RP-2001 Series Manual —
P/N 52985:D5 1/26/2017
69
Master Programming Level
Programming
ANN-80 Options
Pressing 2 while ANN-BUS screen #2 will display the following screen:
The
Piezo Enable
option allows the programmer to select whether the piezo sounder on any
installed N-ANN-80 annunciator will ever sound. Pressing
1
while viewing the ANN-80 Options
Screen #1 causes the display to toggle between
Piezo Enable Yes
and
Piezo Enable No
.
The
Lock Enable
option allows the programmer to select whether or not the N-ANN-80 LCD
annunciator must be unlocked by its key before any annunciator key presses will function. Pressing
2
while viewing the ANN-80 Options Screen #1 causes the display to toggle between
Lock Enable
Yes
(annunciator must be unlocked for keys to function) and
Lock Enable No
(lock position is
ignored). A trouble will generate at the panel if
Lock Enable Yes
is selected for an unlocked N-
ANN-80.
The Acknowledge Button Enable
(ACK BTN ENABLE)
option allows the programmer to select
whether the Ack/Step button on any installed N-ANN-80 LCD annunciator will function normally
or always be ignored. Pressing
3
while viewing the ANN-80 Options Screen #1 causes the display
to toggle between
Ack Btn Enable Yes
(Ack/Step button functions normally) and
Ack Btn Enable No
(Ack/Step button never functions).
The Silence Button Enable
(SIL BTN ENABLE)
option allows the programmer to select whether the
Silence button on any installed N-ANN-80 LCD annunciator will function normally or always be
ignored. Pressing
1
while viewing the ANN-80 Options Screen #2 causes the display to toggle
between
Sil Btn Enable Yes
(Silence button functions normally) and
Sil Btn Enable No
(Silence
button never functions).
The Reset Button Enable
(RST BTN ENABLE)
option allows the programmer to select whether the
Reset button on any installed N-ANN-80 LCD annunciator will function normally or always be
ignored. Pressing
2
while viewing the ANN-80 Options Screen #2 causes the display to toggle
between
Rst Btn Enable Yes
(Reset button functions normally) and
Rst Btn Enable No
(Reset button
never functions).
The Drill Button Enable
(DRL BTN ENABLE)
option allows the programmer to select whether the
Drill button on any installed N-ANN-80 LCD annunciator will function normally or always be
ignored. Pressing
3
while viewing the ANN-80 Options Screen #2 causes the display to toggle
between
Drl Btn Enable Yes
(Drill button functions normally) and
Drl Btn Enable No
(Drill button
never functions).
ANN-RLY Options
Pressing
1
for
ANN-RLY Options
while viewing ANN-BUS Screen #3 will cause the following
screen to be displayed:
ANN-80 OPTIONS
1=PIEZO ENABLE
2=LOCK ENABLE
3=ACK BTN ENABLE
ANN-80 Options Screen #1
ANN-80 OPTIONS
1=SIL BTN ENABLE
2=RST BTN ENABLE
3=DRL BTN ENABLE
ANN-80 Options Screen #2
NOTE:
If Canadian Option is enabled and an ANN-80C LCD Canadian annunciator is installed,
the programming screens will display the Canadian annunciator button options instead of the
options shown above.
PROGRAMMING
1=ANN-RLY OPTIONS
2=ANN-LED OPTIONS
ANN-BUS Screen #3
ANN-RLY OPTIONS
1=RELAY 1 IN ZONE 1
2=RELAY 2 IN ZONE 2
3=RELAY 3 IN ZONE 3
ANN-RLY Options Screen