Programming
Master Programming Level
If the Parallel Port option is selected, the user has the ability to select an
Offline Timer
by pressing
3
while viewing Print Options screen #1. The resultant screen allows the programmer to program
the
Offline Timer
for a delay of between 0 and 255 seconds before loss of printer supervision is
reported as a trouble.
If the Serial Port option is selected, the
Printer Supv
and
Offline Timer
options will not be available.
The Baud Rate, Data Bits, Parity and Stop Bits options are only available when the Serial Port
option has been selected.
Pressing
1
for
Baud Rate
while viewing Printer Options screen #2 will cause a screen to appear
which allow the user to select a Baud Rate of
19200, 9600 or 2400
.
Pressing
2
for
Data Bits
while viewing Printer Options screen #2 will cause screens to appear
which allow the user to select
5, 6, 7,
or
8 Data Bits
.
Pressing
3
for
Parity
while viewing Printer Options screen #2 will cause a screen to appear which
allows the user to select between
No Parity
,
Even Parity,
or
Odd Parity
.
Pressing
1
for Stop Bits while viewing Printer Options screen #3 will cause a screen to appear
which allows the user to select between
0.5
,
1.0,
or
2.0 Stop Bits
.
ANN-I/O LED Zone Assignments
The information displayed by LEDs on every N-ANN-I/O module is not programmable and will
therefore be as indicated in the following table.
LED
Zone (any address)
1
AC Fault
2
General Alarm
3
General Supervisory
4
General Trouble
5
Alarm Silenced
6
Earth Fault
7
Battery Fault
8
Charger Fault
9
Disable
10
Maintenance
11
Zone 1 Alarm
12
Zone 2 Alarm
13
Zone 3 Alarm
14
Zone 4 Alarm
15
Zone 5 Alarm
16
Zone 6 Alarm
17
Not Used
18
Not Used
19
Not Used
20
Not Used
21
Zone 1 Trouble
22
Zone 2 Trouble
23
Zone 3 Trouble
24
Zone 4 Trouble
25
Zone 5 Trouble
26
Zone 6 Trouble
27
Not Used
28
Not Used
29
Not Used
30
Not Used
31
Zone 1 Supervisory
32
Zone 2 Supervisory
33
Zone 3 Supervisory
34
Zone 4 Supervisory
35
Zone 5 Supervisory
36
Zone 6 Supervisory
37
Not Used
38
Not Used
39
Not Used
40
Not Used