80
RP-2001 Series Manual —
P/N 52985:D5 1/26/2017
Operating Instructions
Supervisory Operation
•
Third line in display:
Zone 1
indicates the zone programmed to this device which, in this
example, is Input Zone 1.
•
Fourth line in display:
Time; the current time in this example is
10:00A
which represents 10:00 AM
Date; the current month, day and year in this example is
09
for September,
18
for the 8th day
of the month and
14
for the year 2014
4.6 Supervisory Operation
Supervisory operation is similar to alarm operation but with the following differences:
•
The piezo sounder pulses ½ second On and ½ second Off
•
The Supervisory indicator flashes ½ second On and ½ second Off
•
The LCD displays the status label
Active Supervisory
along with the device name, type,
adjective/noun, associated zones and time/date
•
The output circuits programmed as Supervisory NAC are activated
•
The supervisory relay is activated
•
The alarm relay is not activated
•
Silenced alarms are not resounded
•
Timers are not started
•
Store event in history buffer
A typical Supervisory event would be displayed as illustrated in the following:
In the preceding example:
–
FROZEN SUPRV -
indicates zone detector is below approximately 45
o
F
Note that, like alarms, supervisory signals latch (except when programmed for supervisory
autoresettable). Supervisory alarms do not cause resound as do other alarm conditions. Open
circuits in supervisory wiring are processed by the control panel the same way as other trouble
conditions. Refer to “Alarm Operation” on page 79, for a description of the information displayed
on the control panel LCD.
4.7 Disable/Enable Operation
Input zones which are disabled do not cause an alarm or any zone activation. Disabled NACs are
held in the off state. Disabled zones/NACs are treated as if they were in trouble, with the exception
being the LCD status label that will be displayed is
DISABL
.
Note that disabled Releasing Circuits are treated as
supervisory
events.
4.8 Waterflow Circuits Operation
If an alarm exists from a zone that is a waterflow non-silenceable type, the Alarm Silence key will
not function.
FREEZE SUPERVISORY
<ADJ> <NOUN>
ZONE 05 FROZEN SUPRV
10:00A 091814