70
RP-2001 Series Manual —
P/N 52985:D5 1/26/2017
Programming
Master Programming Level
The N-ANN-RLY module provides ten Form-C relays which can be programmed for various
functions. The initial screen displays Relays 1 through 3. Pressing the down arrow key will display
the remaining relays for this module.
To program any of the N-ANN-RLY relays, while viewing the appropriate ANN-RLY Option
screen, press the number key corresponding to the relay to be programmed. Following is a list of
the available programming options for each relay:
•
General Alarm
•
General Trouble
•
General Supervisory
•
Future Use
•
Future Use
•
Future Use
•
General Discharge
•
Discharge Release 1
•
Discharge Release 2
•
AC Loss
•
Waterflow Delay
•
Future Use
•
Future Use
•
Future Use
•
General 2nd Shot Release
•
2nd Shot Release 1
•
2nd Shot Release 2
•
Input Zone 1
•
Input Zone 2
•
Input Zone 3
•
Input Zone 4
•
Input Zone 5
•
Input Zone 6
3.5.8 History
The History option allows an authorized user to view or erase events which have occurred in the
control panel. Pressing
2
while viewing Programming Screen #3 will display the History options as
shown in the following display:
View Events
Pressing
1
while viewing the History Screen will allow the user to select the events to be viewed as
illustrated in the following:
PROGRAMMING
1=ANN-BUS
2=HISTORY
3=WALKTEST
Programming Screen #3
HISTORY
1=VIEW EVENTS
2=ERASE HISTORY
History Screen
HISTORY
1=VIEW ALL
2=VIEW ALARMS
3=VIEW OTHER EVENTS
View Events Screen