RP-2002 Series Manual —
P/N 53039:E6 1/26/2017
81
Indicators
Operating Instructions
piezo sounder and LCD display segments after the
Reset
key is released. Any alarm or trouble that
exists after a reset will resound the system.
Note that if Silence Inhibit has been enabled, the FACP cannot be reset for one minute following
initiation of an alarm.
4.2 Indicators
The eight indicators, which are located on the front panel, operate as follows:
AC Power
This is a green indicator which illuminates if AC power is applied to the FACP. A loss of AC power
will turn off this indicator.
Fire Alarm
This red indicator flashes when one or more alarms occur. It illuminates steady when the
Acknowl-
edge/Step
or
Alarm Silence
key is pressed. The Fire Alarm indicator turns off when the
Reset
key is
pressed. The indicator will remain off if all alarms have been cleared.
Supervisory
This is a yellow indicator that flashes when one or more supervisory conditions occur, such as a
sprinkler valve tamper condition. It illuminates steady when the
Acknowledge/Step
or
Alarm
Silence
key is pressed. It turns off when the
Reset
key is pressed and remains off if all supervisory
alarms have been cleared.
Trouble
This is a yellow indicator that flashes when one or more trouble conditions occur. It stays on steady
when the
Acknowledge/Step
or
Alarm Silence
key is pressed. The indicator turns off when all trou-
ble conditions are cleared. This indicator will also illuminate if the microprocessor watchdog cir-
cuit is activated.
Alarm Silenced
This is a yellow indicator that illuminates after the
Alarm
Silence
key is pressed while an alarm
condition exists. It turns off when the
Drill
or
Reset
key is pressed.
Pre-Discharge
Pre-discharge is a yellow indicator that indicates a releasing event has been initiated and the releas-
ing delay timer has been started.
Discharge
This is a red indicator that illuminates steadily when the agent releasing circuit is activated and a
discharge is taking place.
Abort
This is a yellow indicator that illuminates steadily to indicate that an input Abort circuit has been
activated to interrupt an agent release.
4.3 Normal Operation
With no alarms or troubles in the system, the display message is
System All Normal
along with the
current time and date as shown below. To set the time and date, refer to the appropriate section in
this manual.
SYSTEM ALL NORMAL
10:00A 092314