product Description
•
Fire Alarm - red indicator
•
Supervisory - yellow indicator
•
AC Power - green indicator
•
System Trouble - yellow indicator
•
Alarm Silenced - yellow indicator
•
Discharge - red indicator
Local Piezo Sounder
A piezo sounder provides separate and distinct sounds for alarm, trouble, maintenance and
supervisory conditions as follows:
•
Alarm - on steady
•
Trouble - pulse 1 second on and 1 second off
•
Maintenance - pulse ½ second on and ½ second off
•
Supervisory - pulse ½ second on and ½ second off
1.4 Components
Main Circuit Board
The main circuit board contains the system’s CPU and other primary components and wiring
interface connectors. Optional modules plug in and are mounted to the main circuit board.
Power Supply
One FLPS-7 power supply is provided standard with each FACP, mounted to a chassis.
Cabinet
The backbox measures 16.65” (42.29 cm) x 19.0” (48.26 cm) x 5.207” (13.23 cm) and provides
space for two batteries (up to 18 Amp Hours). Also available are the optional dress panel
(DP-51050 [red] and trim-ring TR-CE [red]. The Canadian version is supplied standard with a
modified dress panel and one N-ANN-LED annunciator module.
Batteries
The cabinet provides space for two 18 Amp Hour batteries (larger batteries require use of a UL
listed battery box such as the NFS-LBB or BB-26). Batteries must be ordered separately.
1.5 Optional Modules and Accessories
N-CAC-5X Class A Converter Module
The N-CAC-5X Module can be used to convert the Style B (Class B) Initiating Device Circuits to
Style D (Class A) and Style Y (Class B) Output Circuits to Style Z (Class A). The modules connect
to J2 and J7 on the FACP main circuit board. Note that two Class A Converter modules are required
to convert all six Initiating Device Circuits and four Output Circuits.
4XTM Transmitter Module
The 4XTM provides a supervised output for local energy municipal box transmitter and alarm and
trouble reverse polarity. It includes a disable switch and disable trouble LED. A module jumper
option allows the reverse polarity circuit to open with a system trouble condition if no alarm
condition exists. he 4XTM mounts to the main circuit board connectors J4 & J5.
ANN-SEC Secondary ANN-BUS Module
The ANN-SEC module provides another ANN-BUS port for more wiring flexibility and for
Canadian applications requiring remote annunciation.